| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹14.8 LAccepted-AOC | L1 | Accepted-AOC Lowest Bidder | |
| 2 | L2₹20.4 L+₹2.9 L (16.3%)Rejected-Finance | L2 | Rejected-Finance Other than Lowest Bidder | |
| 3 | L3₹20.9 L+₹3.3 L (19.0%)Rejected-Finance 0000 UNNAMED ROAD GAJIYA KANTIT VINDHYACHAL MIRZAPUR UTTAR PRADESH 231307 | MIRZAPUR | UTTAR PRADESH | 231307 | L3 | Rejected-Finance Other than Lowest Bidder | |
| 4 | L4₹21.5 L+₹3.9 L (22.1%)Rejected-Finance | L4 | Rejected-Finance Other than Lowest Bidder | |
| 5 | L5₹27.4 L+₹9.8 L (55.7%)Rejected-Finance CHHANI NANAK TEHSIL MANDAL PHALLAIN JAMMU J K 180003 | JAMMU | JAMMU | J K | 180003 | L5 | Rejected-Finance Other than Lowest Bidder |
Tender Value
₹40 L
EMD Value
₹80,000
Closing Date
21 Jan 2022, 6:00 pmClosed
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
GE Kapurthala
GE Kapurthala
Repair/ Replacement/ maintenance of Street/ Security lights and external LT network including LT Equipment and allied works at Mil Stn Suranussi under GE Kapurthala
2021_MES_496715_1
GE KPT-57/2021-22
Open Tender
Electrical and Maintenance Works
Item Rate
300 days
Kapurthala
As per tender documents
8 documents required · 8 mandatory
₹500
GE Kapurthala
₹80,000
Yes
7 May 2022
22 Dec 2021
24 Jan 2022
22 Dec 2021
21 Jan 2022
30 Dec 2021
60 days
Amount
Excavation over areas in soft/loose soil not exceeding 1.5 mtr deep and not exceeding 1.5 mtr wide for laying of cables, poles/stays and struts etc and getting out including trimming sides and forming bottom surface. Complete all as specified and directed by Engineer-In-Charge.
Returning, filling in including spreading, leveling, watering and well ramming excavated hard/soft in layers not exceeding 25 cm thick each, back in trenches after cables have been laid and tested, poles, stays , struts have been erected and tested, all as specified and directed.
Removing excavated surplus soil (Soft/loose soil) obtained from excavation to a distance not exceeding 50 mtr and depositing where directed at a level not exceeding 1.5 m above the starting point. Complete all as specified and directed by Engineer-In-Charge.
M&L for for clean dry sand laid in trenches/ducts 15cm below and 8cm above for cushioning to cable. Complete all as specified and directed by Engineer-In-Charge.
Supply and lay burnt bricks sub class 'B' old size for cable protection laid length wise perpendicular to the axis of cable. Complete all as specified and directed by Engineer-In-Charge.
Supplying, Laying and Jointing testing and commissioning XLPE UG cable, sheathed armoured LT 1100 grade heavy duty with Stranded aluminum conductor through pipes in ducts. Poles/ trenches incl fixing of copper lugs, making good to disturbed surface etc for the following cross sectional area complete as per following size and Make :-Finolex/CCI/Gluster/Universal/RPG Note : Excavation and earth work to be measured and paid separately.
10 Sqmm 2 core
16 Sqmm 4 core
35 Sqmm 3.5 core
95 Sqmm 3.5 core
Supply and fix GI tubing light grade for encasing cables for mechanical protection, laid under plinth/floors/ roads/ path /culverts or fixed on walls/on poles by means of MS FI clamps with necessary bolts, nuts and washers all as specified of sizes 50mm bore complete all as specified and directed by Engineer-In-Charge.
Dismantling & taking down existing ACSR conductor of any size by opening the binding wire from HT/LT electric poles. Complete all as specified and directed by Engineer-In-Charge.
Taking down cross arms, channels, angle iron, clamps, nut, bolts, stay wire, stay assembly, GI wire, anti climbing devices, danger notice boards etc. Complete all as specified and directed by Engineer-In-Charge.
Taking down old broken LT PCC poles carefully and including breaking of PCC making good the disturbed surface. Complete all as specified and directed by Engineer-In-Charge.
Taking down old rusted GI pipe of any size from pole/trench complete all as specified.
Taking down insulators off size & type all as specified. Complete all as specified and directed by Engineer-In-Charge.
Taking out old defective/burnt underground cable from trenches/ floors/road/wall /pipe/ pole LT cable of any size/ description including Complete all as specified and directed by Engineer-In-Charge.
Supply and fixing aluminium conductor steel reinforced for overhead lines on poles including aluminium binding wire 14 SWG, jumpers, line tapes etc complete all as specified of size weasel and mink. Note :- For payment purpose weight of ACSR condcutor shall be considered. Make Jaipuria/Alind/ICC/NICCO
Supply and fixing MS cross arms, bracing, supports, clamps and back plates fabricated from structural steel section including nuts, bolts, washers, welding bending, cold or hot, drilling joles or bolt in any shape of size including 2 coat of aluminium paint over a coat of red oxide primer complete all as specified and directed.
Supply and fixing continues earth wire 4 mm dia galvanised steel wire including galvanised mild steel binding wire 14 SWG complete all as specified. Note : For payment purposed wt of 4 mm dia galnanised wire only shall be taken and clamps, hooks shall be measured and paid separately.
Supply and fixing Pin type insulator porcelain viterous white brown or green incl one galvanised mild steel spindle two galvanised iron washer and one galvanised iron nutrs 150 mm height, 150 mm dia for 11000 volts grade. Make Jaipur/Rashtriya
Supply and fixing Disc type composite polymeric insulators, 11000 volts grade, 45 KN, with tension clamps, bolts, nuts etc complete all as specified and directed . Make Jaipur/Rashtriya
Supply and fixing of post insulator porclain vitreous, white, brown or green suitable for Gang operated Air nrake switch 11000 volts including mild steel spindle, nut, bolts etc Complete all as specified and directed by Engineer-In-Charge. Make Jaipur/Rashtriya
Supply and fixing Loop type insulator porcelain vitreous, white or brown for HT say large size with overall diamensions 65 x 140 mm, clearance hole 20 mm for 11000 volts grade. Complete all as specified and directed by Engineer-In-Charge. Make Jaipur/Rashtriya
Supply, erecting intruely vertically position concrete pole 9 Mtr long of size 102 mm x 172 mm at top and 102mmx279 mm at bottom class 10 complete including painting of pole up to 1.5 Mtr high from PCC coping in black & white strip each of 30mm high with two coats of synthetic enamel paint complete all as specified and directed (Excavation/ earthwork/PCC work shall be measured & paid separatelly) including taking out existing unserviceable pole & removing from site.Make Cement Fabric chandigarh/Punjab concrete Ltd/PCIC/ECI
Material & labour for PCC work (1:4:8) type D-2 using 40 mm graded stone aggregate in foundation of electric pole, etc including necessary form work and fare finish to exposed surfaces without using extra cement etc. Complete all as specified and directed by Engineer-In-Charge.
Material & labour for PCC work (1:3:6) type C-2 using 40 mm graded mechnically crushed stone aggregate in foundation of stay/coping of c pole including necessary form work and fare finish to exposed surfaces without using extra cement etc. Complete all as specified and directed by Engineer-In-Charge.
Material and labour for plain cement concrete (1:2:4) type B-1 using 20 mm graded stone aggregates for coping around poles,including necessary form work finishing even and smooth without using extra cement. Complete all as specified and directed by Engineer-In-Charge.
Material and Labour for stay assembly complete with 20 mm dia, 2100 mm long stay rod with threaded ends and GI nuts, two numbers thimbles MS clamps made out of 40 mm x 6 mm flat iron including MS nuts bolts and washers 300 mm x 300 mm x 6 mm MS stay plate stay bow of size 40 cm long 16 mm dia, loop type insulator including painting the exosed MS work with 2 coats of aluminium paint over a coat of red oxide primer complete all as shown in electrical plate No 1 (Earth work, concrete work, loop type insulators, stay strand, clamp shall be measured and paid for separately.
Material and Labour for galvanised stay strand size 7/4 mm. Complete all as specified and directed by Engineer-In-Charge.
Supply and fixing for Danger notice plate for HT of 25 cm x 20 cm x 1.6 mm thick mild steel sheet vitreous enameled white, with letters figures and conventional skuull and bones and written as "DANGER" in signal red colour and fixed with MS clamps made out of MS flat 25 mm x 3 mm , including nuts & bolts including 2 coats of aluminium paint over a coat of red oxide primer all as specified. Note :- Instructions are to be written in three languages viz Punjabi Hindi and English.
Dismantling and taking down GO Switch off size including, operating machanism etc complete from any position.
Supplying and fixing switch Air break Gang Operated Switch outdoor type HT 11 KV triple poles 400 amps with fixed contacts of phosphorus bronze and moving contacts of copper with mechnically operating from ground level vertical mounted complete with HT insulator on steel frame operating rod made out of 25 mm GI pipe medium grade worked from ground level with handle and locking arragement with 12 insulators with drop out fuses complete all as per specified and directed by Engr-in-Charge and (Clamps/cross arms shall be measured and paid for separately) Make : ABB/Pactil/Oblum/Rashtrya.
Supply, fixing and testing & cable jointing Kit for 11 KV grade cable for indoor type ermination cold shrinkable joint complete with joining material and accessories suitable for XLPE armoured aluminium cable of size 95 Sqmm 3 Core. Complete all as specified and directed by Engineer-In-Charge. Make : Denson/M Seal/Raychem.
All as per item No 30 here-in-before in before but of size 120 sqmm to 185 sqmm 3 core. Complete all as specified and directed by Engineer-In-Charge.
Supply, fixing and testing after jointing Cable jointing Kit for 11 KV grade cable for outdoor type termination cold shrinkable joint complete with jointing material and accessories suitable for XLPE armoured aluminium cable of size 95 Sqmm 3 core. Complete all as specified and directed by Engineer-In-Charge. Make - Denson/M Seal/Raychem
All as per item No 32 here-in-before in before but of size 120 sqmm to 185 sqmm 3 core. Make - Denson/M Seal/Raychem
Supply only new insulating transformer oil and filling after dehydration of transformer oil to obtain di-electric strength not less than 50 KV at 4 mm gap , conforming to IS-335, filling in repaired transformer or for topping up of transformers installed at site. Complete all as specified and directed by Engineer-In-Charge.Make of oil : Power oil/Savita/Indian Oil.
Dehydration and filtration of transformer oil/ voltage stabilizer oil at site of installation for 11 KV, 433 step down transformer of any capacity and any make installed on poles/plinth mounted indoor/outdoor and obtaining di-electric strength minimum 50 KV (r.m.s) with in 1 minute with 2.5 mm gap with portable filtration cum dehydration machine. Note :- (Testing of di-electric strength of dehydrated transformer oil of each transformer /voltage stabilizer will be carried out in the presence of Engr-in-Charge.)
Material and labour for draining out transformer oil in a clean barrel and disconnection of internal elect connection by taking out the top cover complete including taking out burnt unserviceable HT/LT coils from limbs, cleaning of tank removal of sludge cap of transformer upto 250KVA. Complete all as specified and directed by Engineer-In-Charge.
Material and labour for replacement old burnt HT coils of transformer of cap upto 250 KVA complete by replacing super enameled copper winding of existing gauge along with insulation material all as per specified and directed.
Material and labour for replacement old burnt LT coils of transformer of cap upto 250 KVA complete by replacing super enameled copper winding of existing gauge along with insulation material. Complete all as specified and directed by Engineer-In-Charge.
Job for re-fixing /commissioning and testing complete as IE rules of transformer by reassembling of HV/LV coil after rewinding (Cores shall be kept in over for ovening of coils upto72 Hrs at 100 degree centigrade for removal of complete moisture) in tank and connection of all LT/HT electrical connection complete by re-fixing of top cover and refilling of transformer oil and making all HT/LT connections all as specified and directed by EIC upto cap 250 KVA transformer. Note: Item SNo 65 to 66 above: - (a) Cost of glass sleeves/ ebonite sleeves shall be deemed to be indicated in unit rate and nothing extra shall be paid on this account. (b) Rewinding/ new winding of HT/LT coils, new coils, new core steel lamination sheet,top cover, gasket etc shall be deemed to be included in unit quoted rate and nothing extra shall be paid on this account. (c) Transformer oil found serviceable for re-use shall be dehydrated and filtered. (d) Additional/ Extra qty of transformer oil required for topping up/maintaining the oil level shall be measured and paid under separate item of sch ‘A’. (e) Suitable container required for collection and storage of transformer oil shall be arranged by the contractor without any extra cost to the Govt. Complete all as specified and directed by Engineer-In-Charge.
Supply only LT bush assembly brass complete with double check nuts, washers and oil seal all accessories with bushing insulators suitable for transformers of capacity 63 KVA to 160 KVA. Complete all as specified and directed by Engineer-In-Charge.
Supply only LT bush assembly brass complete with double check nuts, washers and oil seal all accessories with bushing insulators suitable for transformers of capacity 200 KVA to 315 KVA. Complete all as specified and directed by Engineer-In-Charge.
Supply only HT bush assembly brass complete with double check nuts, washers and oil seal all accessories with bushing insulators suitable for transformers of capacity 63 KVA to 160 KVA. Complete all as specified and directed by Engineer-In-Charge.
Supply only HT bush assembly brass complete with double check nuts, washers and oil seal all accessories with bushing insulators suitable for transformers of capacity 200 KVA to 315 KVA. Complete all as specified and directed by Engineer-In-Charge.
Supply only 11 KV porcelain bushing insulators for HT side out door/indoor type transformer capacity 50 KVA to 315 KVA. Complete all as specified and directed by Engineer-In-Charge.
Supply only new cork sheet gasket 6 mm thick superior quality on top cover plate of the transformer of capacity 50 KVA to 315 KVA.
Supply only tap changer switch suitable for outdoor/indoor type for transformer of capacity of 50 KVA to 160 KVA, suitable for fixing on HV side to to vary the voltage on LV side upto +7.5% in sleep of 2.5%. Complete all as specified and directed by Engineer-In-Charge.
Supply only tap changer switch suitable for outdoor/indoor type for transformer of capacity of 200 KVA to 315 KVA, suitable for fixing on HV side to to vary the voltage on LV side upto +7.5% in sleep of 2.5%. Complete all as specified and directed by Engineer-In-Charge.
Supply and fixing in replacement Air breather assembly complete filled with fresh blue coloured slica gel suitable for outdoor/indoor type transformer of capacity 50 KVA to 160 KVA. Complete all as specified and directed by Engineer-In-Charge.
Supplying and laying synthetic Rubber insulated mats 25 mm thick for voltage upto 11 kv for electrical purpose as per IS 15652-2006, (superseding IS 5424) suitable for electrical shock safety of sizes 2m x 1m Make :- Jyoti/Dunlop
Material and labour for Prunning of tree branches of any sizes and dia, not less than 2 Mtr around the LT /HT OH line which obstructing the power supply/ maintenance of electric supply as well as illumination in area including repair of damage broken ACSR conductor, GI wire and jumpers and disposed exc 50 mtr away clearing area complete testing of line all as directed. (Note : (i) Rate quoted inclusive are repair to damage work in item) (ii) Each Span approx 30-40 Mtr.
Supply and fix in replacement; MCCB 250 Amp, 4 pole, 36 KA 415 Volt 50 Hz with adjustable thermal release and adjustable magnetic setting complete all as specified and directed. Make : Standard CAT Part No ISLCNF 0250 (Frame size SKB-3) or equivalent CAT part of make :-Siemen's/ L & T/Legrand/Havells)
Supply and fix in replacement, MCCB 350 Amp 04 pole 415 volt 50 HZ breaking capacity 36 KA with adjustable thermal release and adjustable magnetic setting complete all as specified and directed. Make : Havells CAT Part No IHLCNF0315 (Frame size SKB-4) or equivalent CAT part of make :-Siemen's/ L & T/Legrand/Havells) in makes indicated in Appendix 'B' of Particular Specifications complete all as specified.make :-Siemen's/ L & T/Legrand/Havells
Supply and fix in replacement; MCCB 400 Amp 04 pole 415 volt 50 HZ breaking capacity 36 KA with adjustable thermal release and adjustable magnetic setting complete all as specified and directed. make :-Siemen's/ L & T/Legrand/Havells) Specifications complete all as specified and as directed.make :-Siemen's/ L & T/Legrand/Havells
Supply, fabricating installation, electrically connected LT Busbar chamber size 450mm X 300mm X 150mm out door cubical type factory made of CRCA sheet 3.15 mm thick machine pressed and angle iron frame 40x40x6mm in around the busbar chamber body fixing on the wall including spray painted with two coats of synthetic paint from out side and inside with approved stove enameled gray paint over one coat of red oxide primer complete and suitable for 230 Volts AC single Phase 2 wire Aluminum bus bar of each capacity 100Amp & strips fully mounted on porcelain insulator including cable connection and connected acessories. Complete all as specified and directed by Engineer-In-Charge.
Supply and fixing off load change over switch 415 V 50 HZ Type FP 125 Amp Make : IndoAsian/Havells/L&T.
Material and Labour earth continuity conductor or main earthing lead fixed to wall on batten or recess or chases or buried in ground or drawn in conduit/pipe or fixed to poles or any other indicated situation for loop earthing etc. as required aluminium strip 25x3 mm. Complete all as specified and directed by Engineer-In-Charge.
Material and Labour earth continuity conductor or main earthing lead fixed to wall on batten or recess or chases or buried in ground or drawn in conduit/pipe or fixed to poles or any other indicated situation for loop earthing etc. as required galvanised iron strip 32x6 mm. Complete all as specified and directed by Engineer-In-Charge.
M&L for earthing complete with galvanised steel earth plate electrode 600mm x 600mm x 6 mm thick buried directly in ground earth pit not less than 2.25 mtr below normal GL with the top edge of the plate not less then 1.5 mtr below the normal GL connected to GI 25X4mm by means of bolts, nuts, check nuts and washer of galvanised iron or steel and protected by 40mm GI pipe (light grade) and watering pipe 20mm bore GI pipe (light grade) including GI wire meshed funnel and chamber PCC (1:4:8) type D2 using 40mm grade stone aggregate, coping shall be (1:3:6) type CI using 20mm stone aggregate with RCC 1:2:4 type B1 (using 20mm graded stone aggregate) pit cover re-inforced with 8mm dia at 80mm c/c both way in lieu of CI pit cover with angle iron frame, including excavation and earth work in any type of soil and removal of surplus soil of earth complete all as shown in electrical plate of SSR Part I and as specified including charcoal dust, common salt complete and earth lead connected to earthing test point all as specified and testing of earthing on completion. NOTE 1. The unit rate includes for protection pipe and GI 32X6mm from top of earth plate up to 7.5 meter above ground level.
M&L for earthing complete with galvanised steel earth plate electrode 600mm x 600mm x 6 mm thick buried directly in ground earth pit not less than 2.25 mtr below normal GL with the top edge of the plate not less then 1.5 mtr below the normal GL connected to GI wire 4mm dia by means of bolts, nuts, check nuts and washer of galvanised iron or steel and protected by 15mm GI pipe (light grade) and watering pipe 20mm bore GI pipe (light grade) including GI wire meshed funnel and chamber PCC (1:4:8) type D2 using 40mm grade stone aggregate, coping shall be (1:3:6) type CI using 20mm stone aggregate with RCC 1:2:4 type B1 (using 20mm graded stone aggregate) pit cover re-inforced with 8mm dia at 80mm c/c both way in lieu of CI pit cover with angle iron frame excavation and earth work and removal of surplus soil of earth complete all as shown in electrical plate of SSR Part I and as specified including charcoal dust, common salt complete and earth lead connected to earthing test point all as specified and testing of earthing on completion. NOTE 1. The unit rate includes for protection pipe and GI earth wire 4.00mm dia from top of earth plate up to 7.5 meter above ground level.
Attending and rectification / redressal of day to day complaints of street / security light (HPSV,MH,Flourescent tube light, T-5, LED , Flood light fittings etc. of any make) complaints received through telephone or in person and rectification of defects fixed on street light poles 9/11 m long, building walls, roof by bringing down the fittings on grond or in position including replacement of lamp, ignitor, flexible wire, reflector etc including cleaning of glass/acrylic cover for clear reflection of light, replacement of old unserviceable street light fittings with new fittings etc as required to make the light fitting functional (Vehicle, ladder, tools and takes as required at site for repair/for making light fittings functional shall be provided by the contractor at his own cost and arrangement.Note : (i) Disconnecting electrical connections, opening up for inspection and making joint inventories of defects and spaces to be replaced, re-fixing old serviceable spares and fixing new spares in item replacement reasonbling, installing and fixing against in position testing and commissioning equipment of appliances. (i) Light fitting, ballast, starter, ignitor, diffuser, cable, flexible wire and LED drive etc if required to be replaced in repair shall be measured and paid separetely under relevant item of this BOQ as a supply only. (ii) Contractor shall deploy sufficient number of electricians and helpers as directed by Engineer-in-charge to attend the complaints and reactify the same within 24 hours of receipt of complaints, failing which a penalty of Rs. 300.00 per complaint shall be imposed on contractor besides payment of complaint shall not be allowed. Attendence record of electrician and helpers shall be maintained jointly by the Engineer-in-Charge and Contractor as well. A pucca bound maintainence register shall also be maintained by the Engineer-in-Charge and Contractor as well. (iii) Contractor's representative shall collect the complaints at complaint cell at 8.30 AM to 9.00 AM from JE E/M and report after completion of rectification of complaints and handover a complaint slip to JE E/M with user signature as a record of attending the complaints for payment purposes. (iv) Old retrived material shall be deposited in AGE E/M yard and will be given to contractor after completion of contract. (v) Contractor will deposit new material to Engineer in charge for acceptance and then material will be issued by JE E/M daily based on assesment of complaints. (vi) Supply only spares (in replacement) shall be measured and paid for separately under respective items of Schedule 'A'. The unit rate quoted by the contractor in this item shall included for the cost of fixing all types of spares, re-fixing, minor parts such as bolts nuts, washers etc. Purchase vouchers and receipt vouchers shall be attached with the RAR and Final Bill. (vii) Each complaint shall be entered in MB mentioning complaint No, date, location, defects detected, work executed, spares replaced etc in a tabular form in the enlarged MB. (viii) Users signature shall be obtained in token of complete redressal / rectification of a complaint. (ix) Cost of minor repairs, replacement of petty items such as nuts, bolts, washers, screws etc.
All as per item No. 60 but for 16 metres height high mast lights.
Supply, fix, connect and test in replacement , LED street light fitting 35 Watts (or above watt) IP 65/66 with PDC Aluminium body and toughened glass visor fitted in frame, separate driver compartment provided, secondary optical lens for superior light distribution efficiency >95 Lm/W, CCT5700K IP65, input voltage from 120-270 V power factor above 0.95 complete fitting including all accessories Note : Contractor shall provide 1 years written manufactures warranty for the LED fixture complete including driver from the certified date of completion. Make : Polycab Cat Part No PCGLS 01 30 Product code PUB0502004 and C&S electric Cat part No LTESS 12 X 2.5 HPLED/LS Product Code INDUS/30W/LS (Model Indus series) /Bajaj/Philips in makes indicated in Appendix 'B' of Particular Specifications complete all as specified and as directed Note : Contractor shall provide 1 years written manufactures warranty for the LED fixture complete including driver from the certified date of completion.
Supply, fix, connect and test in replacement, LED flood light fitting 70 Watts capacity having following specification fixture should be having pressure die cast alluminium IP 66 with extended alluminium heat sink with pressure die cast aluminium end caps with seprate control gear unit (b) Fixture should be having PMMA optics for uniform distribution (c) Input voltage 110 V to 300 V AC (d) Surge protection of 5 KV (d) Mechanical protection IK 05 (e) Power factor > 0.95 (f) Lumen/watt 105 Lumen/watt (g) THD > 10% (h) Fixture front cover with polycarbonate encapsulated (j) Fixture having fuse protection short circuit protection and over voltage protection cutt off voltage 110- 310 V having Auto shutdown mode (k) Fixture should be approved from Govt of India ministry of science & Technology (m) Brand name should be enclosed on fixture (n) LED flood light must be having discute LED Structure Make :Bajaj cat part NoPAR0201004 PCGLF 02 60 /Philips/Wipro/Crompton Greeves in makes indicated in Appendix 'B' of Particular Specifications complete all as specified and as directed by Engineer-in-Charge. Note : Contractor shall provide 1 years written manufactures warranty for the LED fixture complete including driver from the certified date of completion.
Supply, fix, connect and test in replacement , Post Top,energy saving,environmental friendly,long life aesthetically designed with symmetrical light distribution,spun aluminium landscape luminaire with high power LEDs as light source CORAL (OPAL) - IP 65 CORALMINIPT15WLED757PSYMTOPC Make : Havells/Crompton Greeves/Wipro/Philips
Supply only MCB SP, 32 to 63 Amp 240 Volts, 20 KA, B-Series, in DB / Junction Box or equivalent in makes indicated in Appendix 'B' of Particular Specifications. Complete all as specified and directed by Engineer-In-Charge.
Supply only contactor ML-2 with 415 Volt coil AC, 03 rating 32 A, 400 V Cat Part No SS90701 of Make LT. Complete all as specified and directed by Engineer-In-Charge.
Supply only constant current LED driver Bajaj Cat Part BGD 70065 Y-45W or equivalent in Appendix 'B' for relevant lights. Complete all as specified and directed by Engineer-In-Charge.
Supply only 1100 Volts grade heavy duty cable 3 core 1.5 Sqmm PVC insulated copper stranded conductor passing through and including 20 mm bore PVC pipe for connection pupose of street light fitting from DB to street light fitting by cutting with the cutter and making good in CM 1:3. Complete all as specified and directed by Engineer-In-Charge.Finolex/CCI/Gluster/Universal/RPG
Supply and fix in replacement ; Time light distribution board analog Time switch 230 volt three phase of 16 Amps rating with contactor fixed inside steel enclosure box and fixed to pole/LT Panel including clamps, nuts, bolts and washers etc complete all as specified and directed.Make Indo-Asian cat part No TL016ABO in Legrand/Scheneider/Havells in makes indicated in Appendix 'B' of Particular Specifications. Complete all as specified and directed by Engineer-In-Charge.
Supply and fix in replacement; loop type insulator, vitreous porcelain white, brown or green with over all size 65x90 mm with clearance dia of hole 16mm. Complete all as specified and directed by Engineer-In-Charge.
Supply and fix in replacement, shackle type porcelain vitreous white, green or brown insulators for working pressure 1100 volts, 90 mm dia, 75 mm height including galvanised MS straps, washers, insulator bolts, washers & nuts complete all as specified and as directed . Make : Mysore/Bengal Potteries/WS Madras or equivalent in makes indicated in Appendix 'B' of Particular Specifications
Supply and fix in replacement; pin type insulator porcelain white brown or green including one galvanized mild steel spindle two galvanised iron washer and one galvanised iron nuts 100 mm height 65 mm dia for 1100 volts grade. Complete all as specified and directed by Engineer-In-Charge.
Material and labour for boring hole under the road / pavement / hard standing with the help of trenchless technology using ultra sound technique and necessary machine for inserting GI pipe of 100/80 mm bore not less than one meter below ground level. Complete all as specified and directed by Engineer-In-Charge.
Supply, lay, joint, test and commission in replacement; under ground XLPE/PVC armoured heavy duty electric cable insulated and PVC sheathed LT with stranded aluminium conductor 1100 vols grade cross sectional area 16 Sqmm 2 core laid in trences, in floor, in duct, through pipes or along the pole. Complete all as specified and directed by Engineer-In-Charge..Make :-Finolex/CCI/Gluster/Universal/RPG
Supply, lay, joint, test and commission in replacement; under ground XLPE/PVC armoured heavy duty electric cable insulated and PVC sheathed LT with stranded aluminium conductor 1100 vols grade cross sectional area 6 Sqmm 2 core laid in trences, in floor, in duct, through pipes or along the pole. Complete all as specified and directed by Engineer-In-Charge..Make :-Finolex/CCI/Gluster/Universal/RPG
Supply and fix in replacement; 50 mm bore galvanised iron pipe light grade for cable protection fixed to pole/along wall/floor/under road etc complete all as specified and directed. Make : Jindal/Tata/BST/OswalNote : Clamps nuts & bolts etc shall be measured and paid for separately under appropriate items of sch 'A'Note : Clamps nuts & bolts etc shall be measured and paid for separately under appropriate items of sch 'A'
Material and labour for preparation of old painted surface of PCC LT poles and applying two coats of synthetic enamel paint in alteranate black and white strips of 30 cm each up to 1.5 mtr height from top of PCC coping and numbering of poles. Complete all as specified and directed by Engineer-In-Charge.
Labour only for cutting/pruning of tree branches 1.5 m all around the LT overhead lines of span not exceeding 70 m and around the pole obstruction the overhead line & removing the branches to distance not exceeding 50 m to be comlete all as specified and directed.
AGGARWAL ENGINEERING CO
J.K & Company
DUGGAL CONSTRUCTION CO
KULDEEP SINGH
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .