Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹2.0 CrAccepted-AOC | ₹2.0 Cr | L1 | Accepted-AOC Quoted lowest value |
| 2 | L2₹2.2 Cr+₹11.2 L (5.46%)Rejected-AOC | ₹2.2 Cr+₹11.2 L (5.46%) | L2 | Rejected-AOC Rate quoted higher than L1 |
| 3 | L3₹2.2 Cr+₹16.4 L (8.04%)Rejected-AOC | ₹2.2 Cr+₹16.4 L (8.04%) | L3 | Rejected-AOC Rate quoted higher than L1 |
| Sl No | Description | Qty | Unit | Ravi Electricals L3 | KARTHIKEYAN ELECTRICALS L1 | ANNAI ELECTRICALS L2 |
|---|---|---|---|---|---|---|
| 1.00 | HT Double Pole structure
Supply and erection of 11kV 2 pole structure comprising 2 numbers 33feet with RS Joist of size 200x100x5.7mm centre to centre 10 feet width with tie and support frame by 100x50x6mm RS channels, cross bracings by 50x6mm RS angles with requisite heavy duty clamps, bolts & nuts to support the switch gears, insulators, 0 copper jumpers and accessories to receive and distribute the 11 kV 2Pole structure of consumer side and painting of all metal parts with one coat of Zinc Chromate primer and two Coats of aluminium paints-Complete Set with following HT accessories as per the CEA regulations.
(a) 1 set of 3 nos 11 KV post top DISC insulators with Channels 12 feet length and earthing.
(b) 11 KV 3 insulator tilting Type AB Switch with operating rod, 2 Nos of 12 feet length supporting channels and earth connection.
(c) One set of 3 nos 11 KV HG/Drop Out fuse with 11KV PT Insulators, Supporting Channels of 12 feet Length-2 Nos, Cross Supporting channels, earth connection, etc.
(d) 1 Set of 3 Nos. 11 KV Lightning Arrester with Supporting Channels of 12 feet Length and earth connections etc.,
(e) 1 Set of 3 Nos. 11 KV Pin Insulator with GI Pin and Stool, Supporting Channels of 100mm x 50 mmx 12 feet length with earth Connections etc., for Jumper Supporting. | 1 | No. | 6,00,000 ₹6,00,000 | 4,90,000 ₹4,90,000 Lowest | 6,16,000 ₹6,16,000 |
| 1.01(h) The RYB 3 Nos. of Overhead No.0 SWG Copper Wire from EB DP Structure to Consumer EB structure and AB Switch to Transformer with colouring of No. 0 SWG copperWire , Complete painting of DP Structure with one coat of Zinc Chromite primer and two Coats of aluminium paints-Complete Set. The Work should be strictly carried out based on CEA Regulations. | ||||||
| 2.00 | Design manufacturing Supply, erection, testing, commissioning and handing over of 11KV 25KA HT single panel outdoor vacuum Circuit Breaker Switch Board panel with following specifications, VCB Comprising one number 630 A 25 KA drawout VCB as incoming | 1 | No | 6,00,000 ₹6,00,000 | 5,30,000 ₹5,30,000 Lowest | 6,16,000 ₹6,16,000 |
| 2.011).Horizontal Draw out VCB fitted with manual and motor operated spring charging machanism with 230V AC motor & motor control switch mechanical ON/OFF indicator operation counter, automatic safety shutters&mech push button. | ||||||
| 2.022.) Voltage sensors, sensors are core less devices for sensing line voltage in MEDIUM VOLTAGE SYSTEM 3.) Current sensors,cordless type does not saturate, rated current 250A suited to load current 20A to 415A. | ||||||
| 2.034.)Numerical comprehensive feeder manager MF 790C with inbuilt features of protection measurment/Automation communication/ control maximum demand and control management feeder manager accepts input from current and voltage sensors, 10 protection group settings 100fault records, 500 event record eith 120 simultaneous events facility in each record 15 Digital inputs 8 digital outputs with digital CB control front universal serial Bus (USB) PORT can be used 10 connect to a laptop/personal computer.flear end RS485 PORT also provided IEC60870-5-103 | ||||||
| 2.045)110VDC Hooter arrangements | ||||||
| 2.056)11kV,630A,25kA copper Busbar with PVC sleeve | ||||||
| 2.067) Suitable size of Earth Bus | ||||||
| 2.078)Heater ON/OFF switch with filament type heater & Single phase switch with socket,Lamp for panel illumination with snap type door limit switch,fuses/MCBs for AC/DC control. | ||||||
Tender Value
₹2.0 Cr
EMD Value
₹1.1 L
Closing Date
17 Sept 2025, 3:00 pmClosed
Superintending Engineer PWD Buildings Sivagangai
Superintending Engineer PWD Buildings C M Circle Sivagangai 630562
Providing HT Supply with Double pole structure and Single Panel Vacuum Circuit breaker arrangements Transformer Diesel Generator Lift Luminar flow with HEPA filter Air conditioner units and street light arrangements
2025_PWD_599711_1
17 SE Buildings C M Circle Sivagangai 2025 2026 dt 26 08 2025 5
Open Tender
Electrical Works
Lump-sum
120 days
Paramakudi in Ramanathapuram District
Please refer Tender documents.
9 documents required · 9 mandatory
₹0
₹1.1 L
16 Dec 2025
4 Sept 2025
18 Sept 2025
4 Sept 2025
17 Sept 2025
4 Sept 2025
Amount
HT Double Pole structure Supply and erection of 11kV 2 pole structure comprising 2 numbers 33feet with RS Joist of size 200x100x5.7mm centre to centre 10 feet width with tie and support frame by 100x50x6mm RS channels, cross bracings by 50x6mm RS angles with requisite heavy duty clamps, bolts & nuts to support the switch gears, insulators, 0 copper jumpers and accessories to receive and distribute the 11 kV 2Pole structure of consumer side and painting of all metal parts with one coat of Zinc Chromate primer and two Coats of aluminium paints-Complete Set with following HT accessories as per the CEA regulations. (a) 1 set of 3 nos 11 KV post top DISC insulators with Channels 12 feet length and earthing. (b) 11 KV 3 insulator tilting Type AB Switch with operating rod, 2 Nos of 12 feet length supporting channels and earth connection. (c) One set of 3 nos 11 KV HG/Drop Out fuse with 11KV PT Insulators, Supporting Channels of 12 feet Length-2 Nos, Cross Supporting channels, earth connection, etc. (d) 1 Set of 3 Nos. 11 KV Lightning Arrester with Supporting Channels of 12 feet Length and earth connections etc., (e) 1 Set of 3 Nos. 11 KV Pin Insulator with GI Pin and Stool, Supporting Channels of 100mm x 50 mmx 12 feet length with earth Connections etc., for Jumper Supporting.
(h) The RYB 3 Nos. of Overhead No.0 SWG Copper Wire from EB DP Structure to Consumer EB structure and AB Switch to Transformer with colouring of No. 0 SWG copperWire , Complete painting of DP Structure with one coat of Zinc Chromite primer and two Coats of aluminium paints-Complete Set. The Work should be strictly carried out based on CEA Regulations.
Design manufacturing Supply, erection, testing, commissioning and handing over of 11KV 25KA HT single panel outdoor vacuum Circuit Breaker Switch Board panel with following specifications, VCB Comprising one number 630 A 25 KA drawout VCB as incoming
1).Horizontal Draw out VCB fitted with manual and motor operated spring charging machanism with 230V AC motor & motor control switch mechanical ON/OFF indicator operation counter, automatic safety shutters&mech push button.
2.) Voltage sensors, sensors are core less devices for sensing line voltage in MEDIUM VOLTAGE SYSTEM 3.) Current sensors,cordless type does not saturate, rated current 250A suited to load current 20A to 415A.
4.)Numerical comprehensive feeder manager MF 790C with inbuilt features of protection measurment/Automation communication/ control maximum demand and control management feeder manager accepts input from current and voltage sensors, 10 protection group settings 100fault records, 500 event record eith 120 simultaneous events facility in each record 15 Digital inputs 8 digital outputs with digital CB control front universal serial Bus (USB) PORT can be used 10 connect to a laptop/personal computer.flear end RS485 PORT also provided IEC60870-5-103
5)110VDC Hooter arrangements
6)11kV,630A,25kA copper Busbar with PVC sleeve
7) Suitable size of Earth Bus
8)Heater ON/OFF switch with filament type heater & Single phase switch with socket,Lamp for panel illumination with snap type door limit switch,fuses/MCBs for AC/DC control.
9)MS sheet steel enclosure & installation suitable for indoor
10)Incoming arrangements (Excluding cable termination kits, lugs and glands)
11)Outgoing arrangements (Excluding cable termination kits, lugs and glands)
12)Suitable Power pack (230V AC/110V DC)
13) Surge arrester (9kV,10kA) .
Supply and laying of 1RX3C x 240 sq.mm 11 KV HT XLPE UE cable in a trench to be excavated at a depth of 1.00 metre and covering the cable through suitable cement truff and refilling the earth to make good .
Supply and clamping of 1RX3C x 240 sq.mm 11 KV HT XLPE UE on post or wall with MS Clamps.
Supply and providing cable suitable 11KV 3 core 240 -300 sqmm XLPE HT UG cable with necessary outdoor type heat shrinkable Termination kit CONSISTS OF RIGHT ANGLE / STRAIGHT BOOTS, WRAP AROUND SLEEVES, INSULATION TAPE, BUTYL SEALANT, CONSTANT FORCE SPRING, CLAMPS, TINNED COPPER BRAIDS ETC with termination complete (M-seal/ Rechym/ Densonmake).
Construction of plinth with suitable concrete foundation for 500KVA outdoor transformer and 630A 11kV single panel outdoor VCB as per standard specifications as directed by departmental officers suitable for installation of above equipments.
Supply, erecting, testing and commissioning of 500 KVA, 11KV/433V, off - load tap changing copper wound outdoor type distribution transformer confirming to IS 1180 - Level 2 with HT & LT Cable Entry Boxes, Copper Extension for Cable End Termination for HT & LT sides, Bucholz Relay, Marshaling Box, Wheels, Channels etc., and fitted with the following:
(a) HV Bushing terminal arrangements
(b) LT cable end box suitable for 3 runs of 3½ x 400 sq.mm LTUG cable.
(c) Conservator with shut off valve.
(d) Dehydrating Silicagel Breather
(e) Conservator drain plug valve
(f) Tank drain plug valve
(g) 4 Nos. plain rollers
(h) Thermometer pocket with thermometer with capillary tubing for maximum reading position
(i) Drain plug valve
(j) Filter valve
(k) Oil filling whole with cap
(l) Oil level gauge
(m) Two body earthing terminal
(n) Rating and terminal marking diagram plate
(o) Lifting hooks/Lifting eyes/Jacking pad to facilitate movement to transformer and easy ground level
(p) Off load hand operated tap changing switch at stand by height from ground level
(q) Tapping on primary winding for voltage variation +5% to -5%
(r) Neutral on L.V side to be available for 4 wire supply and brought out for earthing
(s) Air release device
(t) The transfsormer should be supplied with first filling of oil
(u) All removable covers shall be provided with weather proof hot oil resistance gaskets to prevent leakage of water into core and oil from the tank ) with suitable Current Transformer Accuracy Class of 5P10 in suitable Metallic enclosure for transformer neutral - earth link terminal with necessary connections complete.Make and model should be approved by the departmental officers before used on work.
Supply and laying of 3run 3½ x 400 sq.mm PVC armoured LTUG cable in a trench to be excavated at a depth of 0.75 metre putting 0.15 mt. Layer of sand and covering the cable completely with bricks and sand and refilling the earth to make good.
Supply and clamping of 3runs 3-1/2 x 400 sq.mm. aluminium PVC LTUG armoured cable on post or on wall with MS clamps.
Design, & fabrication of & Commissioning of Sheet Steel
enclosed, Dust & Vermin Proof, 800A single tier MV ACB
Floor Mounting Pattern, Cubicle Type Panel made up of
1.6 mm CRCA Sheet Steel with powder coating, segregation
of Incoming & outgoing feeders, Busbar, Cable chamber
the outgoing feeders should be necessary clearance to
terminate the outgoing cables with suitable capacity,
necessary SMC. Busbar insulator supports, base frame
of 75mm x 50 mm x 3mm with black colour paints all
Busbars insulated with RYB colored heats shrinkable
sleeves Busbars joints are duly tined, necessary GI bolt
nuts washers and spring washers etc. following switch
gears & feeders.
E.B Incoming:-- 1No 800A FP MDO type ACB, Shunt & UV
release – 1 Nos Incoming Metering ; 96 sq.mm Digital type Multifunction meter –1 nos (VAF ) Earth Fault Relay – 1 no, RYB indication lamps - 1 set
E.B Bus Bar 2"x 1/2" Copper Flat Per Phase, neutral, earth two runs
Outgoing:-
Outgoing:-
630A TPN Main with HRC Fuse .– 2 Nos with interconnection copper flat of 1 1/2" x 1/2"
400A TPN Main with HRC Fuse .– 2 Nos. with interconnection copper flat of 1 " x 1/2"
315A TPN Main with HRC Fuse .– 2 Nos. (For existing Building & spare) with interconnection copper flat of 1 " x 1/2"
250A TPN Main with HRC Fuse .– 2 Nos. with interconnection copper flat of 1 " x 1/4"
200A TPN Main with HRC Fuse .– 2 Nos. with interconnection copper flat of 1 " x 1/4"
Bus Bar Supports All Bus Bars supports by using MS
supported SMC insulating materials.
Bus Bar Insulations: All Bus Bars insulated by RYBN
Colored Heat Shrinkable Sleeves. Joints : All Bus Bar
Joints tinned and galvanized bolt nuts with plate & spring
washers INTERLOCKING ARRANGEMENT
1. Both the EB & Bus couplers mechanically interlocked
with Three lock two key systems
(Make and model should be approved by department officers before use on work .
Supply and providing HT yard link fencing with fixing of 8ft height in RCC concreted pillar of size 0.7ft x 0.75ft by excavated the earth with depth of 2ft putting concrete pillar and refilling the earth to make good and fixing of chain link fencing with size of (2"x2")x10SWG galvanised iron wire all around the HT yard with necessary binding wire with ISI earthing. RCC pillar with chain link fencing should be provided Suitable for to cover the Six Pole Structure, transformer and Supplier's Double pole structure for seperate the EB yard and consumer supply yard places. HT yard is provided with two gate entries, where one entry for EB side and another entry for consumer side. Each gate is fabricated using 2" GI pipe as outer frame with weldmesh with necessary support. Earthing the fencing by using no.8 SWG copper wire all around the fencing. Earthing of gate by using 25mmx3mm copper flat, filling the yard with 400mm jelly for a height of 0.50feet from ground level to make good.
Preparation of site plan, physical layout, electrical line
schematic diagram 10 sets, getting drawing approval from
CEIG, preparation of completion report, rectification report,
etc., and arranging CEIG inspection and obtaining safety
certificate from CEIG, and preparation of one set approved drawing and copy of safety certificate in a neat frame work fixed in panel room and getting HT supply from TNEB
Providing suitable concrete foundation with plain cement concrete 1:2:4 using 20mm jelly for wearing coat including laying, compacting, finishing and curing etc., complete as per standard specifications and as directed by the departmental officers for 250kVA Genset (Data 18)
Supply, Testing Commissioning and Handing over of 250 KVA Diesel Generator set with acoustic enclosure conforming to CPCB IV+ Norms and BIS Specifications of 0.8 P.F. Three phase 415V/ 420 Volts, 50Hz, 1500 RPM CPCB approved capacity developing 310 HP with acoustic enclosure water cooled clock wise rotating feed pump with 200KW / 250KVA operating capacity brushless alternator close coupled underneath fuel tank standard safeties LLOP with stop solenoid battery with lead Electric start and vibration fitting and accessories and AMF panel as detailed below including transporting & unloading charges.
(A) Engine: Water cooled diesel engine suitable for Generator application conforming CPCBIV+ norms and IS standards with a shaft out put of 310 HP at 1500 RPM under NTP conditions. The Engine shall comprise the following standard fitting flexible coupling fly wheel, air cleaner, fan blower, radiator, water pump, fuel filter, lubricating oil filter, etc.(Kirloskar Green / Cummins)
(B) 12/24 Volt Electronic starting Equipment: Complete with starter motor, dynamo, standard batteries with cable, flexible exhaust piping of 50cms length
(C) Engine Instrument Panel / Mounted: Starting push button / starting key, lubricating oil, temperature gauge, lubricating oil pressure gauge, water temperature gauge, safety control for low lubricating oil, pressure, safety control for high water temperature, safety control for over speed, hour meter (mechnical ) and RPM indicator, battery charging ammeter. The engine should be capable of providing 10% over load for one hour for every 11 hours continuous at full load.
D)ALTERNATOR: 250KVA/200KW Capacity of brushless alternator, AC 3 phase, 50Hz, 415/420V, 0.8 PF, 1500 RPM under NTP conditions, conforming to CPCB IV+ Norms.
(E) AMF CONTROL PANEL: The AMF control panel (cubical) should be fabricated with vermin proof and dust proof best quality sheet steel and floor mounted with removable rear panels and hinged front doors with enamel painted and incorporating the following with suitable provision for connection incoming and outgoing leads having been made on the control panel.
3. 3Nos current transformer with suitable ratio
4. Frequency meter
5. KWH meter
6. 1 No power factor meter
7. Battery charging set comprising of the following for charging the battery from mains
8. 1 set Air break contactor with auxiliary netural contactor for main supply
9. 1 set Low volage HRC fuse for the short circuit protection of the main supply
10. 1 set Alternator contactor with auxiliary netural contactor
11. 1 set Three pole bimetal release for over load protection of alternator
12. 1 set low voltage HRC fuse for the short circuit protection of the alternator
13.1 set DC control relays incorporating engine start/ stop and failure to start / lockout
15. 1 no Push button "Start"
16. 1 no Push button "Stop"
17. 1 no Push button "Reset"
18.1 No signal lamp for indicating load on mains
19. 1 no signal lamp for indicating load on set
20.1no signal lamp for indicating set fails to start
21.1no signal lamp for indicating set running
22.1No signal lamp for indicating battery
23. 1set Pilot lamps of 3 nos
24. MCCB of suitable capacity with magnetic thermal overload release, instant start circuit trip and under voltage release switch
25.Rectangular copper bus bars (1No for each phase, neutral and earthing terminals) of adequate capacity duly colour coded with head shrinkable PVC sleeves.
26.1No mains voltage monitor
27.Hooter/Audio alarm for indicating set fails to start and for DG O/L.
28.1set Timers
29.Audio and Visual indicator arrangements for: a) Low lubricating oil pressure b) High water temperature c) Over speed
30.1No Earth fault relay
31.Isolator to isolate the neutral
1. The control panel should be complete with necessary fuses, cables, label, other accessories with neutral isolation arrangements. 2. The engine should trip for the following: a) Low lubricating oil pressure b) High water temperature c) Over speed
3.Supply and fitment of Auto Mains Failure Panel, 1 EB Service wih 400 Amps switch and contactors SUF Control relays, timers etc suitable for auto change over of DG & EB Service.
F.FUEL TANK 600 litres fuel tank shall be fabricated out of 14 SWG CRCA MS sheet and is part of base frame. It is duly painted and fitted with inlet and outlet connections and mechanical fuel gauge. Fuel tank can be easily removed for cleaning or any maintenance. G. Exhaust Gas Recirculation system arrangements as per CPCB IV+ norms as amended
H.BASE FRAME: Base frame should be fabricated with MS channel frame of rigidly welded construction for mounting of generaor set. The engine and alternator should be coupled by suitably designed diaphragm type flexible coupling with guard and mounted on the base frame with proper alignment.
I) ACOUSTIC ENCLOSURE: The Acoustic enclosure, Self standing weather proof Acoustic canopy conforming CPCB IV+ norms floor mounting type with modular construction with the provision to assemble and dismantle easily and designed to suit all weather condtions and compliance to IS standards.
Erection of acoustic enclosure suitable for 250KVA Diesel generator complete with all accessories as above and suitable supports etc. as approved by competent authority to suit updated CPCB norms.
J) Erection of generator set with proper alignment over the existing foundation.
K)Supply of manuals for operation & maintenance of DG set with warranty card etc. L) CEIG approval: Preparation of site plan physical layout, electrical line schematic Diagram 10 sets, getting drawing approval from CEIG preparation of complection report rectification report etc., arranging CEIG inspection and obtaining CEIG safety certificate, payment of CEIG inspection fees if necessary and preparation of one set of approval Drawing and copy of safety certificate in a neat frame work.
(M)TESTING AND COMMISSIONING
After the installation of DG set on its foundation, the DG set should be tested and commissioned with first charging of lubrication oil to its level, first charging of battery and run the set for eight hours on full load test complete.
The Genset engine and alternator make should be approved by department officials before used on work.
Supply and installation of additional length of exhaust piping with suitable MS pipe so as to extend outside the generator room with necessary thermal insulation .
Design, Engineering, supply, fabrication, erection, testing, commissioning and handing over of 1 No 26 persons capacity Bed-cum-Passenger Lift with M/C room, Speed 1 m/s with Stainless Steel Panels, Disable friendly, microprocessor based controller, VVVF drive, Fire rated doors and ARD.
1. Location : Additional Building for the Gobvernment Hospital at Paramakudi 2. No of Lift : 1 No 3. Type of lift : passenger cum bed lift.
4. Capacity of lift : 26 persons capacity passenger cum bed lift /1768Kg 5. Speed : 1.0 Metres / Sec 6. Type of Drive: Specific Variable Voltage, Variable Frequency V3F drive with enhanced ride comfort and leveling function 7. No. of floors: Ground + 4 floors
8. Total travels ;14 Mts(apprx.) 9. Levelling Accuracy: High level accuracy with smooth and jerk free stopping. 10. Construction of Car: 18SWG High quality S.S car hair line finish, S.S hand rail, granite floor in SS floorline finish, Eureka false ceiling, stretcher impact protection.
11. Position of machine: Directly above the lift well. 12. No. of landing entrance: one in front Total 5 Nos 13. No. of car entrance: one in front only.
14. Car entrance door: power operated side opening sliding 18SWG stainless steel hair line finish. 15. Landing entrance door: power operated V3F side sliding, opening 18SWG stainless steel hair line finish with provision for emergency key opening at all landing
16. Lift well required: 2400mm (width) x 3000mm (depth) (As per IS 14665 Part 1- 2000) 17. Lift pit depth available : 1600mm 18. Car size:1600mm (width) x 2400mm (Depth) (as per IS 14665 part 1 -2000 )
19. Car clear opening: 1200mm wide x 2000mm height (as per IS 14665) (part 12000) 20. Lift machine room available: 4350mm width x 5500mm depth (as per IS 14665 part 1-2000)
23. Car fittings: 4 Nos sleek CFL light fittings with 2 Nos 300mm sweep cabin fan 24. Lift well: R.C.C. construction with brick masonry. 25. Indication: UP/Down digital direction and position indicator for all landing and in car (25mm Height, seven segment, DOT matrix Digital Floor position indicator scrolling type)
26. Emergency Alarm Bell: Battery operated alarm bell to be provided with Automatic charging device.
27. Emergency light: Battery operated light to be provided with Automatic charging device.
28. FireMan’s switch: To be provided at ground floor 29. Minor builders work: to be provided by lift contractor. 30. Scaffolding: to be provided by lift contractor
31. Sill angles and facia plates: to be provided by lift contractor 32. Steel for lift machinery: to be provided by lift contractor 33. Servicing and maintenance: Free comprehensive servicing and maintenance should be provided by the lift contractor during the guarantee period of one year.
34. Automatic Rescue device: To facilitate the landing of the lift to the nearest floor at the time of power failure. This shall consists of suitable type battery system with charger, inverter, under voltage protection system etc., complete in a separate MS chamber for housing and with all accessories.
35. Provision of intercom with phone: To be provided by lift contractor.3 points EPABX system at three places wide i) in side the car, ii) Head room, iii) at ground floor attendar room.
36. Lift License: Preparation of Drawing, payment of charges to CEIG and insurance policies if any and obtaining CEIG safety certificate as per lift act should be done by lift contractor.
37. Floor announciator with music. Included. 38. Special features: a. Infra red colour sensor with full height creen.
a. Infra red door sensor with full height screen. b. Tubular S.S hand rail in cars. c. Voltage stabilizer for circuit control. d. Stainless Steel signal fixtures.
e. Vendal proof S.S. Button with S.S. cover f. SS hairline finish door frames for landing doors. g. VF door Register signal h. Call Register signal
i. Stainless steel facia plate for car operating panel and landing fixtures. j. Steel ladder for machine room and ladder for lift Shaft pit,
k. On – Off switch for fan and light l. Over load warning indicator With audio announcement. m. Fall width half height rear panel mirror.
39. Provision of architraves covering all three sides up to a width of 300 decorum sheet of plywood with TW frame with aluminum beading architraves should also cover the thickness of still level door frame at the landing and indicator boxes at all landings.
40. Other standard features: Voltage stabilizer for control units, Over speed governor, phase failure and phase reversal relay alarm bell, T. Guide brackets for car and counter weight, rubber padding under winding unit, motor of adequate capacity, electromagnetic brake with compression springs car safety gears buffer, electro mechanical door locks emergency key side supporting angles, motor over load protection devices final limits switch, main suspension ropes counter weights lifting hoist for mounting the machineries.
41. Guarantee: Guarantee for the materials and workmanship of equipments complete should be offered by lift firm for a period not less than one year. 42. Site testing in accordance with IS 14665 should be carried out at the time of handing over. Necessary spares and tools required for the maintenance for a period of one year 43. Supply of operation and maintenance manual with Necessary tools for Operation. The list of tools required should be detailed by the contractor in a separate sheet duly signed by contactor.The make shouls be approved by the departmental officers before used on work . [( G+3) + 150000] =3500000+150000 = 3650000
Design, Engineering, supply, fabrication, erection, testing, commissioning and handing over of 1 No 15 persons capacity Stretcher-cum-Passenger Lift with M/C room, Speed 1 m/s with Stainless Steel Panels, Disable friendly, microprocessor based controller, VVVF drive, Fire rated doors and ARD. Technical specifications: 1. Type of lift : stretcher cum passenger lift 2. Capacity of lift : 15 Persons Stretcher-cum-Passenger Lift 1020Kg 3. Speed : 1.00 Meter/Sec 4. Type of Drive: Micro Processor variable voltage variable frequency V3F drive with enhanced ride comfort and leveling functions. 5. No. of floors: (Ground + 4 upper floors) 6. No. of Landing Entrances:5 (Ground + 4 upper floors) 7. No. and Position of car Entrances: 1(one), In Front only. 8. Position of machine: Directly above the lift well Gearless 9. Size of Lift well: 2500 x 1900 (MM Wide*MM) 10. Lift Car Inside size: 1000 x 2400 mm 11. Type or Design of Lift Car: Stainless steel neat-Hairline Finish 12. Fireman's switch: Included. 13. Car Ceiling-Car Floor: Sleek (Small circular Light)-SS Hairline Finish-PVC 14. Car Fittings. LED Lights & Regular circular) Fan 300mm sweep. 15. Type of Car entrance Protection: power operated centre opening sliding door-stainless steel-Hairline Finish 16. Type of Landing Entrance Protection: center opening sliding Door - Stainless Steel -emergency key opening at all landings.
21. Electric Supply: AC 400/440 Volts, 3 Phase, 50 Cycles 22. Steel for lift machinery: Included. Special Inclusions: 23. Digital Position Indicator in car and landings 24. Batteryt Operated Emergency Light and Alarm Bell with battery and charging device. 25. Call Register signal and VF Door operator
26. False Ceiling in Car. 27. Infra Red Door Screen-for full height 28. Vandal Proof S.S Button with S.S Cover 29. Automatic Rescue Device: Consist of battery system with charges, inverter (Under voltage protection system etc with all accessories)
30. Minor builders work: included in the scope. 31. Scaffolding: Included in the scope 32. Lift License: The erection work includes the preparation of drawing and getting license to operate lift. 33. Free service for one year
34. Lift duty motor of adequate capacity, electro magnetic brake with compression springs, over speed governor, phase failure and phase reversal relay, alarm bell, T guide brackets for car and counter weight, rubber padding under winding unit, car safety gears, buffer electro mechanical door locks, emergency key, side supporting angles motor over load protection devices. Final limit switch, main suspension ropes, counter weights, lifting hoist for mounting the machineries,
35. Guarantee: Guarantee for the materials and workmanship of equipments complete should be offered by lift firm for a period of one year 36. Site testing in accordance with IS 14665 should be carried out at the time of handing over.Supply of operation and maintenance manual with Necessary tools for Operation. The list of tools required should be detailed by the contractor in a separate sheet duly signed by contactor.The make shouls be approved by the departmental officers before used on work(SR) (M-2377)(for G + 3 Floors)[( G+3) + 100000] =2100000+100000 = 2200000
Design, Engineering, supply, fabrication. Erection, Testing commissioning and handing over of 1 No 240Kgs Dump Lift MRL Speed 1 m/s with M.S. Panels, microprocessor based controller, VVVF drivethe following Technical Specification.
1) Number of Lifts/Type of Lift : One / Dumb Waiter service. 2. Load/speed : Weight (240 Kgs) 1.00 mtr/sec
4. Automatic Rescue Device : Input Voltage: Three Phase 440VAC, 50Hz Pure Sine Wave Main Line Voltage. Output Voltage: Two Phase 440VAC, 50Hz Modified Square wave with power Booster Logic. Battery Voltage: 48V (4Battery of 12V) and 7 Amp depend upon the Motor Rating.
5. No.Of floors: (G +4)
6. No. of Stops : 2 Stops, 2 Landings, 2 Openings
8.Power Supply: AC 415 volt 3 Phases 50 Cycle + 10%.
9. Auxiliary: Single Phase 220 Volt 50 Cycle AC.
10. Car size (Clear inside): 1000mm width x 1200mm depth Car clear opening: 1000mm width x 1200mm height
11. Car (Cabin): Light Fittings /
12. Car enclosure : Stainless Steel CABIN (1.5 mm) HAIR LINE FINISH.Additional Car Spec. Car Flooring Aluminum Checker Plate.
13. Entrance : One Entrance.
14. Car & landing Entrance : MS IFG DOOR System. (MANUALSYSTEM )
15. Indicator for landing : Wall mounted Position with UP and DOWN Arrows. (Dot matrix scoriling display)
16. Emergency : Alarm & Light ( Auto Operated Battery with Charging Device)
17. Fireman’s Switch : Ground Floor with 4 th Floor
18.Steel for lift machinery:Included in this Scope
19.Servicing and maintenance:Free comprehensive servicing and maintenance should be provided by the lift contracter during the guarantee period of one year.
20.Lift License:Preparation of Drawing,payment of charges to CEIG safety certificate as per lift act should be done by lift contracter.
21.Special features: a.Up and Down arrows in landing only.
b.Steel cubical for controller.
c.Lift duty motor of adequate capacity, electromagnet break with compressor springs,over speed governor,phase failiure & Phase reversal relay alarm bell T-guide backets of car and counter weight Rubbes padding under Winding units car safety gears buffers electro mechanical door lock,emergency key,side supporting angle,motor over load protection devices final limit switch,main suspension ropes,counter weights lifting hoist for mounting the machineries.
22.Guarantee:Guarantee for the materials and workmanship of equipments complete should be offered by lift firm for a period not less than one year.
23.Site testing in accordance with IS 14665 should be carried out at the time of handing over.
24.Supply of operation and maintenance manual and Necessary tools for Operation and a set of spare required for 1 year.
25.Servicing and maintenance:Free comprehensive servicing and maintenance should be provided by the lift contracter during the guarantee period of one year.The make should be approed by the departmental officers before used on work. [( G+3) + 50000] =1100000+50000 = 1150000
Supply and clarnping of 3 1/2 x 35 sq.mm PVC LTUG armoured LTUG cable on post or on wall with MS Clamps. (for Lift)
Supply and fixing of brass cable gland for 3-1/2 x 35 sq.mm. PVC armoured LTUG cable with earth connection .
Supply and providing cable end termination of 3-1/2x35sq.mm. PVC LTUG aluminium armoured cable with necessary aluminium cable sockets by crimping etc with electrical connection complete .
Wiring with 2x1.5 sq.mm. PVC insulated SC unsheathed FRLS copper conductor of 1100V grade in suitable PVC rigid pipe concealed in wall and ceiling with PVC accessoires in flush with wall with 3mm thick hylum sheet cover with TW switch box and 5AFT switch and making good of the concealed portion with suitable colour forPVCconcealedlight/fan Point (for electronic regulator) (5 points per coil) . ( For Lift Machine room)
Supply and laying of 3 1/2 x 95 sq.mm PVC armoured LTUG cable in a trench to be excavated at a depth of 0.75 metre putting 0.15 metre layer of sand and covering the cable completely with bricks and sand and refilling the earth to make good (For Existing Building)
Supply and clamping of 3-1/2 x 95 sq.mm. aluminium PVC LTUG armoured cable on post or on wall with MS clamps.
Supply and frxing of brass cable gland for 3-1/2 x 95 sq.mm. aluminium PVC armoured LTUG cable with earth connection.
Supply and providing cable end termination of 3-1/2 x 95 sq.mm. aluminium PVC LTUG aluminium armoured cable with necessary aluminium cable sockets by crimping etc with electrical connection complete.
Supply and laying of 3 1/2 x 150 sq.mm PVC armoured LTUG cable in a trench to be excavated at a depth of 0.75 metre putting 0.15 metre layer of sand and covering the cable completely with bricks and sand and refilling the earth to make good (For Existing Building)
Supply and clamping of 3-1/2 x 150sq.mm. aluminium PVC LTUG armoured cable on post or on wall with MS clamps.
Supply and frxing of brass cable gland for 3-1/2 x 150 sq.mm. aluminium PVC armoured LTUG cable with earth connection.
Supply and providing cable end termination of 3-1/2 x 150 sq.mm. aluminium PVC LTUG aluminium armoured cable with necessary aluminium cable sockets by crimping etc with electrical connection complete.
DX AIR COOLED CONDENSING UNITS:Design ,supply ,
installation, testing and commissioning of 5.5TR Nominal capacity
DX Air-cooled Condensing unit fixed with energy efficient R410A
Refriant scroll compressor along with grooved copper
tube/aluminium fins air cooled condensor coil with anticorrosion
coatings,liquid ,accumulator, low noise alumimium propeller condenser fan with Fan motor etc all suitably assembled neatly in heavy duty GSS sheet metal cabinet and duly powdercoated as
per specification .the unit to include built in safety controls like HP / LP switch power quality protector ,in built thermal / temperature protection .
Supply ,installation , testing and commissioning of 2200cfm 5.5 TR Nominal capacity factory assembled double skin ceiling mounded AHU with 50mm-45kg/cum PUF Insulated detachable panels ,extruded thermal
break aluminium profiles filled with PUF,panel external skin with 0.6 mm preplasticized sheet, panel internal skin with 0.6mm galvanized sheet, AMCA tested DIDW backward/forward curved
centrifugal fan with EFF1 rating motor ,drive arrangement with taper lock pulleys for fan and motor ,vibration isolators out of heavy duty rubberized mounts, prefilters with 3ply HDPE 50mm
thick filters having an efficiency of 90% 10 mic, 6row /12FPI deep DXcopper cooling coil with copper header and aluminium fins ,GI mist arrestor ,condensate coil trough with SS-304-20G insulated
with 9mm closed cell elastomeric foam, guard for inspection door ,out let damper of aerofoil blades &PVC gears ,and flexible fire retardant canvass complete with galvanized hardware .
each of the cooling coils will have independent distributers,electronic expansion valve kit ,catch all drier, independent DX coil circuit to connectivity to each ODU circuit. (For Operation Theatre - First Floor)
supply and filling of R-410A Refrigerant gas .
supply &fixing of hard drawn copper refrigerant piping of suction line of size 22.20 mm with necessary fitting and clamp .
supply &fixing of hard drawn copper refrigerant piping of liquid line of size 12.70mm with necessary fitting and clamp etc .
supply and fixing of flexible canvas connection .
supply ,fabrication and erection of fabricated duct made up of Aluminium Sheets of 22Gauge thickness .
supply ,fabrication and erection of fabricated duct made up of Aluminium Sheets of 24Gauge thickness .
supply and providing thermal insulation of 9mm thick vidoflex with aluminium foil .
Supply and providing acoustic for initial portion of ducting with 12mm thick fibre glass rigid board covered with tissue paper and aluminium perforated sheet.
supply and fixing of extruded aluminium powder coated supply and return air grilles /diffuser with MS volume control damper .
Supply, Installation , testing & commissioning of laminar flow arrangements with HEPA filters, frames etc., 8ft x 6ft for OT ceiling suspended provides ultra clean sterile Class 100 clean air & designed as per Class 5 of ISO 14644-1 standards with air pleanum at aluminium powder coated 1mm thick casing with aluminium pleat HEPA filters and 0.3 micron 99.97% efficiency and SS 304 perforated grill with 13mm thickness XLP insulation with modular housing , frame: aluminium, flange type, filter media: micro glass fibre, sealant : Polyurethane with air flow as per standards suitable 5.5 TR .
supply and fixing of 1" PVC water drain pipe line .
supply ,fabrication and fixing of MS channel for celling mounting the air conditioning Indoor units.
supply ,fabrication and fixing of MS channel for celling mounting the air conditioning Outdoor units.
Supply and laying of 2 x 10 sq.mm PVC armored LTUG cable in a trench to be excavated at a depth of 0.75 meter putting 0.15mt.Layaer of sand and covering the cable completely with bricks and sand and refilling the earth to make good.
Supply and clamping of 2 x 10 sq.mm PVC LTUG armoured LTUG cable on post or on wall with MS Clamps.
Supply and fixing of brass cable gland for 2 x 10 sq.mm PVC armored LTUG cable with earth connection.
Supply and fixing of double pole sheet steel enclosure box with 6 to 32 A MCB with earth connection. ( for Street Light with Post) .
Supply and fixing of 15W LED decorative Gate light fitting (Havells Ruby/Coral /Eq) complete with suitable length 32 mm dia GI pipe (Class 'B') on the existing gate pillar with supply and fixing of MS box of 30cm x 20cm x 10cm with angle iron frame work with door with lock and key arrangements with supply and fixing of 6A DP MCB inside the MS box with PVC unsheathed Copper leads with 15W LED Lamp (Higher End).
AC Chargeable Emergency Lamp 2 x 11W PL Lamp with all connected accessories.
2m x 1m Rubber Mat suitable for 11 KV installation confirming to IS.
First Aid Box complete with all First Aid Medicines.
Shock Treatment Chart fixed in glass frame .
4 Nos. Fire Buckets made out of 40 x 40 x 6mm MS Angle.
Aluminum extendable ladder upto 25ft (WR-M0087)
Danger Board as required by the Electrical Authorities .
Fire Extinguisher Co2, 4.5 kg. confirming to TAC Norms .
Earthing as per the ISI specification with an earth electrode of 2.1mt class ‘B’ GI pipe of dia not less than 40mm, with copper earth plate of size 125mm x 50mm x 6mm, with necessary funneling arrangement with necessary masonry work and with 38mm RCC cover slab for the brick masonry.
Supply and run of 25mm x 3mm tinned copper flat with necessary clamps / supports on wall / floor / ground for earth connection .
Supply and run of 25mm x 6mm tinned copper flat with necessary clamps / supports on wall / floor / ground for earth connection .
Supply and run of 1 No. 8 SWG Hard Drawn Copper wire in suitable PVC rigid pipe concealed in wall and in Earth and making good of the concealed portion with suitable colour.
ANNAI ELECTRICALS (BID ID -1462215)
Ravi Electricals (BID ID -1461617)
stage.html
html • 0.04 MB
tech_eval.pdf
fin_eval.pdf
aoc.pdf
boq_comp_chart.xlsx
xlsx
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .