Loading…
Loading…
Tender Value
₹12.7 L
EMD Value
₹32,000
Closing Date
29 Oct 2026, 5:30 pm
Karnataka Urban Water Supply and Drainage Board
Rahul
Providing water supply facility to Bhutnal tanda by supply, erection, commissioning and trail run of 2 Nos of 25 HP mono block submersible pump set along with accessories at Bhutnal WTP under 15th Finance tied grants for the year 2023-24.
KUWSDB/2026-27/WS/WORK_INDENT554
KUWSDB/2026-27/WS/WORK_INDENT554
Open
Water supply/sewage lines
Two Tender Document System(Two Cover)
KUWSDB Vijayapura Division
5 documents required · 3 mandatory · 2 optional
Department Registration Details
Total value of civl engineering works executed and payments received in the last five years (year-wise)
List of existing commitments and ongoing work
List of works for which tenders already submitted
Banker Details
Work done certificate
Audited CA certificate of Annual Turnover
Fill and upload all the annexures / required documents as per uploaded Bid document
₹500
₹32,000
29 Sept 2026
29 Sept 2026
31 Oct 2026
22 Oct 2026
BILL OF QUANTITIES.
Name of Work: Providing water supply facility to Bhutnal tanda by supply, erection, commissioning and trail run of 2 Nos of 25 HP mono block submersible pump set along with accessories at Bhutnal WTP under 15th Finance tied grants for the year 2023-24.
Sl. No. Qty. Items UNIT RATE (Rs) AMOUNT (Rs)
1 2 Pump & Motor: Supply & delivery at site Kirloskar/Sam Turbo/Jyothi/M &P/ WPIL/Beacon Weir/Flow more or any other make approved by the Board mono block submersible pump set confirming to IS 8034-2000 specifications, to work site with testing of as per instructions of engineer incharge of work and latest amendments etc. complete. and the following descrption: a) Duty condition: Min. 25HP or Suitable HP Capable of delivering of 20LPS/ of Treated water against a total head of 60-80mtrs. Including suction lift of 3 mtrs b) Speed: Duty condition should be met at 1460 RPM. c) Shutt off head: Min 110% & Max 130% of the specified head d) Minimum Efficiency: 76%. i) Casing cast Iron. ii) Impellor- CF 8 M iii) Shaft-Stainless steel shaft-SS 410 iv) Stuffing Box- Graphite Asbestos packing v) Wear rings- Phosphor Bronze vi) Gland-Cast Ir vii) Inter stage ring Phosphor Bronze viii) Shaft sleeve & nuts- Bronze ix) Neck ring - Bronze f) Driving end bearing: Grease lubricated roller/ball/journal g) Non driving end bearing: Grease lubrcated deep groove h) Coupling: Suitable size vibration proof flexible coupling i) Base plate: Heavy duty common CI/MS base plate for pump and motor wth suitable 'I' section girders, channels, plates, bolts & nuts etc. NOTE: (1) The duty point of the pump should be to the left of the BEP. 2) The pump is required to work at an altitude of 550.00 mtr. above MSL and at a max, ambient temperature of 450 C (1.1) Motor:- a) Protection: IP 55 b) Insulation: 'F' class c) Ambient temperature: 450C d) Cushion: 10% more than power required by the pump and capable of providing rated output upto + or 10% voltage variation and/or + or -3% frequency variation or combination e ) Driving end bearng: Grease lubricated roller bearng f) Non driving end bearing: Grease lubricated ball bearing etc., complete with all lead and lift as directed by Engineer in Charge Each 300000.00 600000.00
2 60 DOUBLE FLANGED PIPES AND SPECIALS. Supply & delivery at site brand new best indigenous double flanged 8.00 mm thick M.S. Pipes and specials suitable for test pressure equivalent to twice the working pressure. The pipes should be coated with Food grade epoxy primer coat of 45 micron thick and 2 coats of food grade Nonphelic / nontoxic Berger / Poladian / Akzo Noble make epoxy paint of 80 microns thick each coat inside and anticorrossive paint outside. The pipe should be tested as per IS 3589 / 1996. The welding should be done as per IS 2825-1969. The thickness of flanges should confirm to IS 6392 - 1971. For delivery side: Minimum 150 mm dia or suitable size flanged pipes. etc., complete with all lead and lift as directed by Engineer in Charge mtr 2500.00 150000.00
3 4 Minimum 150 mm dia or suitable size MS radial bend. etc., complete with all lead and lift as directed by Engineer in Charge Each 1500.00 6000.00
4 1 Minimum 150 mm or suitable dummy flange 20mm thick. etc., complete with all lead and lift as directed by Engineer in Charge Each 2000.00 2000.00
5 15 Delivery Manfold: Supply and delivery at site brand new best indegenious make MS pipe manfold of 8.00mm valve thickness and 150 mm dia etc., complete with all lead and lift as directed by Engineer in Charge Mtr 2500.00 37500.00
6 2 Minimum150 x 150 x 100 mm dia or suitable size flanged Tee with radial branch etc., complete with all lead and lift as directed by Engineer in Charge Each 1254.00 2508.00
7 2 Dismantling joint Suppling Ductile Iron Push on special confirming to IS 9523:2000 - D.I. PN 16.0 Dismantling Joints Diameter 150 mm etc., complete with all lead and lift as directed by Engineer in Charge Each 5842.20 11684.40
8 2 Fixing DI/CI specials of mechanical jointing of different sizes after setting into the pipe line system, including cleaning, introducing rubber gasket to proper alignment and lightening with bolts and nuts. The cost includes hire charges of tools and plants with appurtenances etc Diameter 150 mm Working pressure 16KG per cm2 (PN 16) etc., complete with all lead and lift as directed by Engineer in Charge Each 48.30 96.60
9 2 Delivery Side Sluice Valve: Supplying and fixing DI Resilient seated soft sealing SLUICE VALVE of variouis dia. with body bonnet of ductile iron (DI) conforming to IS-1865 and of grade GGG 40/50, shaft of stainless steel, wedge fully rubber lined with EDPM seals of NBR and the valves should be vacum tight and 100% leak proof with face to face dimensions as per IS 14846-2000 only. The stem sealing should be with toroidal sealing rings (minimum 2 “ O “ rings). Body and bonut should be coated with Electrostatically applied Epoxy Powder Coating with minimum coating thickness of 250 micron both inside and outside. The rate is inclusive of cost of valves, T.P set, galvanized bolts & nuts and rubber insertions etc. but excluding earth work. (Note: TP set should be considered only for DI pipes estimate. For MS pipes estimates, TP sets cost of corresponding dia shall be deducted from the SR rates of valves and provision for corresponding dia MS flanges should be made in the estimate.) 150 mm dai PN 16 on suction & deliver side etc., complete with all lead and lift as directed by Engineer in Charge Each 22207.50 44415.00
10 1 Control panel board units with star delta starter Supply and delivery at site reputed make approved by the Board floor mounting, free standing, cubicle type control panel board unit of adequate size to fix all the following items and suitable for operation on 3 phase 50 cycles 380/440 volts AC supply fitted with the following: 80 Amps MCCB with current setting range of 63-80 amps of C&S/Hawalls/BCH/CGL/Alstom/GEmake or any other make approved by the Board of 25 KA breaking capactiy with U/V release, shunt release and with suitable thermal release. 1 No. Phase indicating lamps with switches of C&S/ BCH/Hawells/GE make or any other make approved by the Board- 1 set Digital type panel mounting type Ammeter of suitable CT ratio of Board approved make - 1 NO. Digital type panel mounting type Voltmeter of suitable CT ratio of Board approved make - 1 NO. MS air insulated bus bar chamber with 4 Nos 80 Amps. 5 MVA Air insulated bus bar made of high conductivity, high strengh aluminium alloy complying with the requirements of grade E91 E of I5 5082. suitably braced with non-hygrosco-pic SMS supports. Provision shall be made in the bus bar chamber for one incoming and three outgoing feeders. The bus bar chamber should be of adequate capacity to handle the incoming and out-going cables and for fixing the switchgears as per requirement-1 No. 63 A Amps heavy duty triple pole change over fuse switch comprising of two switches mounted on common chasis. complete with handle assembly door interlock and pad locking arrangement with mechanical linkage shorting. links and 60 Amps capacity HRC fuses in sheet metal enclosure of Board approved make conforming to the latest ISS 4064-1 Dual parameter Power factor/energy meter of Board approved make-1 No 16 A amps TP mcb in sheet metal enclosure conforming to the letest ISS 4064 for capacitor circuit, of Board approved make-2 No. 32 amps DP load break heavy duty switch fuse unit with rewireable fuses in sheet metal enclosure conforming to the letest ISS 4064 for lighting circuit, of Board approved make-1 No. Cable entries and terminals suitable for numbers, type and size of aluminium conductor power cables, etc ISet. NOTE:- 1) The Panel board shall be complete with all other required fittings, and shall be fabricated using 2 mm thick sheet steel and suitable size copper cable/copper wire painted with two coats of a highly corrosion resistant primer applied wet on wet and a finishing coat of synthetic enamel paint of the ash greay shadea finishing coat of synthetic enamel paint of the ash grey shade 2) HRC fuses links suitable for motor duty shall be provided to 80 Amps change over switch fuse unit. 3) HRC fuse link rated not less than 1.5 times the rates current of the capacitor bank shall be provided in the 32 Amps capacity switch fuse unit for capacitor circuit. 4) The internal wiring shall be done using adequate size 5) The Bus bar chamber should be of adequate size to accommadate all incoming, outgoing cables and required switch gears. 6) Mounting a 200 Amps, 4 Pole Change over switch with HRC fuses of suitable capacity and any Board approved make in a Compartment with Door, Interlock and providing Aluminium Busbar for the Termination of Cables from the Two Transformers. 7) The Painting should be done using seven Tank Process. etc., complete with all lead and lift as directed by Engineer in Charge Each 100000.00 100000.00
11 2 FCMA based Soft Starter: Supply & delivery of 25 HP soft starter based on Flux compensated magnetic amplifier technology of Innovative Technomics make or any other make approved by the Board for smooth starting by torque control and reduction in starting current etc.The soft starter should have 1No-300Amps and 1No-265Amps Air break contactor for make and break. The entire status of operation & fault should be displayed on a 7 segment 5 digit Digital display with its meaning on the front panel door. Resin cast dualcore Current transformers of suitable ratio, 0.5-60 Secs pnuematic on and off delay timer for automatic change over from reduced voltage to full voltage, BCH make or any other make approved by the Board-1 No. Start-Stop push buttons, conforming to the latest ISS 6875 BCH/C&S make or any other make approved by the Board - 1 Set Motor ON Indicating lamp of BCH/ C&S make or any other make approved by the Board - 1 No. Panel mounting version digital type Ammeter of suitable CT ratio Prok devices make or any other make approved by the Board-1 No. Panel mounting version digital type Voltameter of suitable CT ratio Prok devices make or any other make approved by the Board-1 No. C.T.operated thermal over load relay GE/ Alstom/Easun C&S make or any other approved make - 1 No. Single phase preventor of Minilec/Proke Davy's make or any other make approved by the Board-1No. Under/over voltage relay. of GE/ Alstom/Easun C&S make or any other make approved by the Board with built in PT's for each phase- 1 No. Indicating lamps, RED, GREEN AND AMBER LAMP of rating 230 volts AC of BCH/ C&S make or any other make approved by the Board-1 Set Alarm bell suitable for 230V, AC, 50 HZ-1 No. Cable box with compression type cable glands for incoming cables-1 No. Cable box with compression type cable glands for out going cables-1 No. Earth leakage relay with core balanced current transformer of GE/ Alstom/Easun C&S make or any other make approved by the Board-1 No. Aux relay for alarm protection and cancellation-1 No. Control terminals and power terminals- 1 Set NOTE: 1. The starter panel shall be fabricated using 16 SWG sheet, steel flats and suitable size angle iron. 2. All copper joints shall be electrotinned. 3. The control wiring shall be done using 1100 volts grade adequate size multicore copper cable of Finolex/ Uniflex make. 4. All the control wiring shall be properly ferruled. 5. The circuit shall be designed for close transition using 6. The starter panel is required for intallation at an altitudenot exeeding 0 m above MSL and the maximum ambient air temperature of 45 degree C. 7. The starter panel shall be complete with all other required fitting and first fillings of oil. 8. The panel shall be designed to conform to the requirement of the latest IS 8623, factory built assembly of switch gears and control gears. 9.The inter connections shall be done using adequate size insulated electrolytic copper strip and copper cable. 10. The Starter shall be suitable for Six starts per hour. 11. The Painting should be done using Seven tank process. etc., complete with all lead and lift as directed by Engineer in Charge Each 70000.00 140000.00
12 150 Main side Cable:Supply and delivery at site Calama / SBEE / Ravin / Chandresh / Nicco / Mysotech/ or other make approved by Board 3.50 Core 95 Sq mm Alluminium conductors PVC sheathed 1.1 KV class UG Cable conforming to the latest ISS 1554. etc., complete with all lead and lift as directed by Engineer in Charge Mtr. 373.22 55982.25
13 100 Load side cable : Supply and delivery at site brand new SBEE / Ravin / Chandresh / Nicco or other make approved by Board 3.00 core 50 Sqmm Aluminium standard conductors PVC insulated sheated steel tape / wire armoured PVC outer sheated 1.1 KV class LG cable confirming to the latest ISS 1554. etc., complete with all lead and lift as directed by Engineer in Charge Mtr. 178.97 17897.30
14 30 Capacitor Calbe : Supply and delivery at site brand new SBEE / Ravin / Chandresh / Nicco or other make approved by Board 4 core 10 Sqmm Aluminimum standard conductors PVC insulated sheated steel tape / wire armoured PVC outer sheated 1.1 KV UGD cable confirming latest ISS 1554. etc., complete with all lead and lift as directed by Engineer in Charge Mtr. 118.00 3540.12
15 2 Erection of pumpsets:- Erection of CF pumpsets on the existing main girder including formation of machine foundation using suitable size M.S channels cross girders, plate girders bolts & nuts, washers etc., complete. Lowering of bowl assembly, column pipe assembly into the jackwell and fixing of discharge head in position true to line, maintaning the VSS motor vertical alignment, dynamic balancing and linking to delivery line using delivery pipes from jackwell. Proper packing of the holes in the walls of jackwell after laying pipe with cement concrete 1:2:4 etc., complete with all lead and lift as directed by Engineer in Charge Job 15000.00 30000.00
16 1 Laying and jointing of MS pipes and specials for suction and delivery connections of the pump using suitable size bolts, nuts, packing etc., complete including fixing foot valve, all types of valves, gauges, strainers, delivery and suciton manifold. The work shall includie providing pipe supports, thrusts block in CC 1:2:4 prop., wherever necessary upto the end of the delivery manifold, using all the required materials such as sand, cement jelly including making holes in sump, pump house for laying suction and delivery pipes, packing of holes with CC 1:2:4 etc., complete with all lead and lift as directed by Engineer in Charge Job 12500.00 12500.00
17 90 Earth work excavation for cable trench of 0.5 to 0.75 Mtr. Width and Depth upto 1 Mtr including trial pits, depositing on bank upto a lead of 50 Mtr, Supplying and Displaying necessary Danger Boards and Lighting, Using sight Rails and Sign Boards at every 100 Mtr wherever necessary as directed.. L-150, W-0.6, D-1 etc., complete with all lead and lift as directed by Engineer in Charge Cum 260.00 23400.00
18 40 Spreading and forming with sand all round the cable to a depth of 75 mm and width of 500 mm. (Does not include cost of sand). L-100 etc., complete with all lead and lift as directed by Engineer in Charge Mtrs 148.10 5924.00
19 50 Laying of cable in Existing Trench/GI pipe/Stone Ware/RCC Hume pipe using Wooden/Aluminum Rollers as directed by the departmental staff a)3.5 x95 Sqmm 11 KV XLPE cable- etc., complete with all lead and lift as directed by Engineer in Charge Mtrs 72.00 3600.00
20 90 Refilling the cable trenches with selected available earth from trench excavation including watering, consolidation in layers of 15 cm. Thickness including depositing of the surplus earth with a lead of 200 Mtr etc., complete with all lead and lift as directed by Engineer in Charge Cum 58.00 5220.00
21 100 Laying of cable in Existing Trench/GI pipe/Stone Ware/RCC Hume pipe using Wooden/Aluminum Rollers as directed by the departmental staff a)3.5 x 50Sqmm 11 KV XLPE cable- etc., complete with all lead and lift as directed by Engineer in Charge Mtrs 31.14 3113.90
22 30 Laying of Capacitor Cable : Running the cable in existing ducts including properly securing cable in position etc., complete using all the required materials etc., complete i) 3 core 30 Sqmm (load side cable) etc., complete with all lead and lift as directed by Engineer in Charge Mtr 16.15 484.50
23 8 Cable Terminations: Termination of cable using copper ring to the terminal end for solderless crimping to aluminimum conductors by adopting crimping tool. i)3.50 Core 50 sqmm 1100 volts class cable main side 7.21.14 etc., complete with all lead and lift as directed by Engineer in Charge Each 10.00 80.00
24 24 ii)3 Core 35 sqmm 1100 volts class cable load side 7.21.12 etc., complete with all lead and lift as directed by Engineer in Charge Each 5.00 120.00
25 24 iii)3 Core 30 sqmm 1100 volts class cable (Capacitor) 7.21.12 etc., complete with all lead and lift as directed by Engineer in Charge Each 3.00 72.00
26 24 Power Shunt Capacitors:- Supply and delivery at site brand new EPCOSmake approved by Board low loss, high efficient 2x 80 KVAR power shunt capacitors conforming to ISS 2834, suitable for operation on 3 phase, 50 Hz., 380 / 440 volts, AC supply required form maintaining the power factor of the installation at not less than 0.95 lagging. a) The capacitor shall be provided with a suitable discharge device to reduce the voltage between the terminals, to allowable level within one minute. b) Terminal cover on all the units and bank shall be provided. etc., complete with all lead and lift as directed by Engineer in Charge KVAR 432.00 10368.00
Total 1266506.07
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
Final BOQ Bhtnal Tanda.xlsx
Others - BOQ • 0.02 MB
Bhutnal Tender Bid Document final.docx
Tender Document • 3.34 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .