| Sl No | Description | Qty | Unit | LABINNOVISION L1 | Biosafe Lab India Pvt. Ltd L2 |
|---|---|---|---|---|---|
| 1.00 | Quarterly maintenance & (breakdown maintenance if any) of Supply AHUs ( 2 nos) of flow capacity 5000 cfm at 125 mm WG static pressure as per Technical Specification . | 16 | Nos | 2,750 ₹44,000 | 6,070 ₹97,120 |
| 2.00 | Quarterly maintenance & (breakdown maintenance if any) of outdoor Unit of AHU of 11 TR each ( 8 Nos) which include compressor, condenser, fan etc., expansion device, copper tubing between DX cooling coil and outdoor unit, refrigerant for the system. | 64 | Nos | 7,770 ₹5.0 L | 5,780 ₹3.7 L |
| 3.00 | Quarterly maintenance & (breakdown maintenance if any ) of Exhaust Air Handling Unit with exhaust air capacity 6500 cfm at static 175 mm WG and as per technical specification of the tender. | 16 | Nos | 1,650 ₹26,400 | 4,194 ₹67,104 |
| 4.00 | Supply and Installation of HEPA Filters for BIBO filter Assembly ( 3 filters in one set). Total CFM of BIBO is 5500. | 2 | SET | 39,600 ₹79,200 | 55,932 ₹1.1 L |
| 5.00 | Testing and validation : Testing and validation of Biosafety lab as per approved guidline/standard and approval by local/foreign authority. The details shall be as per technical specification of the tender. | 2 | Nos | 55,000 ₹1.1 L | 2,33,050 ₹4.7 L |
| 6.00 | Supply and Installation of HEPA Filters for AHU filter Assembly. AHU CFM is 5500. The detail of HEPA filter shall be as per technical specification. | 6 | Nos | 44,000 ₹2.6 L | 12,388 ₹74,328 |
| 7.00 | Supply and Installation of Fine Filters for AHU filter Assembly . AHU CFM is 5500. The other detail as per technical specification of tender. | 6 | Nos | 27,500 ₹1.6 L | 8,686 ₹52,116 |
| 8.00 | Supply and Installation of HDPE washable pre filter for AHU filter assembly . AHU CFM is 5500. The other detail as per technical specification of tender. | 12 | Nos | 11,000 ₹1.3 L | 4,898 ₹58,776 |
| 9.00 | SITC of Modulating Actuator for volume Control damper | 2 | Nos | 11,500 ₹23,000 | 20,508 ₹41,016 |
| 10.00 | ON/OFF Type actuator for volume Control damper | 2 | Nos | 11,500 ₹23,000 | 16,780 ₹33,560 |
Tender Value
₹1.1 Cr
EMD Value
₹2.2 L
Closing Date
24 Dec 2025, 6:00 pmClosed
Chief Engineer
Chief Engineer, CSD, BARC, Trombay-85
Operation and Maintenance of Bio Safety Lab III ( BSL-III) with animal facility along with mechanical and electrical system of BSL Lab at RMC facility of BARC, Parel, Mumbai. ( Period of contract -2 Years)
2025_BARC_889637_1
BARC/CSD/ET/34/2025-2026
Open Tender
Machineries/ Mechanical Engg Items
730 days
RMC Parel Mumbai
Please refer Tender documents.
4 documents required · 4 mandatory
₹0
₹2.2 L
PG Hostel Anushaktinagar, Mumbai-94
22 Jan 2026
12 Dec 2025
26 Dec 2025
12 Dec 2025
24 Dec 2025
12 Dec 2025
12 Dec 2025 - 24 Dec 2025
18 Dec 2025
Quarterly maintenance & (breakdown maintenance if any) of Supply AHUs ( 2 nos) of flow capacity 5000 cfm at 125 mm WG static pressure as per Technical Specification .
Quarterly maintenance & (breakdown maintenance if any) of outdoor Unit of AHU of 11 TR each ( 8 Nos) which include compressor, condenser, fan etc., expansion device, copper tubing between DX cooling coil and outdoor unit, refrigerant for the system.
Quarterly maintenance & (breakdown maintenance if any ) of Exhaust Air Handling Unit with exhaust air capacity 6500 cfm at static 175 mm WG and as per technical specification of the tender.
Supply and Installation of HEPA Filters for BIBO filter Assembly ( 3 filters in one set). Total CFM of BIBO is 5500.
Testing and validation : Testing and validation of Biosafety lab as per approved guidline/standard and approval by local/foreign authority. The details shall be as per technical specification of the tender.
Supply and Installation of HEPA Filters for AHU filter Assembly. AHU CFM is 5500. The detail of HEPA filter shall be as per technical specification.
Supply and Installation of Fine Filters for AHU filter Assembly . AHU CFM is 5500. The other detail as per technical specification of tender.
Supply and Installation of HDPE washable pre filter for AHU filter assembly . AHU CFM is 5500. The other detail as per technical specification of tender.
SITC of Modulating Actuator for volume Control damper
ON/OFF Type actuator for volume Control damper
Quarterly maintenance & breakdown maintenance , if any of Double door Autoclave , steam operated , high pressure high vacuum autoclave. The chamber size is approximately 600mmx600mmx1200mm.
Quarterly maintenance & breakdown maintenance ,if any of Pass Box
Quarterly maintenance & breakdown maintenance ,if any of ETP system for BSL which includes, pumps, pipings, actuators, tanks, level sensors etc.
SITC of Differential Pressure Transducer of 0-500 pa
SITC of Temperature and RH sensor in supply duct
Pressure sensor with display
SITC of Door status switch
SITC of Hawkeye
Operating the BSL facility round the clock 24 x 7 and monitoring the parameters of the lab
Providing sodium hypochloride for ETP operation of 10 % concentration
Maintenance of NPCC panel as per specifications
Maintenance of EPCC panel as per specifications
Maintenance of 400A incommer panel as per specifications
Maintenance of ETP panel as per specifications
Maintenance of VTPN/PPI/SPN DB as per specifications.
Maintenance of remote push buttion panel as per specifications
Maintinance of surface/recessed lights as per specification
Maintinance of earth stations as per specification
Comprehensive maintenance of 60kVA UPS system as per specifications.
Comprehensive maintenance of BMS, ETP, Door access system, CCTV system, fire alarm system as per specifications.
SITC of 36W LED recess lighting fixture as per specifications.
SITC of 20W LED recess lighting fixture as per specifications.
SITC of 40W LED rail type lighting fixture as per specifications.
SITC of 6A anti bacterial switch as per specifications.
SITC of 16A anti bacterial switch as per specifications.
SITC of 6A anti bacterial socket as per specifications.
SITC of 16A anti bacterial socket as per specifications.
SITC of Data point as per specification.
SITC of LED panel Indication lamps (R/Y/B/Green/yellow/Amber/white) as per specifications.
Replacement of VFD suitable for 11KW motor as per specifications.
Replacement of VFD suitable for 5.5KW motor as per specifications.
Installation of 1.1kV 3.5C/4C Aluminium/copper conductor, XLPE armoured power cable as pe specifications Upto 6Sq.mm. cable
Installation of 1.1kV 3.5C/4C Aluminium/copper conductor, XLPE armoured power cable as pe specifications 10Sq.mm to 25 Sq.mm cable
Installation of 1.1kV 3.5C/4C Aluminium/copper conductor, XLPE armoured power cable as pe specifications 185 Sq. mm cable
End Termination of copper/aluminium armoured cable as per specifications 4C x 4/6 Sq mm cable
End Termination of copper/aluminium armoured cable as per specifications 4C x 16 Sq mm cable
End Termination of copper/aluminium armoured cable as per specifications - 3.5C x 70 Sq mm cable
End Termination of copper/aluminium armoured cable as per specifications- 3.5C x 185 Sq mm cable
End Termination of copper/aluminium armoured cable as per specifications - 3.5C x 400 Sq mm cable
End Termination of copper/aluminium armoured cable as per specifications - 6P x 1.5 Sq mm control cable
End Termination of copper/aluminium armoured cable as per specifications- 2P x 1.5 Sq. mm control cable
Supply, installation, testing, commissioning of 12V 120AH battery as per specifications
Supply, installation, testinng of pripary power point using 2.5.Sqmm wire as per specification.
Supply, installation, testinng of pripary light/fan point using 1.5.Sqmm wire as per specification.
Supply, installation, testinng and commissioning of 1.5 TR split Air conditioner 5 star as per specification inverter type.
Supply, installation, testinng and commissioning of 1.5 TR Window Air conditioner 5 star as per specification inverter type.
stage.html
html • 0.03 MB
tech_eval.pdf
boq_comp_chart.xlsx
xlsx
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Tendernotice_1.pdf
PDF • 1.00 MB
Mechanical_final_specification.pdf
Additional Documents • 0.49 MB
Proforma_of_schedules_BARC_CSD_ET_34_2025_2026.pdf
Additional Documents • 0.25 MB
Electrical_specification.pdf
Additional Documents • 0.82 MB
TECHNICAL_BID_BARC_CSD_ET_34_2025_2026.xls
Additional Documents • 0.30 MB
BOQ_935069.xls
BOQ • 0.28 MB
Tender_document.pdf
Tender Documents • 1.81 MB
SCHEDULE-A_BARC_CSD_ET_34_2025_2026.pdf
Additional Documents • 0.18 MB
Download all tender documents and submit your bid