Loading…
Loading…
| # | Company | Status |
|---|---|---|
| 1 | Admitted-Finance | Admitted-Finance |
| 2 | Admitted-Finance | Admitted-Finance |
| 3 | Admitted-Finance | Admitted-Finance |
| 4 | Admitted-Finance B402 SOMDUTT CHAMBERS 1 SMS INDIA PRIVATE LIMITED 5 BHIKAJI CAMA PLACE NEW DELHI 110066 SOUTH WEST DELHI DELHI 110066 | NEW DELHI | DELHI | 110066 | Admitted-Finance |
Tender Value
Refer Docs
Closing Date
9 Oct 2021, 3:00 pmClosed
Executive Engineer, STD Leh, PDD Ladakh
Office of the Executive Engineer, Sub Transmission Division Leh, Above Royal Enfield Showroom, Housing Colony, Bumgarh, Leh
Design, Manufacture, Supply, Installation, Erection, Testing and Commissioning of 6.3 MVA, 66/11KV LILO substation at Nanak Hills, Leh
2021_PDNRE_4400_1
STD/Leh/10 of 2021 dated 07-09-2021
Open Tender
Electrical Works
Item Rate
540 days
Nanak Hill Leh UT Ladakh
Mentioned in Tender documents
5 documents required · 5 mandatory
₹10,000
Executive Engineer Sub Transmission Division Leh
Yes
Chief Engineer Distribution PDD Ladakh
8 Jan 2022
8 Sept 2021
12 Oct 2021
8 Sept 2021
9 Oct 2021
24 Sept 2021
13 Sept 2021 - 20 Sept 2021
17 Sept 2021
Amount
Power transformer (Supply)
6.3 MVA, 66/11 kV, 3-Ph, YNyn0, Z=7 %, ONAN with copper wound Power Transformer with OLTC(-15% to +5% in steps of 1.25%) , RTCC panel including all cabling & 10% spare oil. (BIL-650kV Peak, Altitude- 3400 M, Creepage distance=2960 mm/kV) The Transformer shall be suitable for single ACSR Zebra Conductor termination on HV and cable box shall be provided on LV side) The Transformer shall be suitable for outdoor installation & complete with all accessories to meet the technical specification.
100 kVA, 11/0.433 kV, Copper Wound, 3ph, Dyn-11, Z=4% outdoor type "Station Transformer" with OFF Circuit Tap Changer , -5% to + 5 % in steps for 2.5 % & including 10 % spare oil. (Altitude- 3400 M) MV connection shall be through XLPE insulated cable and LV Side shall be connected through XLPE Insulated cable.
66kV equipment
72.5 kV, 1250 A, 31.5 kA for 1 sec, SF6 Circuit Breaker, outdoor type, 3-Ph gang operated complete with operating mechanism & support structure with 10 % spare SF-6 gas.(BIL-650 kVpeak, Creepage distance=2960 mm/Kv, Altitude- 3400 M)
72.5 KV, 1250 A, 31.5 kA for 1 sec, 3-Ph gang operated Double Break Centre Post rotating , outdoor type, motor operated Disconnector (Isolator) complete without solid core post Insulator.(BIL- 650 kVpeak,Creepage distance=2960 mm/kV, Altitude- 3400 M)with earth switch
72.5 KV, 1250 A, 31.5 kA for 1 sec, 3-Ph gang operated Double Break Centre Post rotating , outdoor type, motor operated Disconnector (Isolator) complete without solid core post Insulator.(BIL- 650 kVpeak,Creepage distance=2960 mm/kV, Altitude- 3400 M) without earth switch
66 KV Outdoor type, live tank, single phase Current Transformer as per the details below: The CT shall meet the technical specification & other design requirement as per design requirement.(BIL- 650 kVpeak, Creepage distance=2960 mm/kV, Altitude- 3400 M) Transformer feeder CTR : 150-100/0.577-1-1-1 A
66 KV Outdoor type, live tank, single phase Current Transformer as per the details below: The CT shall meet the technical specification & other design requirement as per design requirement.(BIL- 650 kVpeak, Creepage distance=2960 mm/kV, Altitude- 3400 M) Line CTR: 400-200/1-1-1-1 A
Neutral current transformer for 132 /11kV transformer on 132 kV side neutral CTR 150-100/1 A CT design parameters
72.5 kV, 1-ph, Capacitor Voltage Transformer(CVT) for 66 kV Incoming Line (66kV/√3, 110/√3, 110/√3V, 110/√3V) as per technical specification.(BIL- 650 kVpeak, Creepage distance=2960 mm/kV, Altitude- 3400 M)
72.5 kV, 1-ph, Potential Transformer(PT) on busbar (66kV/√3,110/√3,110/√3,110/√3) as per the technical specification. .(BIL- 650 kVpeak, Creepage distance=2960 mm/kV, Altitude- 3400 M)
60 kV, 10 kA, Metal Oxide type, heavy duty, station class 3, Lightning Arrestor complete with Surge Counter & flexible copper connecting lead. (BIL- 650 kVpeak, Creepage distance=2960 mm/kV, Altitude- 3400 M)
66kV BPI for Isolator.(BIL- 650 kVpeak, Altitude- 3400 M)
66kV BPI for Buswork. (BIL- 650 kVpeak, Altitude- 3400 M)
CT, CVT & PT JB complete with 30 nos Disconnecting type Terminals Blocks, complete with wiring.
Bay Marshalling Kiosk, made of 2.5 mm. thick sheet steel, protection class IP 55 complete with 200 TB
String Insulator Hardware for 66 Kv (Supply)
Single Tension Insulator assembly suitable for 11 kV, 90 kN Disc Insulator with all hardwares accessories for single ACSR "Zebra" conductor ( without disc Insulator) with turn buckle.
Single Tension Insulator assembly suitable for 11 kV, 90 kN Disc Insulator with all hardwares accessories for single ACSR "Zebra" conductor ( without disc Insulator) without turn buckle.
Single Suspension Insulator assembly suitable for 11 kV, 90 kN Disc Insulator with all hardwares accessories for single ACSR "Zebra" conductor ( without disc Insulator) drop type
90 KN Disc Insulator , B & S type for the String Insulator
ACSR "Zebra" conductor
Terminal connectors for 66kV side.The Quantity of Terminal connectors shall be as per substation layout & shall be supplied as per technical specification as per individual equipment requirement (Supply)
Terminal connector for 66kV Isolator to receive single ACSR Zebra Conductor.
Terminal connector for 66kV SF6 Circuit Breaker to receive single ACSR Zebra Conductor
Terminal connector for 66kV Current Transformer terminal to receive single ACSR Zebra Conductor
Terminal connector for 66kV CVT terminal to receive Single ACSR Zebra Conductor
Terminal connector for 66kV PT terminal to receive Single ACSR Zebra Conductor
Terminal connector for 66kV BPI to receive single ACSR Zebra Conductor
Terminal connector for 120kV Lightning Arrester to receive Single ACSR Zebra Conductor
Transformer Bushing Connector ( 145kV Side )
Terminal connector for NCT suitable for 50x6 mm CU flat
C-Wedge connector for single ACSR Zebra
T- type connector suitable for single ACSR Zebra through and same T-off
Shield Wire & Accessories (Supply)
7/3.15 mm GSS wire for shielding
Tension Fittings for 7/3.15mm Earth wire
Earth Wire Connector (PG Clamps)
Cleat Clamp for clamping 7/3.15 mm GSS wire on to the Structure
Pad Clamp for clamping 7/3.15 mm GSS wire on to the Structure for earthing
12.5 Meter Lightning mast with spike (Tubular pole)
11kV Switchgear (Supply)
11kv , 26.3kA for 1 Secs., 630A, 500MVA rupturing capacity indoor VCB switchgearpanel 24V DC operated with required PTs, CTs, protective relays, metering equipment, auxiliary equipment, extensible (both sides) copper busbars, complete cable termination Kits and all realy shall be of numerical type with suitable for IEC 61850 protocol as per technical specification. With 1 nos 630A incoming feeder, 400A outgoing feeder, 400A station transformer feeder.
2200 KVAR at 12.65 kV automatically switched capacitor banks with RVT, isolator, L&E switch & series reactor along with supporting structure with 10% spare capacitor units
Control and Relay Panel (Supply)
Indoor floor mounted, simplex type Control and Relay Panels, with mimic & annunciation panel for 66kV system as per specification comprising of the C & R Panels shall be complete with Numerical Relays as per the Technical specifications & shall be compatible for SCADA/ SAS as open protocol. For 66 kV Line Protection & control Panel
Indoor floor mounted, simplex type Control and Relay Panels, with mimic & annunciation panel for 66kV system as per specification comprising of the C & R Panels shall be complete with Numerical Relays as per the Technical specifications & shall be compatible for SCADA/ SAS as open protocol. For 66 kV Transformer Protection & Control Panel
Earthing and Lightning protection material (Supply)
75 x12 mm GI flat for Main Earth mat & Auxiliary Mat
65 x12 mm GI Flat for Equipment Earthing like CT,CB, Isolator , LA, BPI & Tower Earthing, riser below ground etc.
75 x 12mm GI Flat for earthing of Transformer body
50 x 6 mm GI Flat for earthing of Marshalling Boxes, Panel, Junction boxes, Distribution Board, Battery Charger etc. (2.36kg/m)
50x6 mm MS flat for cable trench earthing.
50 x 6 mm Copper flat for earthing of Transformer Neutral on HV as well LV Side. (2.69kg/m)
40 mm Dia, 3 mtr long MS rod earth earth electrode (perforated) for earthing of LA, CVT, Lightning Mast, Transformer Neutral
40 mm Dia 3 mtr long MS rod earth Earth Electrode at corners of Main Earth Mat , Gate & control room Earthing
40 mm Dia 3 mtr long GI PIPE earth Earth Electrode at corners
50x6 mm GI flat for all building spikes
40 mm Dia 3 mtr long GI. Rod Earth Electrode with earth pit for building spikes earthing
40 mm Dia 3 mtr long MS. Rod Earth Electrode with earth pit for boundary.
Supply and erection of Rod type earthing as per IS with 300 mm long,40 mm dia rod to be placed in 3000 mm deep pit for Transformer Neutral earthing t to be filled with salt & charcoal (as per standard earthing Practices)(Power trafo )
Structural Steel (Supply)
Towers and Beams(Lattice type)
Structural steel for Tower and beams (50% of MS and 50% of HT)
Hardwares, nuts, bolts and spring washer
Foundation Nuts and bolts
Structural steel for Equipment (Pipe type)
Hardwares, nuts, bolts and spring washer
Foundation Nuts and bolts for equipment
Cable and accessories (Supply)
11 kV, 3 Core 400 sqmm., AL Conductor, XLPE Insulated , PVC Sheathed, Armoured PVC Outer Sheath Cable for 11 kV outgoing fedder from Power transformer to 11 kV switchgear panel.(2 runs/phase)
11 kV outdoor termination kit (3CX400 Sqmm.)
11 kV indoor termination kit (3CX400 Sqmm.)
11 kV, 3 Core 50 sqmm., AL Conductor, XLPE Insulated , PVC Sheathed, Armoured PVC Outer Sheath Cable for 11 kV panel to station transformer
11 kV outdoor termination kit (3CX50 Sqmm.)
11 kV indoor termination kit (3CX50 Sqmm.)
11 kV, 3 Core 185 sqmm., AL Conductor, XLPE Insulated , PVC Sheathed, Armoured PVC Outer Sheath Cable for 11 kV outgoing panel to 11kV Double pole.
11 kV outdoor termination kit (3CX185 Sqmm.)
11 kV indoor termination kit (3CX185 Sqmm.)
LT Power Cable (Supply)
31/2 core x 150 sq.mm AL (XLPE)cable from Station Transformer and DG set to LVAC Board
31/2 core x 70 sq.mm AL (XLPE)cable from Station Transformer and DG set to LVAC Board
31/2 core x 150 Sqmm Al cable for oil filtration
31/2 core x 70 Sqmm Al cable for outdoor illumination & for battery charger
2 core x 16 Sqmm Cu cable for BMK, Trafo MB, fire panel & LDB
4 Core 16 sqmm Al cable for ACDB to PDB
4 Core 16 sqmm Al cable fo outdoor illumination JB
3 Core 2.5 sqmm CU cable fo outdoor illumination
2 Core x 50 sqmm Cu cable for DCDB to battery charger(Flexible multi strand)
Termination kit and accessories for above item
Copper Control Cable (Supply)
2 core 4 sqmm.
2 Core 6 sqmm.
4Core 4 sqmm.
4 core 2.5 sqmm.
7 core 2.5 sqmm.
12 core 2.5 sqmm.
19 core 2.5 sqmm.
Double compression Glands and terminations (including ferruling, suitable Cu Lugs to meet the system requirements) for 1100 V grade PVC Insulated multicore Copper stranded conductor control cables of the following sizes: (Supply)
2 core 4 sqmm., 2 Core 6 sqmm., 4Core 4 sqmm., 4Core 2.5 sqmm., 7 core 2.5 sqmm, 12 core 2.5 sqmm, 19 core 2.5 sqmm.
Cable Trays (Supply)
Ladder type Cable Trays for outdoor (300mm wide)
Perforated Cable Trays inside the Control Building (300mm wide)
HDPE/PVC pipe for laying cable for road crossing (160mm dia and 100mm dia)
AC Distribution Board (Supply)
AC 415V, 250A, 3-Ph cubicle type Indoor, floor mounted, auxiliary service board as per specification comprising of : LVAC Board will have 2 sections , section will be fed from independent Aux. transformer and DG set. Busbar rating 250 A, 3-Ph., 25 kA for 1 sec, Copper. i)2 Nos. - Incomer feeders with 250A TPN MCCB( Microprocessor base) ii)1 Nos. - Outgoing feeders with 100A TPN MCCB( Microprocessor base) iii)4 Nos. - Outgoing feeders with 63A TPN MCCB iv)4 Nos. - Outgoing feeders with 32A TPN MCCB v)2 Nos. - Outgoing feeders with 16A SP MCCB
DC Distribution Board ( 24 V DC )
DC Distribution Board will have 2 sections , each section will be fed from independent Battery charger. Busbar rating 100 A for 24 V DC, 16 kA /for 1 SEC, Copper. i)1 no. incomer 100A MCCB( Microprocessor base) ii)4 Nos. - Outgoing feeders with 32A MCCB iii)3 Nos. - Outgoing feeders with 16A MCCB
Battery set ( 24 V DC ) (Supply)
24V DC, 140 AH lead acid battery of VRLA type complete with accessories as per specification with 10% spare acid in non-returnable container (In tier arrangement).
Battery charger ( 24 V DC ) (Supply)
Automatic float and Float cum boost charger 40 A suitable for 24 V 150 AH VRLA battery & charger shall be as per specification
11kV Double pole structure (Supply)
Supply and erection of 11 Meter Steel Tubular pole (540 SP55 as per IS: 2713) with base plate(450x450x6mm MS painted type) with two coats of red Oxide and one coat of bitumen compound at bottom till planting depth. Silver/Aluminum paint shall be painted on exterior of pole. The weight of the Pole shall be 227 kg and outside diameter and thicknes of section shall be 193.7X4.85 mm(bottom), 165.1x4.50 mm( middle) and 139.7x4.50 mm(top). The pole shall be erected in a pit of size 600mmx600 mm(2000mmdeep) in M 20 grade PCC 300 mm muff shall be provided above the ground level in M 20 PCC Each Pole shall have M12 stud welded for earthing. The poles shall be erected as Double pole structure.
GSL No. 8 SWG
45 KN, 4500 Kg Ball and Socket type Disc insulator
11 KV, 10 KN pin insulator complete with 250 mm long Pins with Nuts
11 KV disc insulator for stay set
Horizontal shape cross arms made out of 2200 mm long MS channel galvanized of size 100x50x6 mm.(wt. 21.032 Kg including fabrication and painting with two coat Red Oxide and Aliminium paint .
Stay Sets 8' long complete with X-Plat 460mm of Angle 65x65x6 Elbow & rod Wt. 13.80 Kg.
GSS wire 7/8 SWG (4 mm)
GI Nuts & Bolts off sizes
U-bolt for suspension fittings.
MS angle galvanized, size 50x50x6 mm, 2400 mm (ISI Marked) including fabrication charges, painting for Bracing angle. (10.18 Kg)
MS chanel galvanized, size 75x40x6 mm, 2200 mm (ISI Marked) including fabrication charges, painting support structure for GO switch, do fuse. (15.70 Kg)
G.I. Strip 25x6 mm 9 mtr. For earthling Wt.10.80 Kg.
Half Clamps Wt. 1.65 kg.
Danger plates of 2 mm thick plate.
Barbed wire
Number plate
Phase plate (Set of three)
AL binding wire
11 KV LA (Type 9KV 10KA Heavy Duty)
11 kV 400 Amps. GO Switch complete with handle, pipe & Supporting channel.
11 KV D.O. fuse unit
Supply and erection of Rod type earthing as per IS with 300 mm long, 32 mm dia rod to be placed in 3000 mm deep pit and pit shall be treated with salt & charcoal as per IS. The connection to the pole shall with 50x6 mm GI Flat.
Fire fighting (Supply)
Fire Fighting equipment as per section-6 22.5 Kg capacity FE CO2 type, Trolley Mounted
25 Kg Capacity FE DCP type, Trolley Mounted
DCP 10 Kg Capacity, Wall mounted
FE CO2 6.5 Kg capacity, Wall mounted
DCP 5 Kg Capacity, Wall mounted
Foam Type 9 liter Capacity, Wall mounted
Water CO2 9 liter, Wall mounted
Fire Buckets (12 Nos. with stand in one set)
Rubber mats for contro room building near 11 kv panels as per voltage rating requirement conforming to IS-15652 with latest amendments
Outdoor illumination (Supply)
LED flood light fitting with 150W led with all accessories control gear for Yard Lighting ( to be mounted on Gantry Tower )
LED street light fitting with 120W led with all accessories control gear on street ( to be mounted on 10 mtr. Pole)
70W LED lights post latern light mounted on 4 mtr. P-type pole
10 Mtr. MS Tubular poles 540SP-72
4 Mtr. P-type pole made of 100mm Dia GI Pipe
Lighting junction box for Light suitable for out door Installation comprising of 4 Nos. CBT M 4 type terminal connector for light connections Max size 150 x150x100mm
Measuring Instruments (Supply)
Digital earth resistance meter
5 kV automated Insulation resistance meter
Earthing stick
Digital multimeter
Furniture (Supply)
2 nos. of Executive Table :(1800mmX900mm)(Wooden) 3 nos. of Executive Chair:(Revolving mid back type) 6 Nos. of Visitor's Chair with hand rest Computer Room Executive Chair (Revolving mid back type) 2 nos. of Steel Almirah LengthXWidthXHeight in mm (1016X560X1980) 1 Nos. of Recta work station of size 1200mmX600mm,25 mm thick work top with 3 drawer pedestal along with keyboard tray and CPU trolley and partitions of thickness 53 mm and of height 1200 mm.
Miscelleaneous (Supply)
First Aid box Accident prevention chart Aluminum alloy ladder Safety belt
415V, 63/32 A Industrial socket for electrical room and outdoor
40 kVA, 415V, 3 Ph, silent type DG Set with synchronizing panel for emergency supply.
415V, 2000 Watt induction heater with reflector and microprocessor based temp. sensor and with cabling for control room.
Computer with printer
Power transformer (Erection)
6.3 MVA, 66/11 kV, 3-Ph, YNyn0, Z=7 %, ONAN with copper wound Power Transformer with OLTC(-15% to +5% in steps of 1.25%) , RTCC panel including all cabling & 10% spare oil. (BIL-650kV Peak, Altitude- 3400 M, Creepage distance=2960 mm/kV) The Transformer shall be suitable for single ACSR Zebra Conductor termination on HV and cable box shall be provided on LV side) The Transformer shall be suitable for outdoor installation & complete with all accessories to meet the technical specification.
100 kVA, 11/0.433 kV, Copper Wound, 3ph, Dyn-11, Z=4% outdoor type "Station Transformer" with OFF Circuit Tap Changer , -5% to + 5 % in steps for 2.5 % & including 10 % spare oil. (Altitude- 3400 M) MV connection shall be through XLPE insulated cable and LV Side shall be connected through XLPE Insulated cable.
66kV equipment (Erection)
72.5 kV, 1250 A, 31.5 kA for 1 sec, SF6 Circuit Breaker, outdoor type, 3-Ph gang operated complete with operating mechanism & support structure with 10 % spare SF-6 gas.(BIL-650 kVpeak, Creepage distance=2960 mm/Kv, Altitude- 3400 M)
72.5 KV, 1250 A, 31.5 kA for 1 sec, 3-Ph gang operated Double Break Centre Post rotating , outdoor type, motor operated Disconnector (Isolator) complete without solid core post Insulator.(BIL- 650 kVpeak,Creepage distance=2960 mm/kV, Altitude- 3400 M)with earth switch
72.5 KV, 1250 A, 31.5 kA for 1 sec, 3-Ph gang operated Double Break Centre Post rotating , outdoor type, motor operated Disconnector (Isolator) complete without solid core post Insulator.(BIL- 650 kVpeak,Creepage distance=2960 mm/kV, Altitude- 3400 M) without earth switch
66 KV Outdoor type, live tank, single phase Current Transformer as per the details below: The CT shall meet the technical specification & other design requirement as per design requirement.(BIL- 650 kVpeak, Creepage distance=2960 mm/kV, Altitude- 3400 M) Transformer feeder CTR : 150-100/0.577-1-1-1 A
66 KV Outdoor type, live tank, single phase Current Transformer as per the details below: The CT shall meet the technical specification & other design requirement as per design requirement.(BIL- 650 kVpeak, Creepage distance=2960 mm/kV, Altitude- 3400 M) Line CTR: 400-200/1-1-1-1 A
Neutral current transformer for 132 /11kV transformer on 132 kV side neutral CTR 150-100/1 A CT design parameters
72.5 kV, 1-ph, Capacitor Voltage Transformer(CVT) for 66 kV Incoming Line (66kV/√3, 110/√3, 110/√3V, 110/√3V) as per technical specification.(BIL- 650 kVpeak, Creepage distance=2960 mm/kV, Altitude- 3400 M)
72.5 kV, 1-ph, Potential Transformer(PT) on busbar (66kV/√3,110/√3,110/√3,110/√3) as per the technical specification. .(BIL- 650 kVpeak, Creepage distance=2960 mm/kV, Altitude- 3400 M)
60 kV, 10 kA, Metal Oxide type, heavy duty, station class 3, Lightning Arrestor complete with Surge Counter & flexible copper connecting lead. (BIL- 650 kVpeak, Creepage distance=2960 mm/kV, Altitude- 3400 M)
66kV BPI for Isolator.(BIL- 650 kVpeak, Altitude- 3400 M)
66kV BPI for Buswork. (BIL- 650 kVpeak, Altitude- 3400 M)
CT, CVT & PT JB complete with 30 nos Disconnecting type Terminals Blocks, complete with wiring.
Bay Marshalling Kiosk, made of 2.5 mm. thick sheet steel, protection class IP 55 complete with 200 TB
String Insulator Hardware for 66 Kv (Erection)
Single Tension Insulator assembly suitable for 11 kV, 90 kN Disc Insulator with all hardwares accessories for single ACSR "Zebra" conductor ( without disc Insulator) with turn buckle.
Single Tension Insulator assembly suitable for 11 kV, 90 kN Disc Insulator with all hardwares accessories for single ACSR "Zebra" conductor ( without disc Insulator) without turn buckle.
Single Suspension Insulator assembly suitable for 11 kV, 90 kN Disc Insulator with all hardwares accessories for single ACSR "Zebra" conductor ( without disc Insulator) drop type
90 KN Disc Insulator , B & S type for the String Insulator
ACSR "Zebra" conductor
Terminal connectors for 66kV side.The Quantity of Terminal connectors shall be as per substation layout & shall be supplied as per technical specification as per individual equipment requirement (Erection)
Terminal connector for 66kV Isolator to receive single ACSR Zebra Conductor.
Terminal connector for 66kV SF6 Circuit Breaker to receive single ACSR Zebra Conductor
Terminal connector for 66kV Current Transformer terminal to receive single ACSR Zebra Conductor
Terminal connector for 66kV CVT terminal to receive Single ACSR Zebra Conductor
Terminal connector for 66kV PT terminal to receive Single ACSR Zebra Conductor
Terminal connector for 66kV BPI to receive single ACSR Zebra Conductor
Terminal connector for 120kV Lightning Arrester to receive Single ACSR Zebra Conductor
Transformer Bushing Connector ( 145kV Side )
Terminal connector for NCT suitable for 50x6 mm CU flat
C-Wedge connector for single ACSR Zebra
T- type connector suitable for single ACSR Zebra through and same T-off
Shield Wire & Accessories (Erection)
7/3.15 mm GSS wire for shielding
Tension Fittings for 7/3.15mm Earth wire
Earth Wire Connector (PG Clamps)
Cleat Clamp for clamping 7/3.15 mm GSS wire on to the Structure
Pad Clamp for clamping 7/3.15 mm GSS wire on to the Structure for earthing
12.5 Meter Lightning mast with spike (Tubular pole)
11kV Switchgear (Erection)
11kv , 26.3kA for 1 Secs., 630A, 500MVA rupturing capacity indoor VCB switchgearpanel 24V DC operated with required PTs, CTs, protective relays, metering equipment, auxiliary equipment, extensible (both sides) copper busbars, complete cable termination Kits and all realy shall be of numerical type with suitable for IEC 61850 protocol as per technical specification. With 1 nos 630A incoming feeder, 400A outgoing feeder, 400A station transformer feeder.
2200 KVAR at 12.65 kV automatically switched capacitor banks with RVT, isolator, L&E switch & series reactor along with supporting structure with 10% spare capacitor units
Control and Relay Panel (Erection)
Indoor floor mounted, simplex type Control and Relay Panels, with mimic & annunciation panel for 66kV system as per specification comprising of the C & R Panels shall be complete with Numerical Relays as per the Technical specifications & shall be compatible for SCADA/ SAS as open protocol. For 66 kV Line Protection & control Panel
Indoor floor mounted, simplex type Control and Relay Panels, with mimic & annunciation panel for 66kV system as per specification comprising of the C & R Panels shall be complete with Numerical Relays as per the Technical specifications & shall be compatible for SCADA/ SAS as open protocol. For 66 kV Transformer Protection & Control Panel
Earthing and Lightning protection material (Erection)
75 x12 mm GI flat for Main Earth mat & Auxiliary Mat
65 x12 mm GI Flat for Equipment Earthing like CT,CB, Isolator , LA, BPI & Tower Earthing, riser below ground etc.
75 x 12mm GI Flat for earthing of Transformer body
50 x 6 mm GI Flat for earthing of Marshalling Boxes, Panel, Junction boxes, Distribution Board, Battery Charger etc. (2.36kg/m)
50x6 mm MS flat for cable trench earthing.
50 x 6 mm Copper flat for earthing of Transformer Neutral on HV as well LV Side. (2.69kg/m)
40 mm Dia, 3 mtr long MS rod earth earth electrode (perforated) for earthing of LA, CVT, Lightning Mast, Transformer Neutral
40 mm Dia 3 mtr long MS rod earth Earth Electrode at corners of Main Earth Mat , Gate & control room Earthing
40 mm Dia 3 mtr long GI PIPE earth Earth Electrode at corners
50x6 mm GI flat for all building spikes
40 mm Dia 3 mtr long GI. Rod Earth Electrode with earth pit for building spikes earthing
40 mm Dia 3 mtr long MS. Rod Earth Electrode with earth pit for boundary.
Supply and erection of Rod type earthing as per IS with 300 mm long,40 mm dia rod to be placed in 3000 mm deep pit for Transformer Neutral earthing t to be filled with salt & charcoal (as per standard earthing Practices)(Power trafo )
Structural Steel (Erection)
Towers and Beams(Lattice type)
Structural steel for Tower and beams (50% of MS and 50% of HT)
Hardwares, nuts, bolts and spring washer
Foundation Nuts and bolts
Structural steel for Equipment (Pipe type)
Hardwares, nuts, bolts and spring washer
Foundation Nuts and bolts for equipment
Cable and accessories (Erection)
11 kV, 3 Core 400 sqmm., AL Conductor, XLPE Insulated , PVC Sheathed, Armoured PVC Outer Sheath Cable for 11 kV outgoing fedder from Power transformer to 11 kV switchgear panel.(2 runs/phase)
11 kV outdoor termination kit (3CX400 Sqmm.)
11 kV indoor termination kit (3CX400 Sqmm.)
11 kV, 3 Core 50 sqmm., AL Conductor, XLPE Insulated , PVC Sheathed, Armoured PVC Outer Sheath Cable for 11 kV panel to station transformer
11 kV outdoor termination kit (3CX50 Sqmm.)
11 kV indoor termination kit (3CX50 Sqmm.)
11 kV, 3 Core 185 sqmm., AL Conductor, XLPE Insulated , PVC Sheathed, Armoured PVC Outer Sheath Cable for 11 kV outgoing panel to 11kV Double pole.
11 kV outdoor termination kit (3CX185 Sqmm.)
11 kV indoor termination kit (3CX185 Sqmm.)
LT Power Cable (Erection)
31/2 core x 150 sq.mm AL (XLPE)cable from Station Transformer and DG set to LVAC Board
31/2 core x 70 sq.mm AL (XLPE)cable from Station Transformer and DG set to LVAC Board
31/2 core x 150 Sqmm Al cable for oil filtration
31/2 core x 70 Sqmm Al cable for outdoor illumination & for battery charger
2 core x 16 Sqmm Cu cable for BMK, Trafo MB, fire panel & LDB
4 Core 16 sqmm Al cable for ACDB to PDB
4 Core 16 sqmm Al cable fo outdoor illumination JB
3 Core 2.5 sqmm CU cable fo outdoor illumination
2 Core x 50 sqmm Cu cable for DCDB to battery charger(Flexible multi strand)
Termination kit and accessories for above item
Copper Control Cable (Erection)
2 core 4 sqmm.
2 Core 6 sqmm.
4Core 4 sqmm.
4 core 2.5 sqmm.
7 core 2.5 sqmm.
12 core 2.5 sqmm.
19 core 2.5 sqmm.
Double compression Glands and terminations (including ferruling, suitable Cu Lugs to meet the system requirements) for 1100 V grade PVC Insulated multicore Copper stranded conductor control cables of the following sizes: (Erection)
2 core 4 sqmm., 2 Core 6 sqmm., 4Core 4 sqmm., 4Core 2.5 sqmm., 7 core 2.5 sqmm, 12 core 2.5 sqmm, 19 core 2.5 sqmm.
Cable Trays (Erection)
Ladder type Cable Trays for outdoor (300mm wide)
Perforated Cable Trays inside the Control Building (300mm wide)
HDPE/PVC pipe for laying cable for road crossing (160mm dia and 100mm dia)
AC Distribution Board (Erection)
AC 415V, 250A, 3-Ph cubicle type Indoor, floor mounted, auxiliary service board as per specification comprising of : LVAC Board will have 2 sections , section will be fed from independent Aux. transformer and DG set. Busbar rating 250 A, 3-Ph., 25 kA for 1 sec, Copper. i)2 Nos. - Incomer feeders with 250A TPN MCCB( Microprocessor base) ii)1 Nos. - Outgoing feeders with 100A TPN MCCB( Microprocessor base) iii)4 Nos. - Outgoing feeders with 63A TPN MCCB iv)4 Nos. - Outgoing feeders with 32A TPN MCCB v)2 Nos. - Outgoing feeders with 16A SP MCCB
DC Distribution Board ( 24 V DC ) (Erection)
DC Distribution Board will have 2 sections , each section will be fed from independent Battery charger. Busbar rating 100 A for 24 V DC, 16 kA /for 1 SEC, Copper. i)1 no. incomer 100A MCCB( Microprocessor base) ii)4 Nos. - Outgoing feeders with 32A MCCB iii)3 Nos. - Outgoing feeders with 16A MCCB
Battery set ( 24 V DC ) (Erection)
24V DC, 140 AH lead acid battery of VRLA type complete with accessories as per specification with 10% spare acid in non-returnable container (In tier arrangement).
Battery charger ( 24 V DC ) (Erection)
Automatic float and Float cum boost charger 40 A suitable for 24 V 150 AH VRLA battery & charger shall be as per specification
11kV Double pole structure (Erection)
Supply and erection of 11 Meter Steel Tubular pole (540 SP55 as per IS: 2713) with base plate(450x450x6mm MS painted type) with two coats of red Oxide and one coat of bitumen compound at bottom till planting depth. Silver/Aluminum paint shall be painted on exterior of pole. The weight of the Pole shall be 227 kg and outside diameter and thicknes of section shall be 193.7X4.85 mm(bottom), 165.1x4.50 mm( middle) and 139.7x4.50 mm(top). The pole shall be erected in a pit of size 600mmx600 mm(2000mmdeep) in M 20 grade PCC 300 mm muff shall be provided above the ground level in M 20 PCC Each Pole shall have M12 stud welded for earthing. The poles shall be erected as Double pole structure.
GSL No. 8 SWG
45 KN, 4500 Kg Ball and Socket type Disc insulator
11 KV, 10 KN pin insulator complete with 250 mm long Pins with Nuts
11 KV disc insulator for stay set
Horizontal shape cross arms made out of 2200 mm long MS channel galvanized of size 100x50x6 mm.(wt. 21.032 Kg including fabrication and painting with two coat Red Oxide and Aliminium paint .
Stay Sets 8' long complete with X-Plat 460mm of Angle 65x65x6 Elbow & rod Wt. 13.80 Kg.
GSS wire 7/8 SWG (4 mm)
GI Nuts & Bolts off sizes
U-bolt for suspension fittings.
MS angle galvanized, size 50x50x6 mm, 2400 mm (ISI Marked) including fabrication charges, painting for Bracing angle. (10.18 Kg)
MS chanel galvanized, size 75x40x6 mm, 2200 mm (ISI Marked) including fabrication charges, painting support structure for GO switch, do fuse. (15.70 Kg)
G.I. Strip 25x6 mm 9 mtr. For earthling Wt.10.80 Kg.
Half Clamps Wt. 1.65 kg.
Danger plates of 2 mm thick plate.
Barbed wire
Number plate
Phase plate (Set of three)
AL binding wire
11 KV LA (Type 9KV 10KA Heavy Duty)
11 kV 400 Amps. GO Switch complete with handle, pipe & Supporting channel.
11 KV D.O. fuse unit
Supply and erection of Rod type earthing as per IS with 300 mm long, 32 mm dia rod to be placed in 3000 mm deep pit and pit shall be treated with salt & charcoal as per IS. The connection to the pole shall with 50x6 mm GI Flat.
Fire fighting (Erection)
Fire Fighting equipment as per section-6 22.5 Kg capacity FE CO2 type, Trolley Mounted
25 Kg Capacity FE DCP type, Trolley Mounted
DCP 10 Kg Capacity, Wall mounted
FE CO2 6.5 Kg capacity, Wall mounted
DCP 5 Kg Capacity, Wall mounted
Foam Type 9 liter Capacity, Wall mounted
Water CO2 9 liter, Wall mounted
Fire Buckets (12 Nos. with stand in one set)
Rubber mats for contro room building near 11 kv panels as per voltage rating requirement conforming to IS-15652 with latest amendments
Outdoor illumination (Erection)
LED flood light fitting with 150W led with all accessories control gear for Yard Lighting ( to be mounted on Gantry Tower )
LED street light fitting with 120W led with all accessories control gear on street ( to be mounted on 10 mtr. Pole)
70W LED lights post latern light mounted on 4 mtr. P-type pole
10 Mtr. MS Tubular poles 540SP-72
4 Mtr. P-type pole made of 100mm Dia GI Pipe
Lighting junction box for Light suitable for out door Installation comprising of 4 Nos. CBT M 4 type terminal connector for light connections Max size 150 x150x100mm
Measuring Instruments (Erection)
Digital earth resistance meter
5 kV automated Insulation resistance meter
Earthing stick
Digital multimeter
Furniture (Erection)
2 nos. of Executive Table :(1800mmX900mm)(Wooden) 3 nos. of Executive Chair:(Revolving mid back type) 6 Nos. of Visitor's Chair with hand rest Computer Room Executive Chair (Revolving mid back type) 2 nos. of Steel Almirah LengthXWidthXHeight in mm (1016X560X1980) 1 Nos. of Recta work station of size 1200mmX600mm,25 mm thick work top with 3 drawer pedestal along with keyboard tray and CPU trolley and partitions of thickness 53 mm and of height 1200 mm.
Miscelleaneous (Erection)
First Aid box Accident prevention chart Aluminum alloy ladder Safety belt
415V, 63/32 A Industrial socket for electrical room and outdoor
40 kVA, 415V, 3 Ph, silent type DG Set with synchronizing panel for emergency supply.
415V, 2000 Watt induction heater with reflector and microprocessor based temp. sensor and with cabling for control room.
Computer with printer
Following Spares has to be considered
HV Bushing LV Bushing
Trip coil 11kV VCB
OC/EF Relay
Megger upto 5000V Test voltage with analogue/digital metres
Digital multimeter
Tool-box
66kV BPI for Isolator & Bus works.(BIL- 650 kVpeak, Altitude- 3400 M)
90 KN Disc Insulator , B & S type for the String Insulator
Fabrication, proto testing and supply of 10 KV galvanisd towers (HT Steel with expoxy coat). (66kV Line Supply)
Tension type Towers
Step bolts, bolts and nuts, washers etc. fully galvanized required for the above towers.
Tower Accessories (66kV LineSupply)
Phase plates (Set of Three)
Caution plates (Set of Three)
Circuit plates
Number Plates
Anti climbing devices
Earth Bonds 450mm long
Conductor & Ground wire (66kV Line Supply)
ACSR Panther conductor with 1.5% sag as per IS
Over head ground wire 7/3.15 mm galvanized iron, steel, reinforced with 1.5% sag.
Single Suspension fitings and hardware suitable for 2 nos. for 70KN disc insulator complete with allied hardware.
Single tension fitings and hardware suitable for 2nos. for 90KN disc insulator complete with allied hardware.
DISC insulator 11kv, A/F, 430 mm creepage , 70 KN
DISC insulator 11kv, A/F, 430 mm creepage , 90 KN
Hardwire & Accessories for Conductor
Mid span compression joint
repair Sleeves
PG Clamp
Hardware & Accessories for Groundwire
Mid span compression joint
Compression type tension clamp
repair Sleeves
PG Clamp
Supply and erection of Rod type earthing as per speciifcation with 300 mm long, 32 mm dia rod to be placed in 3000 mm deep pit and pit shall be treated with salt & charcoal. The connection to the pole shall with 50x6 mm GI Flat. Each location shall have two earthing
Supply and erection of GI Strip of 25x6 mm, 9mtr size for earthing purpose.
Civil work for tower installation
Fabrication, proto testing and supply of 10 KV galvanisd towers (HT Steel with expoxy coat). (66Kv Line Erection)
Tension type Towers
Step bolts, bolts and nuts, washers etc. fully galvanized required for the above towers.
Tower Accessories (66Kv Line Erection)
Phase plates (Set of Three)
Caution plates (Set of Three)
Circuit plates
Number Plates
Anti climbing devices
Earth Bonds 450mm long
Conductor & Ground wire (66Kv Line Erection)
ACSR Panther conductor with 1.5% sag as per IS
Over head ground wire 7/3.15 mm galvanized iron, steel, reinforced with 1.5% sag.
Single Suspension fitings and hardware suitable for 2 nos. for 70KN disc insulator complete with allied hardware.
Single tension fitings and hardware suitable for 2nos. for 90KN disc insulator complete with allied hardware.
DISC insulator 11kv, A/F, 430 mm creepage , 70 KN
DISC insulator 11kv, A/F, 430 mm creepage , 90 KN
Hardwire & Accessories for Conductor
Mid span compression joint
repair Sleeves
PG Clamp
Hardware & Accessories for Groundwire
Mid span compression joint
Compression type tension clamp
repair Sleeves
PG Clamp
Supply and erection of Rod type earthing as per speciifcation with 300 mm long, 32 mm dia rod to be placed in 3000 mm deep pit and pit shall be treated with salt & charcoal. The connection to the pole shall with 50x6 mm GI Flat. Each location shall have two earthing
Supply and erection of GI Strip of 25x6 mm, 9mtr size for earthing purpose.
Civil work for tower installation
11kV Over head Line (Supply)
Supply and erection of 9 Meter Steel Tubular pole (410 SP55 as per IS: 2713) with base plate(450x450x6mm MS painted type) with two coats of red Oxide and one coat of bitumen compound at bottom till planing depth. Silver/Aluminum paint shall be painted on exterior of pole. The weight of the Pole shall be 154 kg. and outside diameter and thicknes of section shall be 165.1X5.40mm (bottom), 139.7x4.50mm (middle) and 114.3x3.65mm (top). The pole shall be erected in a pit of size 600mmx600 mm(200mmdeep) in M 20 grade PCC 300 mm muff shall be provided above the ground level in M 20 PCC Each Pole shall have M12 stud welded for earthing
Supply and erection of ACSR "Rabbit" Conductor for 11 KV Lines 1.05% sag. Conductor should be as per PDD, Leh specification.
Supply and erection of 11kV 'V' Cross Arm for Single Pole (Galvanized) ( ISMC )75x50x6mm, Lg. 1398.36mm, 9.89 Kg/mtr.)
Supply and erection of 11 kV Top Bracket/Hampeer (Galvanised) weight 2.950 Kg
Supply and erection of 11 kV Cross Arm (H Pole,T Pole and 4 Pole) 100x50x6 mm (Lg. 2200 mm) Galvanised Weight 17.38 Kg.
Supply and erection of Bracing Angle (Galvanized)( ISA 50x50x6 mm Lg 2400mm, Wt. 10.18
Supply and erection of Galvanized, size 75x40x6 mm, 22000mm(ISI Marked) including fabrication charges, Painiting support structure for GO Switch, do fuse. (15.70 Kg)
Supply and erection of Guard Chanel for D/P Fabricated (Galvanized) ( ISMC 20 X 50x6 ( Lg. 2200 mm, weight 10.80
Half Clamp weight 1.47 kg.
Full Clamp weight 2.325 kg.
Supply and erection of Galvanised Stay Set with 50x8mm stay clamp, guy insulator (2Nos.), anchor plate(200x200x6mm), nut-bolts, 2Nos turn-buckles, 1.8m long, 16 mm diameter solid GS stay rod & 7/3, 15mm dia GI stranded wire complete.
Supply and erection of GSS 7/8 SWG (4mm) for earthing
PG clamp for 50 mm2 ACSR (Rabbit) Conductor
Supply and erection of GSL 8 SWG, GI wire medium coated for running as continuous guard/earth wire.
Supply and erection of Galvanised Nuts, bolts and washers as required for erection of pole / line hardware
Eyw Hook & Screw bolts 9"x5/8" Wt. 0.483 kg. (GI)
Insulators
Supply and erection of 33 KV Polymeric composite Pin Insulator 36 kV, 10kN, Lighting Impulse 170 kV Positive and 180 kV Negative, creepage distance 320mm. as per IS
Supply and erection of 33kV Polymeric composite Disc Insulator 36kV, min failing load 70kN, Lighting Impulse 170 kV Positive and 180 kV Negative creepage distance 320mm as per IS Technical Specifications
Hardware Fittings
B & S type tension fiting including complete hardware for item 18-b above
Danger Plate (Enamelled) with clamp
Number plate(Enamelled )with clamp
Phase Plate (Set of three)(Enamelled)(RYB)
Anti climbing device
Barbed wire
Al. Binding wire
Supply and erection of Earthing Complete by GI Pipe 40 mm or GI Rod 20 mm 2.5 mtr long through GI Strip Each location shall have One earthing
Supply and erection of 11 KV lightning arrester,9 KA, 10kA station class(Heavy duty)
11 kV 400 Amps. GO Switch complete with handle, pipe & Supporting channel. As per Nigam's technical specification, relevant ISS and latest amendments.
11 kV D.O fuse unit
Cement bottoming 1:2:4 mix as per REC standards 0.45 cum per pole
11kV Over head Line (Erection)
Supply and erection of 9 Meter Steel Tubular pole (410 SP55 as per IS: 2713) with base plate(450x450x6mm MS painted type) with two coats of red Oxide and one coat of bitumen compound at bottom till planing depth. Silver/Aluminum paint shall be painted on exterior of pole. The weight of the Pole shall be 154 kg. and outside diameter and thicknes of section shall be 165.1X5.40mm (bottom), 139.7x4.50mm (middle) and 114.3x3.65mm (top). The pole shall be erected in a pit of size 600mmx600 mm(200mmdeep) in M 20 grade PCC 300 mm muff shall be provided above the ground level in M 20 PCC Each Pole shall have M12 stud welded for earthing
Supply and erection of ACSR "Rabbit" Conductor for 11 KV Lines 1.05% sag. Conductor should be as per PDD, Leh specification.
Supply and erection of 11kV 'V' Cross Arm for Single Pole (Galvanized) ( ISMC )75x50x6mm, Lg. 1398.36mm, 9.89 Kg/mtr.)
Supply and erection of 11 kV Top Bracket/Hampeer (Galvanised) weight 2.950 Kg
Supply and erection of 11 kV Cross Arm (H Pole,T Pole and 4 Pole) 100x50x6 mm (Lg. 2200 mm) Galvanised Weight 17.38 Kg.
Supply and erection of Bracing Angle (Galvanized)( ISA 50x50x6 mm Lg 2400mm, Wt. 10.18
Supply and erection of Galvanized, size 75x40x6 mm, 22000mm(ISI Marked) including fabrication charges, Painiting support structure for GO Switch, do fuse. (15.70 Kg)
Supply and erection of Guard Chanel for D/P Fabricated (Galvanized) ( ISMC 20 X 50x6 ( Lg. 2200 mm, weight 10.80
Half Clamp weight 1.47 kg.
Full Clamp weight 2.325 kg.
Supply and erection of Galvanised Stay Set with 50x8mm stay clamp, guy insulator (2Nos.), anchor plate(200x200x6mm), nut-bolts, 2Nos turn-buckles, 1.8m long, 16 mm diameter solid GS stay rod & 7/3, 15mm dia GI stranded wire complete.
Supply and erection of GSS 7/8 SWG (4mm) for earthing
PG clamp for 50 mm2 ACSR (Rabbit) Conductor
Supply and erection of GSL 8 SWG, GI wire medium coated for running as continuous guard/earth wire.
Supply and erection of Galvanised Nuts, bolts and washers as required for erection of pole / line hardware
Eyw Hook & Screw bolts 9"x5/8" Wt. 0.483 kg. (GI)
Insulators
Supply and erection of 33 KV Polymeric composite Pin Insulator 36 kV, 10kN, Lighting Impulse 170 kV Positive and 180 kV Negative, creepage distance 320mm. as per IS
Supply and erection of 33kV Polymeric composite Disc Insulator 36kV, min failing load 70kN, Lighting Impulse 170 kV Positive and 180 kV Negative creepage distance 320mm as per IS Technical Specifications
Hardware Fittings
B & S type tension fiting including complete hardware for item 18-b above
Danger Plate (Enamelled) with clamp
Number plate(Enamelled )with clamp
Phase Plate (Set of three)(Enamelled)(RYB)
Anti climbing device
Barbed wire
Al. Binding wire
Supply and erection of Earthing Complete by GI Pipe 40 mm or GI Rod 20 mm 2.5 mtr long through GI Strip Each location shall have One earthing
Supply and erection of 11 KV lightning arrester,9 KA, 10kA station class(Heavy duty)
11 kV 400 Amps. GO Switch complete with handle, pipe & Supporting channel. As per Nigam's technical specification, relevant ISS and latest amendments.
11 kV D.O fuse unit
Cement bottoming 1:2:4 mix as per REC standards 0.45 cum per pole
CIVIL- Site Development Work
Surface dressing of the ground including removing vegetation and in-equalities not exceeding 15cm deep and disposal of rubbish, lead upto 50m and lift upto 1.5m in : All kinds of Soil:
Filling available excavated earth (excluding rock) in trenches, plinth, sides of foundation etc. Layers not exceeding 20cm in depth, consolidating each deposited layer by ramming and watering lead upto 50m and lift upto 1.5m.
Carriage for earth work upto 5km
Supplying and laying 150 mm thick machine crushed 40 mm and 20 mm blue stone aggregates in layers. Bottom layer of 50 mm thickness with 20 mm size aggregates uniformly spread and compacted and Top layer 100 mm thick with 40mm aggregate to be spread uniformly and compacted.
Supplying chemical emulsion in sealed containers including delivery, diluting and applying for antiweed treatment in yard as specified by manufacturer.
CIVIL- Trenches Work
Earth work in excavation by mechanical means (Hydraulic excavator) in foundation trenches, drains, pipes and cables etc. (not exceeding 1.5mtr in width or 10 sqm on plan) including dressing of sides and ramming of bottoms, lift upto 1.5mtr including getting out excavated soil and disposal of surplus soil as directed, within a lead of 50 mtr. Ordinary rock
Providing and laying in position cement concrete of specified grade excluding the cost of centring and shuttering- All work upto plinth level.1:4:8 (1 cement: 4 coarse sand: 8 graded stone aggregate 40mm nominal size) (A) Crushed
Providing and laying in position machine· batched, machine mixed and machine vibrated design mix cement concrete of specified grade for reinforced cement concrete structural elements, excluding the cost of centring, shuttering, finishing and reinforcement, including Admixtures in recommended proportions, (as per IS 91 03) to accelerate, retard setting of concrete improve workability without impairing strength and durability as per direction of Engineer-in-charge-M-25 grade reinforced cement concrete. All work upto plinth level.
Centring and shuttermg including strutting, propping etc. and removal of form for
Foundations: footings, bases of columns etc. for mass concrete.
Walls (any thickness) including attached pilasters, buttresses, plinth and string courses etc.
Reinforcement for R.C.C. work including straightening, cutting, bending, placing in position and binding all complete. Thermo-Mechanically Treated bars.
Structure Steel Strctural steel work welded in built up sections, trusses and framed work, including cutting, hoisting, fixing in position and applying a priming coat of approved steel primer all complete. c) In M.S. angles, channels, Tees etc. for grating work.
Providing and fixing on wall face unplasticised - Rigid PVC rain water pipes conforming to IS : 13592 Type A including jointing with seal ring conforming to IS : 5382 leaving 10 mm gap for thermal expansion.(i) single socketed pipes 110mm diameter
CIVIL- Internal road
Preparation of subgrade by excavating earth to an average of 22.5 cm depth, dressing to camber and consolidation with road roller including making good the undulation etc. and disposal of surplus earth upto 50 mtres.
Construction of (WBM) by providing close graded material, spreading in uniform layers with motor grader on prepared surface, mixing by mix in place method with rotavator at OMC, and compacting with vibratory roller to achieve the desired density, complete as per Clause 401 of MoRTH specifications (with an initial lead of 5 km) (including cost of testing of materials at site and laboratory as directed by the deptt.) (i) Using Grading I material
Cement concrete 1:2:4 (1 cement :2 coarse sand : 4 graded stone aggregate 40 mm nominal size) in pavements, laid to required slope and camber in panels as required including consolidation, finishing and tamping complete.
Providing and laying design mix cement concrete in roads, taxi tracks and runways having a minimum works test beam flexural strength of 30 kg. per sq.cm. at 28 days using not less than 340 Kg. of cement per cum of finished concrete, coarse sand and graded stone aggregate of 40 mm nominal size in appropriate proportions as per specified design criteria approved by Engineer-in-charge mechanically vibrated using needle and surface vibrators including steel form work with sturdy M.S. channel sections including curing and providing and filling construction joints and dummy joints with. approved joint filler and primer including rounding of the edges and filling the grooves 10x25mm deep at top for construction joints and 10 mmx50mm deep at top for dummy joints with joint sealing compound (conforming to grade B of IS: 1834) including making necessary arrangements for expansion joints etc. all complete.
Foundations: footings, bases of columns etc. for mass concrete.
Reinforcement for R.C.C. work including straightening, cutting, bending, placing in position and binding all complete. Thermo-Mechanically Treated bars.
Providing and laying in position bitumen hot sealing compound for expansion joints etc.
CIVIL- Fence wall
Earth work in excavation by mechanical means (Hydraulic excavator) in foundation trenches, drains, pipes and cables etc. (not exceeding 1.5mtr in width or 10 sqm on plan) including dressing of sides and ramming of bottoms, lift upto 1.5mtr including getting out excavated soil and disposal of surplus soil as directed, within a lead of 50 mtr. Ordinary rock
Providing and laying in position cement concrete of specified grade excluding the cost of centring and shuttering- All work upto plinth level. 1:4:8 (1 cement: 4 coarse sand: 8 graded stone aggregate 40mm nominal size) (A) Crushed
Providing and laying in position machine· batched, machine mixed and machine vibrated -design mix cement concrete of specified grade for reinforced cement concrete structural elements, excluding the cost of centring, shuttering, finishing and reinforcement, including Admixtures in recommended proportions, (as per IS 91 03) to accelerate, retard setting of concrete improve workability without impairing strength and durability as per direction of Engineer-in-charge-M-25 grade reinforced cement concrete. All work upto plinth level.
Foundations: footings, bases of columns etc. for mass concrete.
Reinforcement for R.C.C. work including straightening, cutting, bending, placing in position and binding all complete. Thermo-Mechanically Treated bars.
Brick work with non modular fly ash lime bricks (Flag Brick confrming to IS: 12894, class designation to average compressive strength in superstructure above Plinth level upto floor V level in: Cement mortar 1 :6 (1 cement : 6 coarse sand)
15mm Cement plaster on the rough side of single or half brick wall of mix: 1 : 4 ( 1 cement : 4 coarse sand)
Structure Steel Strctural steel work welded in built up sections, trusses and framed work, including cutting, hoisting, fixing in position and applying a priming coat of approved steel primer all complete. c) In M.S. angles, channels, Tees etc. for grating work.
Providing and fixing G.I. chain link fabric fencing of required width in mesh size 50x50mm including strengthening with 2mm dia wire or nuts, bolts and washers as required complete as per direction of Engineer-in-charge. Made of G. I. wire of dia 4mm, PVC coated to achieve outer dia, not less than 5mm in required colour and shade.
Providing and fixing concertina coil fencing with required dia 610 mm (having 15 nos. round per 6 metre length) upto 3m height of wall with existing angle iron 'Y' shaped placed 2.4m or 3.00m apart and with 9 horizontal R.B.T. stud tied with G.l. staples and G.l. clips to retain horizontal including necessary bolts or G.l. barbed wire tied to angle iron all complete as per direction of Engineer -in-charge with reinforced barbed tape (R.B.T.) I Spring core (2.5mm thick) wire of high tensile strength of 165kg/sq.mm with tape (0.52mm thick) and weight 43.478gm/metre (cost of M.S. angle, C.C. blocks shall be paid separately)
CIVIL- External Drainage wall
Earth work in excavation by mechanical means (Hydraulic excavator) in foundation trenches, drains, pipes and cables etc. (not exceeding 1.5mtr in width or 10 sqm on plan) including dressing of sides and ramming of bottoms, lift upto 1.5mtr including getting out excavated soil and disposal of surplus soil as directed, within a lead of 50 mtr. Ordinary rock
Providing and laying in position cement concrete of specified grade excluding the cost of centring and shuttering- All work upto plinth level. 1:4:8 (1 cement: 4 coarse sand: 8 graded stone aggregate 40mm nominal size) (A) Crushed
Providing and laying in position machine· batched, machine mixed and machine vibrated -design mix cement concrete of specified grade for reinforced cement concrete structural elements, excluding the cost of centring, shuttering, finishing and reinforcement, including Admixtures in recommended proportions, (as per IS 91 03) to accelerate, retard setting of concrete improve workability without impairing strength and durability as per direction of Engineer-in-charge-M-25 grade reinforced cement concrete. All work upto plinth level.
Reinforcement for R.C.C. work including straightening, cutting, bending, placing in position and binding all complete. Thermo-Mechanically Treated bars.
Brick work with non modular fly ash lime bricks (Flag Brick confrming to IS: 12894, class designation to average compressive strength in superstructure above Plinth level upto floor V level in: Cement mortar 1 :6 (1 cement : 6 coarse sand)
15mm Cement plaster on the rough side of single or half brick wall of mix: 1 : 4 ( 1 cement : 4 coarse sand)
Structure Steel work welded in built up sections, trusses and framed work, including cutting, hoisting, fixing in position and applying a priming coat of approved steel primer all complete. c) In M.S. angles, channels, Tees etc. for grating work.
Providing and laying non-pressure NP2 class (light duty) R.C.C. pipes with collars jointed with stiff mixture of cement mortar in the proportion of 1:2 (1 cement: 2 fine sand) including testing of joints etc. complete. 300 mm dia. R.C.C. pipe
CIVIL- Control room building
Earth work in excavation by mechanical means (Hydraulic excavator) in foundation trenches, drains, pipes and cables etc. (not exceeding 1.5mtr in width or 10 sqm on plan) including dressing of sides and ramming of bottoms, lift upto 1.5mtr including getting out excavated soil and disposal of surplus soil as directed, within a lead of 50 mtr. Ordinary rock Up to a depth of 2.00m below the existing ground level.
Providing and laying in position cement concrete of specified grade excluding the cost of centring and shuttering- All work upto plinth level. 1:4:8 (1 cement: 4 coarse sand: 8 graded stone aggregate 40mm nominal size) (A) Crushed
Providing and laying in position machine· batched, machine mixed and machine vibrated -design mix cement concrete of specified grade for reinforced cement concrete structural elements, excluding the cost of centring, shuttering, finishing and reinforcement, including Admixtures in recommended proportions, (as per IS 91 03) to accelerate, retard setting of concrete improve workability without impairing strength and durability as per direction of Engineer-in-charge-M-25 grade reinforced cement concrete. All work upto plinth level.
All work from plinth level upto floor V level. Walls, columns, pillars, postsand struts. M25 grade concrete
Beams, plinth beams, girders, bressumers, centilevers, suspended floor lintels roofs and staircases including spiral staircases, shelves etc. M25 grade concrete
Reinforcement for R.C.C. work including straightening, cutting, bending, placing in position and binding all complete. Thermo-Mechanically Treated bars.
Foundations: footings, bases of columns etc. for mass concrete.
Columns, Pillars, Piers, Abutments, Posts and Struts
Lintels, beams, plinth beams, girders, bressumers and cantilevers, with water proof ply 12mm thick
Suspended floors, roofs, landings, balconies and access platform with water proof ply 12mm thick
Brick work with non modular fly ash lime bricks (Flag Brick confrming to IS: 12894, class designation to average compressive strength in substructure upto Plinth level in: Cement mortar 1 :6 (1 cement : 6 coarse sand)
Brick work with non modular fly ash lime bricks (Flag Brick confrming to IS: 12894, class designation to average compressive strength in superstructure above Plinth level upto floor V level in: Cement mortar 1 :6 (1 cement : 6 coarse sand)
Half brick masonary with non modular fly ash lime gypsum bricks (FLAG bricks) of class designation 100 conforming to IS: 12894, in superstructure above plinth and up to floor V level. Cement mortar 1:4 ( 1 cement: 4 coarse sand).
Providing and laying damp-proof course 50 mm thick with cement concrete 1:2:4 (1 cement : 2 coarse sand : 4 graded stone aggregate 20mm nominal size. (A) Crushed
Celling Plaster work 6mm cement plaster 1 : 3 (1 cement: 3 fine sand) finished with a floating coat of neat cement and thick coat of Lime wash on top of walls when dry for bearing of R.C.C. slabs and beams
Internal Plaster work 15mm Cement plaster on the rough side of single or half brick wall of mix: 1 : 4 ( 1 cement : 4 coarse sand)
External Plaster work with water proofing materials 18mm Cement plaster in two coats under layer 12mm thick cement plaster 1 : 5 (1 cement : 5 coarse sand) finished with a top layer 6mm thick cement plaster 1 : 3 (1 cement: 3 coarse sand) finished rough with sponge
Supplying and filling in plinth with fine sand under floors including, watering, ramming consolidating and dressing complete. 100 mm thick
Cement concrete flooring 1:2:4 ( 1 cement: 2 coarse sand : 4 graded stone aggregate) finished with a floating coat of neat cement including cement slurry, but excluding the cost of nosing of steps etc. complete. 100 mm thick
Kota stone slab flooring over 20mm (average) thick base laid over and jointed with grey cement slurry mixed with pigment to match the shade of the slab including rubbing and polishing complete with base of cement mortar 1:4 (1 cement: 4 coarse sand) : 25 mm thick
Providing and laying vitrified floor tiles in different sizes (thickness to be specified by the manufacturer) with water absorption less than 0.08% and conforming to lS: 15622 of approved make in all colours and shades, laid on 20mm thick cement mortar 1:4 (1 cement :4 coarse sand) including grouting the joints with white cement and matching pigments etc. complete Size of tile 60x60cm
Providing and fixing Ceramic glazed floor tiles 300x300 mm (thickness to be specified by the manufacturers) of 1st quality conforming to IS: 13755 of NITCO, ORIENT, SOMANY, KAJARIA or equivalent make in colour such as White, Ivory, Grey, Fume Red, Brown laid on 20 mm thick bed of Cement Mortar 1: 4 ( 1 cement : 4 coarse sand) including pointing the joints with white cement and matching pigment etc., complete. For toilet & pantry etc. area
Providing and fixing 1st quality ceramic glazed tiles conforming to IS :·13753 of minimum thickness 5 mm of approved make like NITCO, ORIENT, SOMANY KAJARIA, or equivalent make in all colour, shades except begundy, bottle green, black of any size as approved by Eningeerin- Charge in skirting, risers of steps and dados over 12 mm thick bed of Cement Mortar 1:3 ( 1 cement: 3 coarse sand) and jointing wtih grey cement slurry@ 3.3 kg per sqm including pointing in white cement mixed with pigment of matching shade complete. For toilet & pantry etc. area Skirting
Suppying and fixing rolling shutters of approved make, made of required size M.S. laths interlocked together through their entire length and jointed together at the end by end locks mounted on specially designed pipe shaft with brackets, side guides and arrangements for inside and outside locking with push and pull operation complete including the cost of providing and fixing necessary 27.5 cm long wire springs manufacture from high tensile steel wire of adequate strength confirming to IS 4454 part1 and M.S. top cover of required thickness for rolling shutters. 80x1.25 mm M.S. laths with 1.25 mm thick top cover.
Providing and fixing ball bearing for rolling shutters.
Providing and fixing stainless steel (Grade 304) railing made of Hollow tubes channels, plates etc.including welding ,grinding, buffing, polishing and making curvature (wherever required) and fitting the same with necessary stainless steel nuts and bolts complete,i/c fixing the railing with necessary accessories and stainless steel dash fasteners, stainless steel bolts etc. of required size on the top of the floor or the side of waist slab with suitable arrangement as per approval of Engineer-in-charge, (for payment purpose only weight of stainless steel members shall be considered excluding
Applying one coat of water thinable cement primer of approved brand and manufacture on wall surface
Distempering with oil bound washable distemper of approved brand and manufacture to give an even shade New work (two or more coats) over and including priming coat with cement primer
Finishing walls with textured exterior paint of required shade on New work (two or more coats applied @ 3.28 litre/10sqm over and including base coat of water proofing cement paint applied@ 2.20kg/10sqm)
Applying primary coat with ready mixed red oxide Zinc Chromate primer of approved brand and manufacture on steel galvanised iron/steel works
Finishing with Epoxy paint (two or more coats) at all locations prepared and applied as per manufacturer's specifications including appropriate priming coat, preparation of surface, etc complete On steel work
Providing and laying integral cement based water proofing treatment including prepration of surfaces as required for treatment of roofs, balconies, terracies etc consisting of following operations. a) applying a slurry coat of neat cement using 2.75kg/ sqm of cement admixed with water proofing compound conforming to IS 2645 and approved by Engineer-in-charge over the RCC Slab including adjoining walls upto 300mm height including cleaning the surface before treatment. b) Laying brick bats with mortar using broken bricks/ Brick Bats 25mm to 115mm size with 50% of Cement mortar 1:5 (1 Cement : 5 coarse sand) admixed with water proofing compound conforming to IS 2645 and approved by Engineer-in-charge over 20mm thick layer of cement mortar of mix 1:5 (1 Cement: 5 coarse sand) admixed with water proofing compound conforming to IS 2645 and approved by Engineer-in-charge to required slope and treating similarly the adjoining walls upto 300mm height including rounding of Junctions of walls and slabs), c) After two days of proper curing applying a second coat of cement slurry using 2.75kg/sqm of cement admixed with water proofing compound conforming to IS 2645 and approved by Engineer-in-charge. d) finishing the surface with 20mm thick jointless cement mortar of mix 1 :4(1 cement: 4 coarse sand) admixed with water proofing compound conforming to IS 2645 and approved by Engineer-in-charge including laying glass fibre cloth of approved quality in top layer of plaster and finially finishing the surface with trowel with neat cement slurry and making pattern of 300x300mm/sq 3mm deep. e) The whole terrace so finished shall be flooded with water for a minimum period of two weeks for curing and for final test. All above operations to be done in order and as directed and specified by Engineer-in-charge. With average thickness of 120mm and minimum thickness at khurra as 65 mm.
Making khurras 45x45 em with average minimum thickness of 5 em cement concrete 1:2:4 (1 cement : 2 coarse sand : 4 graded stone aggregate of 20 mm nominal size) over P.V.C. sheet 1 m x1 m x 400 micron, finished with 12 mm cement plaster 1:3 (1 cement : 3 coarse sand) and a coat of neat cement, rounding the edges and making and finishing the outlet complete.
Providing and fixing white vitreous china pedestal type water closet (European type) with seat and lid, 10 litre low level white vitreous china flushing cistern & C.P. flush bend with fittings & C.I. brackets, 40 mm flush bend, overflow arrangement with specials of standard make and mosquito proof coupling of approved municipal design complete, including painting of fittings and brackets, cutting and making good the walls and floors wherever required :
1W.C. pan with ISI marked white solid plastic seat and lid
One urinal basin with 5 ltr white PVC automatic flushing cistern
White vitreous china wash basin size 630x450mm with a pair of 15 mm CP brass pillar taps
Providing and fixing 600x450mm beveled edge mirror of superior glass (of approved quality) complete with 6mm thick hard board ground fixed to wooden cleats with CP brass screws and washers complete
Providing and fixing PTMT swivelling shower, 15 mm nominal bore, weighing not less than 40 gms
Providing and fixing PTMT soap Dish Holder having length of 138mm, breadth 102mm, height of 75mm with concealed fitting arrangements, weighing not less than 106 gms.
Providing and fixing PTMT towel rail complete with brackets fixed to wooden cleats with CP brass screws with concealed fittings arrangement of approved quality and colour. 600 mm long towel rail with total length of 645 mm, width 78 mm and effective height of 88 mm, weighing not less than 190 gms.
Supplying fitting and fixing supreme brand / Prince brand or similar approved P.V.C. Pipes of following sizes, with all necessary 'R' brand or similar approved P.V.C. Fittings such as bend, tee, elbow, reducer, nipple, plug, long screw fitting, clamps etc. complete at all levels including below G.L. as directed and specified. ii) PRINCE BRAND (High presure pipe Sch-40)
15mm nominal bore
20mm nominal bore
25mm nominal bore
40mm nominal bore
Providing and fixing 100mm sand cast iron grating for gully trap
Providing and laying and jointing glazed stoneware pipes grade "A" with stiff mixture of cement mortar in the proportion of 1:1 ( 1 cement 1 fine sand ) including testing of joints etc. complete (100mm diameter)
Providing and laying and jointing glazed stoneware pipes grade "A" with stiff mixture of cement mortar in the proportion of 1:1 ( 1 cement 1 fine sand ) including testing of joints etc. complete 150 mm diameter
Providing and fixing square mouth SW gully trap grade :A: complete with CI grating brick masonry chamber with water tight CI cover with frame of 300x300mm size(inside) the weighing of cover to be not less than 4.50kg and frame to be not less than 2.70kg as per standard design 100x100mm size P type With FPS bricks class designation 75
Providing and fixing on wall face unplasticised - Rigid PVC rain water pipes conforming to IS : 13592 Type A including jointing with seal ring conforming to IS : 5382 leaving 10 mm gap for thermal expansion. (i) single socketed pipes 110mm diameter
Sintex Water Tank,2000 Litres capacity
Supplying fitting and fixing iron removal filter filling with treated sand, pebbles, manganishdioxide and other required materials of various filtration rate per hour of TARUS make with all necessary fittings such as valve,bib cock,pipe connection etc.with a free maintanance period of six monthhs (F)REVERSE OSMOSIS (R.O)-For best Quality Drinking Water (I) KENT Grand +,15 lph,8 litres storage
Providing and laying non- pressure NP2 class (light duty) RCC pipes with collars joints with stiff mixture of cement mortar in the proportion of 1:2 ( 1 cement 2 fine sand ) including testing of joints etc, complete 150 mm dia RCC pipe
0.91m deep with SFRC cover and frame (heavy duty HD-20 grade designation) 560mm internal diameter conforming to IS 12592 total weight of cover and frame to be not less than 182 kg, fixed in cement concrete 1:2:4( 1 cement 2 coarse sand 4 graded stones aggregate 20mm nominal size) including centering shuttering all complete at the external surface shall be paid for separately) With FPS bricks with class designation 75
For shutters of doors, windows & ventilatorsincluding providing and fixing hinges I pivots and making provision for fixing of fittings wherever required including the cost of EPDM rubber I neoprene gasket required (Fittings shall be paid for separately.) Polyester powder coated aluminium (minimum thickness of polyester powder coated 50 microns)
Providing and fixing 12mm thick prelaminated particle boardflat pressed three layer or graded wood particle board (conforming to IS: 12823 Grade-l type-11) in panelling fixed in aluminium doors, windows shutters and partition frames with C. P. brass I stainless steel screws etc. complete as per architectural drawings and directions of engineer-in-charge. Pre-laminated particle board with decorative lamination on both sides.
Providing and fixing glazing in aluminium door, window, ventilator shutters and partitions etc. with EPDM rubber I neoprene gasket etc. complete as per the architectural drawings and the directions of engineer-in-charge. (Cost of aluminium snap beading shall be paid in basic item.) With float glass panes of 5.50 mm thickness (weight not less than 13.50 kg/sqm)
Providing and fixing aluminium round shape handle of outer dia 100 mm with SS screws etc. Complete as per direction of Engineer-in-charge Polyester powder coated minimum thickness 50 microns aluminium
Providing and fixing 100 mm brass locks (best make of approved quality) for aluminium doors including necessary cutting and making good etc complete.
Steel work welded in built up sections/framed work including cutting, hoisting, fixing in position and applying a priming coat of approved steel primer using structural steel etc. as required. In stringers, treads landings etc. of stair cases including use of chequered plate wherever required; all complete.
Making plinth protection 50mm thick of cement concrete 1:3:6 (1 cement : 3 coarse sand : 6 graded stone aggregate 20mm nominal size) over 75mm bed of dry brick ballast 40mm nominal size well rammed, consolidated and grouted with fine sand including finishing the top smooth.
Providing and fixing 10 mm thick acid and/or alkali resistant tiles of approved make and colour using acid and/or alkali resisting mortar bedding and joints filled with acid and/or alkali resisting cement as per IS:4457 complete as per direction of Engineer-in-charge In flooring on a bed of 10 mm thick mortar 1:4 (1 acid proof cement : 4 coarse sand). Acid and alkali resistant tile
In dado/skirting on 12 mm thick mortar 1:4 (1 acid proof cement : 4 coarse sand). Acid and alkali resistant tile
Light & fan Point (First Point)
Light & fan Point (second Point)
Call bell point including MS Box of Size 180mmx100mmx60mm deep for Call bell
3 pin 6 amp plug point including earthing the 3rd pin (power Point)
3 pin 16 amp plug point including earthing the 3rd pin (power Point)
Supply & erection of PVC Copper insulated & sheathed 2 Wire circular flexible wire size 4 Sq.mm(power point)
Supply & erection of PVC sheathed copper conductor cable single core 1100V grade in sizing 6 Sq mm ( AC Point)
supply & erection of 25 Amp DP MCCB (AC point)
supply & erection of 16 Amp DP MCCB (Exhaust fan point)
Supply & erection of sheet steel enclosure distribution board suitable for MCB,s etc on wall with rag bolts -12 Way (Three Pole) Including SPMCB 10 No 6-32A & incomer DPMCB 63 A
Supply & erection of MCCB on wall or on pedestal including bonding to earth & necessary connections-200Amp,415 V ,3phase
16 Amps SPMCB
25 Amps SPMCB
40 Amps DP MCB
63 Amps FPMCB
Call bell 220/230V with double coil
Bell Push
Supply & erection of 10.5cm dia MS Fan boxes
Supply & erection of 9W LED
Supply & erection 2x24W led tube light
Supply & erection 5w led light
Ceiling Fans,1400mm Sweep (USHA/CGL)
Industrial type Exhaust Fans, 1400 RPM,18 Inches
Industrial Power Socket 32 Amps
Cable from ACDB to distribution board Al ( 4C x 35 sq mm)
CIVIL- Staff Quarter cum Engineer Quarter
Earth work in excavation by mechanical means (Hydraulic excavator) in foundation trenches, drains, pipes and cables etc. (not exceeding 1.5mtr in width or 10 sqm on plan) including dressing of sides and ramming of bottoms, lift upto 1.5mtr including getting out excavated soil and disposal of surplus soil as directed, within a lead of 50 mtr. Ordinary rock Up to a depth of 2.00m below the existing ground level.
Providing and laying in position cement concrete of specified grade excluding the cost of centring and shuttering- All work upto plinth level. 1:4:8 (1 cement: 4 coarse sand: 8 graded stone aggregate 40mm nominal size) (A) Crushed
Providing and laying in position machine· batched, machine mixed and machine vibrated -design mix cement concrete of specified grade for reinforced cement concrete structural elements, excluding the cost of centring, shuttering, finishing and reinforcement, including Admixtures in recommended proportions, (as per IS 91 03) to accelerate, retard setting of concrete improve workability without impairing strength and durability as per direction of Engineer-in-charge-M-25 grade reinforced cement concrete. All work upto plinth level.
All work from plinth level upto floor V level. Walls, columns, pillars, postsand struts. M25 grade concrete
Beams, plinth beams, girders, bressumers, centilevers, suspended floor lintels roofs and staircases including spiral staircases, shelves etc. M25 grade concrete
Reinforcement for R.C.C. work including straightening, cutting, bending, placing in position and binding all complete. Thermo-Mechanically Treated bars.
Foundations: footings, bases of columns etc. for mass concrete.
Columns, Pillars, Piers, Abutments, Posts and Struts.
Lintels, beams, plinth beams, girders, bressumers and cantilevers, with water proof ply 12mm thick.
Suspended floors, roofs, landings, balconies and access platform with water proof ply 12mm thick.
Brick work with non modular fly ash lime bricks (Flag Brick confrming to IS: 12894, class designation to average compressive strength in substructure upto Plinth level in: Cement mortar 1 :6 (1 cement : 6 coarse sand)
Brick work with non modular fly ash lime bricks (Flag Brick confrming to IS: 12894, class designation to average compressive strength in superstructure above Plinth level upto floor V level in: Cement mortar 1 :6 (1 cement : 6 coarse sand)
Half brick masonary with non modular fly ash lime gypsum bricks (FLAG bricks) of class designation 100 conforming to IS: 12894, in superstructure above plinth and up to floor V level. Cement mortar 1:4 ( 1 cement: 4 coarse sand).
Providing and laying damp-proof course 50 mm thick with cement concrete 1:2:4 (1 cement : 2 coarse sand : 4 graded stone aggregate 20mm nominal size. (A) Crushed
Celling Plaster work 6mm cement plaster 1 : 3 (1 cement: 3 fine sand) finished with a floating coat of neat cement and thick coat of Lime wash on top of walls when dry for bearing of R.C.C. slabs and beams
Internal Plaster work 15mm Cement plaster on the rough side of single or half brick wall of mix: 1 : 4 ( 1 cement : 4 coarse sand)
External Plaster work with water proofing materials 18mm Cement plaster in two coats under layer 12mm thick cement plaster 1 : 5 (1 cement : 5 coarse sand) finished with a top layer 6mm thick cement plaster 1 : 3 (1 cement: 3 coarse sand) finished rough with sponge
Supplying and filling in plinth with fine sand under floors including, watering, ramming consolidating and dressing complete. 100 mm thick
Cement concrete flooring 1:2:4 ( 1 cement: 2 coarse sand : 4 graded stone aggregate) finished with a floating coat of neat cement including cement slurry, but excluding the cost of nosing of steps etc. complete. 100 mm thick
Providing and laying vitrified floor tiles in different sizes (thickness to be specified by the manufacturer) with water absorption less than 0.08% and conforming to lS: 15622 of approved make in all colours and shades, laid on 20mm thick cement mortar 1:4 (1 cement :4 coarse sand) including grouting the joints with white cement and matching pigments etc. complete Size of tile 60x60cm
Providing and fixing Ceramic glazed floor tiles 300x300 mm (thickness to be specified by the manufacturers) of 1st quality conforming to IS: 13755 of NITCO, ORIENT, SOMANY, KAJARIA or equivalent make in colour such as White, Ivory, Grey, Fume Red, Brown laid on 20 mm thick bed of Cement Mortar 1: 4 ( 1 cement : 4 coarse sand) including pointing the joints with white cement and matching pigment etc., complete. For toilet & pantry etc. area
Providing and fixing 1st quality ceramic glazed tiles conforming to IS :·13753 of minimum thickness 5 mm of approved make like NITCO, ORIENT, SOMANY KAJARIA, or equivalent make in all colour, shades except begundy, bottle green, black of any size as approved by Eningeerin- Charge in skirting, risers of steps and dados over 12 mm thick bed of Cement Mortar 1:3 ( 1 cement: 3 coarse sand) and jointing wtih grey cement slurry@ 3.3 kg per sqm including pointing in white cement mixed with pigment of matching shade complete. For toilet & pantry etc. area Skirting
Providing and fixing stainless steel (Grade 304) railing made of Hollow tubes channels, plates etc.including welding ,grinding, buffing, polishing and making curvature (wherever required) and fitting the same with necessary stainless steel nuts and bolts complete,i/c fixing the railing with necessary accessories and stainless steel dash fasteners, stainless steel bolts etc. of required size on the top of the floor or the side of waist slab with suitable arrangement as per approval of Engineer-in-charge, (for payment purpose only weight of stainless steel members shall be considered excluding
Applying one coat of water thinable cement primer of approved brand and manufacture on wall surface
Distempering with oil bound washable distemper of approved brand and manufacture to give an even shade New work (two or more coats) over and including priming coat with cement primer
Finishing walls with textured exterior paint of required shade on New work (two or more coats applied @ 3.28 litre/10sqm over and including base coat of water proofing cement paint applied@ 2.20kg/10sqm)
Providing and laying integral cement based water proofing treatment including prepration of surfaces as required for treatment of roofs, balconies, terracies etc consisting of following operations. a) applying a slurry coat of neat cement using 2.75kg/ sqm of cement admixed with water proofing compound conforming to IS 2645 and approved by Engineer-in-charge over the RCC Slab including adjoining walls upto 300mm height including cleaning the surface before treatment. b) Laying brick bats with mortar using broken bricks/ Brick Bats 25mm to 115mm size with 50% of Cement mortar 1:5 (1 Cement : 5 coarse sand) admixed with water proofing compound conforming to IS 2645 and approved by Engineer-in-charge over 20mm thick layer of cement mortar of mix 1:5 (1 Cement: 5 coarse sand) admixed with water proofing compound conforming to IS 2645 and approved by Engineer-in-charge to required slope and treating similarly the adjoining walls upto 300mm height including rounding of Junctions of walls and slabs), c) After two days of proper curing applying a second coat of cement slurry using 2.75kg/sqm of cement admixed with water proofing compound conforming to IS 2645 and approved by Engineer-in-charge. d) finishing the surface with 20mm thick jointless cement mortar of mix 1 :4(1 cement: 4 coarse sand) admixed with water proofing compound conforming to IS 2645 and approved by Engineer-in-charge including laying glass fibre cloth of approved quality in top layer of plaster and finially finishing the surface with trowel with neat cement slurry and making pattern of 300x300mm/sq 3mm deep. e) The whole terrace so finished shall be flooded with water for a minimum period of two weeks for curing and for final test. All above operations to be done in order and as directed and specified by Engineer-in-charge. With average thickness of 120mm and minimum thickness at khurra as 65 mm.
Making khurras 45x45 em with average minimum thickness of 5 em cement concrete 1:2:4 (1 cement : 2 coarse sand : 4 graded stone aggregate of 20 mm nominal size) over P.V.C. sheet 1 m x1 m x 400 micron, finished with 12 mm cement plaster 1:3 (1 cement : 3 coarse sand) and a coat of neat cement, rounding the edges and making and finishing the outlet complete.
Providing and fixing white vitreous china pedestal type water closet (European type) with seat and lid, 10 litre low level white vitreous china flushing cistern & C.P. flush bend with fittings & C.I. brackets, 40 mm flush bend, overflow arrangement with specials of standard make and mosquito proof coupling of approved municipal design complete, including painting of fittings and brackets, cutting and making good the walls and floors wherever required :
1W.C. pan with ISI marked white solid plastic seat and lid
One urinal basin with 5 ltr white PVC automatic flushing cistern
White vitreous china wash basin size 630x450mm with a pair of 15 mm CP brass pillar taps
Providing and fixing 600x450mm beveled edge mirror of superior glass (of approved quality) complete with 6mm thick hard board ground fixed to wooden cleats with CP brass screws and washers complete
Providing and fixing Stainless Steel A ISI 304 (18/8) kitchen sink as per IS:13983 with C.I. brackets and stainless steel plug 40 mm, including painting of fittings and brackets, cutting and making good the walls wherever required : 610x510 mm bowl depth 200 mm
Providing and fixing PTMT swivelling shower, 15 mm nominal bore, weighing not less than 40 gms
Providing and fixing PTMT soap Dish Holder having length of 138mm, breadth 102mm, height of 75mm with concealed fitting arrangements, weighing not less than 106 gms.
Providing and fixing PTMT towel rail complete with brackets fixed to wooden cleats with CP brass screws with concealed fittings arrangement of approved quality and colour. 600 mm long towel rail with total length of 645 mm, width 78 mm and effective height of 88 mm, weighing not less than 190 gms.
Supplying fitting and fixing supreme brand / Prince brand or similar approved P.V.C. Pipes of following sizes, with all necessary 'R' brand or similar approved P.V.C. Fittings such as bend, tee, elbow, reducer, nipple, plug, long screw fitting, clamps etc. complete at all levels including below G.L. as directed and specified. ii) PRINCE BRAND (High presure pipe Sch-40)
15mm nominal bore
20mm nominal bore
25mm nominal bore
40mm nominal bore
Providing and fixing 100mm sand cast iron grating for gully trap
Providing and laying and jointing glazed stoneware pipes grade "A" with stiff mixture of cement mortar in the proportion of 1:1 ( 1 cement 1 fine sand ) including testing of joints etc. complete 100 mm diameter
Providing and laying and jointing glazed stoneware pipes grade "A" with stiff mixture of cement mortar in the proportion of 1:1 ( 1 cement 1 fine sand ) including testing of joints etc. complete 150 mm diameter
Providing and fixing square mouth SW gully trap grade :A: complete with CI grating brick masonry chamber with water tight CI cover with frame of 300x300mm size(inside) the weighing of cover to be not less than 4.50kg and frame to be not less than 2.70kg as per standard design 100x100mm size P type With FPS bricks class designation 75
Providing and fixing on wall face unplasticised - Rigid PVC rain water pipes conforming to IS : 13592 Type A including jointing with seal ring conforming to IS : 5382 leaving 10 mm gap for thermal expansion. (i) single socketed pipes 110mm diameter
Sintex Water Tank,2000 Litres capacity
Supplying fitting and fixing iron removal filter filling with treated sand, pebbles, manganishdioxide and other required materials of various filtration rate per hour of TARUS make with all necessary fittings such as valve,bib cock,pipe connection etc.with a free maintanance period of six monthhs (F)REVERSE OSMOSIS (R.O)-For best Quality Drinking Water (I) KENT Grand +,15 lph,8 litres storage
Providing and laying non- pressure NP2 class (light duty) RCC pipes with collars joints with stiff mixture of cement mortar in the proportion of 1:2 ( 1 cement 2 fine sand ) including testing of joints etc, complete 150 mm dia RCC pipe
0.91m deep with SFRC cover and frame (heavy duty HD-20 grade designation) 560mm internal diameter conforming to IS 12592 total weight of cover and frame to be not less than 182 kg, fixed in cement concrete 1:2:4( 1 cement 2 coarse sand 4 graded stones aggregate 20mm nominal size) including centering shuttering all complete at the external surface shall be paid for separately) With FPS bricks with class designation 75
For shutters of doors, windows & ventilatorsincluding providing and fixing hinges I pivots and making provision for fixing of fittings wherever required including the cost of EPDM rubber I neoprene gasket required (Fittings shall be paid for separately.) Polyester powder coated aluminium (minimum thickness of polyester powder coated 50 microns)
Providing and fixing 12mm thick prelaminated particle boardflat pressed three layer or graded wood particle board (conforming to IS: 12823 Grade-l type-11) in panelling fixed in aluminium doors, windows shutters and partition frames with C. P. brass I stainless steel screws etc. complete as per architectural drawings and directions of engineer-in-charge. Pre-laminated particle board with decorative lamination on both sides.
Providing and fixing glazing in aluminium door, window, ventilator shutters and partitions etc. with EPDM rubber I neoprene gasket etc. complete as per the architectural drawings and the directions of engineer-in-charge. (Cost of aluminium snap beading shall be paid in basic item.) With float glass panes of 5.50 mm thickness (weight not less than 13.50 kg/sqm)
Providing and fixing aluminium round shape handle of outer dia 100 mm with SS screws etc. Complete as per direction of Engineer-in-charge Polyester powder coated minimum thickness 50 microns aluminium
Providing and fixing 100 mm brass locks (best make of approved quality) for aluminium doors including necessary cutting and making good etc complete.
Making plinth protection 50mm thick of cement concrete 1:3:6 (1 cement : 3 coarse sand : 6 graded stone aggregate 20mm nominal size) over 75mm bed of dry brick ballast 40mm nominal size well rammed, consolidated and grouted with fine sand including finishing the top smooth.
Light & fan Point (First Point)
Light & fan Point (second Point)
Call bell point including MS Box of Size 180mmx100mmx60mm deep for Call bell
3 pin 6 amp plug point including earthing the 3rd pin (power Point)
3 pin 16 amp plug point including earthing the 3rd pin (power Point)
Supply & erection of PVC Copper insulated & sheathed 2 Wire circular flexible wire size 4 Sq.mm(power point)
Supply & erection of PVC sheathed copper conductor cable single core 1100V grade in sizing 6 Sq mm ( AC Point)
supply & errection of 25 Amp DP MCCB (AC point)
Supply & erection of sheet steel enclosure distribution board suitable for MCB,s etc on wall with rag bolts -12 Way (Three Pole) Including SPMCB 10 No 6-32A & incomer DPMCB 63 A
Supply & erection of MCCB on wall or on pedestal including bonding to earth & necessary connections-200Amp,415 V ,3phase
16 Amps SPMCB
25 Amps SPMCB
40 Amps DP MCB
Call bell 220/230V with double coil
Bell Push
Supply & erection of 10.5cm dia MS Fan boxes
Supply & erection of 9W LED
Supply & erection 2x24W led tube light
Supply & erection 5w led light
Supply & erection 12w led light
Ceiling Fans,1400mm Sweep (USHA/CGL)
Industrial Power Socket 32 Amps
CIVIL- Tower foundations
Earth work in excavation by mechanical means (Hydraulic excavator) in foundation trenches, drains, pipes and cables etc. (not exceeding 1.5mtr in width or 10 sqm on plan) including dressing of sides and ramming of bottoms, lift upto 1.5mtr including getting out excavated soil and disposal of surplus soil as directed, within a lead of 50 mtr. Ordinary rock Up to a depth of 2.00m below the existing ground level.
Providing and laying in position cement concrete of specified grade excluding the cost of centring and shuttering- All work upto plinth level. 1:4:8 (1 cement: 4 coarse sand: 8 graded stone aggregate 40mm nominal size) (A) Crushed
Providing and laying in position machine· batched, machine mixed and machine vibrated -design mix cement concrete of specified grade for reinforced cement concrete structural elements, excluding the cost of centring, shuttering, finishing and reinforcement, including Admixtures in recommended proportions, (as per IS 91 03) to accelerate, retard setting of concrete improve workability without impairing strength and durability as per direction of Engineer-in-charge-M-25 grade reinforced cement concrete. All work upto plinth level.
Foundations: footings, bases of columns etc. for mass concrete.
Reinforcement for R.C.C. work including straightening, cutting, bending, placing in position and binding all complete. Thermo-Mechanically Treated bars.
CIVIL- Equipment foundations
Earth work in excavation by mechanical means (Hydraulic excavator) in foundation trenches, drains, pipes and cables etc. (not exceeding 1.5mtr in width or 10 sqm on plan) including dressing of sides and ramming of bottoms, lift upto 1.5mtr including getting out excavated soil and disposal of surplus soil as directed, within a lead of 50 mtr. Ordinary rock
Providing and laying in position cement concrete of specified grade excluding the cost of centring and shuttering- All work upto plinth level. 1:4:8 (1 cement: 4 coarse sand: 8 graded stone aggregate 40mm nominal size) (A) Crushed
Providing and laying in position machine· batched, machine mixed and machine vibrated -design mix cement concrete of specified grade for reinforced cement concrete structural elements, excluding the cost of centring, shuttering, finishing and reinforcement, including Admixtures in recommended proportions, (as per IS 91 03) to accelerate, retard setting of concrete improve workability without impairing strength and durability as per direction of Engineer-in-charge-M-25 grade reinforced cement concrete. All work upto plinth level.
Foundations: footings, bases of columns etc. for mass concrete.
Reinforcement for R.C.C. work including straightening, cutting, bending, placing in position and binding all complete. Thermo-Mechanically Treated bars.
CIVIL- Power Transformer foundations
Earth work in excavation by mechanical means (Hydraulic excavator) in foundation trenches, drains, pipes and cables etc. (not exceeding 1.5mtr in width or 10 sqm on plan) including dressing of sides and ramming of bottoms, lift upto 1.5mtr including getting out excavated soil and disposal of surplus soil as directed, within a lead of 50 mtr. Ordinary rock Up to a depth of 2.00m below the existing ground level.
Providing and laying in position cement concrete of specified grade excluding the cost of centring and shuttering- All work upto plinth level. 1:4:8 (1 cement: 4 coarse sand: 8 graded stone aggregate 40mm nominal size) (A) Crushed
Providing and laying in position machine· batched, machine mixed and machine vibrated -design mix cement concrete of specified grade for reinforced cement concrete structural elements, excluding the cost of centring, shuttering, finishing and reinforcement, including Admixtures in recommended proportions, (as per IS 91 03) to accelerate, retard setting of concrete improve workability without impairing strength and durability as per direction of Engineer-in-charge-M-25 grade reinforced cement concrete. All work upto plinth level.
Foundations: footings, bases of columns etc. for mass concrete.
Reinforcement for R.C.C. work including straightening, cutting, bending, placing in position and binding all complete. Thermo-Mechanically Treated bars.
Structure Steel Strctural steel work welded in built up sections, trusses and framed work, including cutting, hoisting, fixing in position and applying a priming coat of approved steel primer all complete. c) In M.S. angles, channels, Tees etc. for grating work.
CIVIL- Station Transformer foundations
Earth work in excavation by mechanical means (Hydraulic excavator) in foundation trenches, drains, pipes and cables etc. (not exceeding 1.5mtr in width or 10 sqm on plan) including dressing of sides and ramming of bottoms, lift upto 1.5mtr including getting out excavated soil and disposal of surplus soil as directed, within a lead of 50 mtr. Ordinary rock
Providing and laying in position cement concrete of specified grade excluding the cost of centring and shuttering- All work upto plinth level. 1:4:8 (1 cement: 4 coarse sand: 8 graded stone aggregate 40mm nominal size) (A) Crushed
Providing and laying in position machine· batched, machine mixed and machine vibrated -design mix cement concrete of specified grade for reinforced cement concrete structural elements, excluding the cost of centring, shuttering, finishing and reinforcement, including Admixtures in recommended proportions, (as per IS 91 03) to accelerate, retard setting of concrete improve workability without impairing strength and durability as per direction of Engineer-in-charge-M-25 grade reinforced cement concrete. All work upto plinth level.
Foundations: footings, bases of columns etc. for mass concrete.
Reinforcement for R.C.C. work including straightening, cutting, bending, placing in position and binding all complete. Thermo-Mechanically Treated bars.
Structure Steel Strctural steel work welded in built up sections, trusses and framed work, including cutting, hoisting, fixing in position and applying a priming coat of approved steel primer all complete. c) In M.S. angles, channels, Tees etc. for grating work.
CIVIL- Landscaping works
Supplying and stacking of good earth at site including royalty and carriage complete (earth measured in stacks will be reduced by 20% for payment)
Supplying & stacking sludge at site including royalty and carriage complete ( sludge measured in stakes will be reducd by 8% for payment.
Supplying and stacking at site dump manure from badi or other approved source including carriage upto 1 km (manure measured in stacks will be reduced by 8% for payment) 18.4.2 Screened through sieve of I.S. designation 16 mm
Fine dressing of the ground
Spreading of sludge, dump manure or/good earth in required thickness as per directions of officer incharge (cost of sludge, dump manure or/and good earth to be paid seperately)
Mixing earth and sludge or manure in proportion specified or directed by officer in charge.
Providing and fixing M.S. flat iron tree guard 60 cm dia. and 2 m high above ground level formed of 4 nos. 25x6 mm , 2.2m long and 8 nos. 25x3 mm 2 m long vertical M.S.flats rivetted to 3 nos.25x6 mm MS flat iron rings in two halves, fixed together at site with required 6 no. of with 8 mm dia. and 30 mm long bolts including painting two coats with paint of approved brand and manufacture over a coat of primer. One name plate of 1 mm thick M.S. sheet of size 250x1 00 mm shall be welded to the tree guard near the middle height and lettered CPWD/PWD/any other approved name The tree guard shall be suitably fixed to the ground by embedding four legs of the tree guard in pits of suitable dia. and to a depth of 25 cm, refilling the pits with soil and ramming, complete in all respect as per satisfaction and direction of Officer-in-charge
TREE PLANTING Supplying and planting of ornamental trees (1'-0" height sapling) including pit making ( 60 cm x 60 cm x 60 cm ), filling the pit with appropriate soil media, manure and fertilizers as per specification and necessary maintenance for a period of one year from the date of planting complete as specified and directed . SHADE TREE (D) Bottle Brush / Nil Gulmohar / Debadaru / Weeping Willow
ABSOLUTE PROJECTS INDIA LTD
JK Electric Engineers Pvt. Ltd.
SMS INDIA PRIVATE LIMITED
stage.html
html • 0.03 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .