Tender ID
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹19.0 LAccepted-AOC | L1 | Accepted-AOC Being L1 | |
| 2 | L2₹22.3 L+₹2.4 L (12.3%)Rejected-Finance 11 82 GROUND FLOOR BLOCK 11 KALYANPURI EAST DELHI DELHI 110091 | EAST DELHI | DELHI | 110091 | L2 | Rejected-Finance Being other than L1 | |
| 3 | L3₹22.8 L+₹2.9 L (14.8%)Rejected-Finance 212 B 8 PARDEWANPUR LAL BANGLA KANPUR 208007 | KANPUR | KANPUR NAGAR | UTTAR PRADESH | 208007 | L3 | Rejected-Finance Being other than L1 | |
| 4 | L4₹29.4 L+₹9.6 L (48.1%)Rejected-AOC | L4 | Rejected-AOC other than L1 | |
| 5 | L5₹33.9 L+₹14.1 L (70.8%)Rejected-Finance | L5 | Rejected-Finance Being other than L1 |
Tender Value
₹35 L
EMD Value
₹70,000
Closing Date
8 Apr 2024, 6:00 pmClosed
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
Col Sharath Ravindran CWE
HQ CWE (AF) Chakeri Kanpur
REPAIR/MAINTENANCE OF HT 33 KV AND 11 KV SUBSTATION EQUIPMENTS, HT OVERHEAD LINE AND OTHER CONNECTED WORKS AT 7 AFH KANPUR CANTT
2024_MES_644915_1
CWE(AF)/CHK/EM/T-47 OF 2023-24
Open Tender
Electrical and Maintenance Works
Item Rate
180 days
GE (AF) E/M Chakeri
Please refer tender documents
8 documents required · 8 mandatory
₹500
GE (AF) E/M Chakeri
₹70,000
6 Jul 2024
2 Mar 2024
16 Apr 2024
2 Mar 2024
8 Apr 2024
25 Mar 2024
Amount
Excavation in trenches, n exc 1.5 m wide and n exc 1.5 m in depth; for foundation, etc. or for shafts, wells, cesspits,manholes, pier holes, for laying of UG Cable etc. n exc 10 sq m on plan and n exc 1.5 m in depth and getting out in soft/loose soil complete all as specified & directed by Engr-in-Charge
Returning filling in including spreading leveling watering and well ramming in layers not exceeding 25 cm in soft/loose soil complete all as specified & directed by Engr-in-Charge
Removing excavated material n.exc. 50m and depositing where directed at a level n.exc 1.5 m above starting point complete all as specified & directed by Engr-in-Charge.
Material and labour for sand cushioning with a layer dry clean Ganga river of sand 8 cm thick before laying of cable and 15 cm thick after laying of cable in trenches complete all as specified. Note: Punned thickness 18 cm shall only be measured.
M & L for un-reinforced precast concrete cable cover HVP type 1, flat of size 300x180x40mm all as specified and directed by Engr-in-Charge
Supply and laying old size sub class 'B' bricks laid flat in trenches over the cable with the length of brick perpendicular to the direction of cable length, adjacent/abutting each other for cable protection complete all as specified and directed.
M&L for boring hole under the road/pavement /hard standing with the help of trenchesless technology using ultra sound technique and necessary machine complete including HDPE pipe of 100 mm dia suitable for 0.4 mpa working pressure not less than one metre below ground level complete all as specified & directed. Note : HDPE pipe of 100 mm dia will be deemed to be included in the quoted rate.Contractor should be quote the rate including HDPE pipe 100 mm medium grade.
Supply ,laying and testing XLPE insulated , screened, PVC bedded galvanised steel strip or wire armoured HT electric power cable heavy duty with aluminium conductor 11000 volts grade cross sectional 120 sq mm 3 core, laid in trenches/ducts /encased in GI pipe /fixed to pole including taking out of unserviceable cable all as specified and directed.
Supply ,laying and testing XLPE insulated , screened, PVC bedded galvanised steel strip or wire armoured HT electric power cable heavy duty with aluminium conductor 11000 volts grade cross sectional 240 sq mm 3 core, laid in trenches/ducts /encased in GI pipe /fixed to pole including taking out of unserviceable cable all as specified and directed.
Supply ,laying and testing in XLPE insulated , screened, PVC bedded galvanised steel strip or wire armoured LT electric power cable heavy duty with aluminium conductor 1100 volts grade cross sectional 300 sq mm 3.5 core ,laid in trenches/ducts /encased in GI pipe /fixed to pole including taking out of unserviceable cable all as specified and directed
S&F in replacement in trenches /fixed on pole / wall GI pipe of 100mm bore light grade,IS-1239 marked with required size of flat iron clamp complete with bolts, nuts and washers of sizes 100 mm bore for cable protection complete all as specified and directed.
M&L for trimming / cutting and removal /uprooting of unwanted trees branches / bushes, small trees including surface dressing and leveling by surface excavation wherever required below / near overhead line including spreading of anti vegetation chemical from Chandmari substation to 7 AF Hospital substation and inside Hospital area/Md accn complete all as specified and directed
Supply and fixing in replacement of DO Fuse element of current rating up to 100 Amps complete all as specified and directed.
M&L for two coats of synthetic enamel painting on existing colour of Transformers 2 to 3.15 MVA as per colour code after preparation of old surface including writing of SM/MES No. all as specified and directed.
M&L switch air break Gang Operated triple pole mechanically operated mounted on insulator and steel frame with operating mechanism worked from ground level for current rating upto 400 Amps suitable for working voltage 33 KV complete with nut bolt washer operating pipe handle with locking arrangement complete all as specified and directed by Engr-in-Charge.
M&L switch air break Gang Operated triple pole mechanically operated mounted on insulator and steel frame with operating mechanism worked from ground level for current rating upto 200 Amps suitable for working voltage 11 KV complete all as specified and directed by Engr-in-Charge.
M&L for Lightening arrestor expulsion type complete with all fittings, transmissions class , discharge capacity 65 kilo amps suitable for 33000 volts and mounted on existing structure including replacement of all Lightening arrestor, clamp, nuts, bolts and washer etc complete all as specified and directed by Engr-in-Charge.
M& L for earthing complete with galvanized steel earth plate electrode 60cm x60 cm x6.0 mm thick buried directly in ground (earth pit not less than 2.25 Mtrs deep below ground level) with top edge of the plate not less than 1.50 Mtr below normal ground level connected to galvanized earth lead strip 32x6mm by means of bolts, nuts, check nuts and washers of galvanized iron or steel all as shown in electrical plate No.5 connected to ear thing test point all as specified or indicated including testing on completion including PCC pit in (1:3:6) type C-2 cement concrete .RCC 1:2:4 Mix type B reinforced with 6mm dia MS bars @ 150mm RCC cover slab 40mm thick with two no’s fitting handle, GI pipe 20mm dia light grade with funnel & wire mesh for watering and 40mm dia light grade GI pipe for earth strip 32x6mm protection etc Earthing result not more then 2 ohm and test result duly signed complete all as specified and directed by Engr-in-Charge. Note :- (i) The excess requirement (if more than 7.5 Mtr) of copper strip will be measured and paid separately. (ii) If excavation exceeds beyond specified depth, the extra cost will deemed to be included in this item rate.
M& L for Earth continuity conductor or main earthing lead galvanised iron strip 32x6mm fixed to wall on batten or recess or chases or buried in ground or drawn in conduit/pipe or fixed to poles or any other indicated situation for loop earthing etc. as required complete all as directed.
M&L for Chemical earthing complete with copper earth plate electrode 90cm x 60cm x 5mm, buried directly in ground( earth pit not less than 2.25 mtr deep below ground level) with top edge of the plate not less than 1.5m below ground level connected to and including copper strip of 32x6 mm protected with GI light grade pipe 40mm dia for earth electrode upto test point or upto 7.5 mtr whichever is less by means of bolts, nuts, check nuts and washers of copper washer all shown in electrical plate No 3 (of SSR part-I) connected to earthing test point all as specified or indicated including provision of necessary excavation and earth work of any type of soil, PCC pit , RCC cover, 50mm thick with 8mm dia TMT bar @ 100cm c/c both way , 20mm bore light grade watering pipe, water funnel, 40mm bore GI medium grade protection pipe, Bentinite powder, comman salt, charcoal dust, returning filling, in of soil, removal of soil to a distance of not exceeding of 50 mtr etc, including testing on completion complete all as specified. Note :- (i) Earth lead beyond 7.5 mtr from electrode to earth terminal point/main switch & GI pipe light grade 40mm dia for protection against mechanical damage to lead shall be measured separately. (ii) On testing after completion if desired earth resistance less than 1 Ohm is not obtained, the earthing will be redone at no extra cost.
Supply and fixing/laying of copper strip of size 32x6 mm as earth continuity conductor provided in between earth test point terminal and upto the equipment incl nuts, bolts and washers complete all as specified and directed.
Carryingout the repair/servicing/overhauling and calibration of HT VCB (with SF-6 Gas filled) panel by highly skilled mechanic / specialist including dismantling of operative mechanism parts, spring motor mechanism, well cleaning with petrol and CRC-226, replacement of unserviceable parts/accessories, replacement of burnt wiring as existing & rewiring the same,oiling and greasing of moving parts, checking and well cleaning of insulators and re assembling of operating mechanism after complete over hauling refilling of SF-6 Gas as desired including captive synthetic current injection test as per IS 14658 : 1999 or IS 13516 : 1993 to check to tripping mechanism of HT VCB 11 KV, 400 Amps of Make: ABB complete all as specified and directed following capacities : - NOTE : (i) All repair/servicing/overhauling and calibration work shall be carried out by the manufacturers authorised representative/OEM. (ii) Cost of spares shall be measured and paid separately under respective item of Schedule 'A':-
VCB (with SF-6 Gas filled) 11 KV 400 Amps indoor type (Incoming )
VCB (with SF-6 Gas filled) 11 KV 400 Amps indoor type (Out going )
Supply of following spares for 11 KV VCB, Make: ABB
Opening coil Y 1-24 V DC, Part No 1 V DC 000009 R-1.
Closing coil Y 2-24 V DC, Part No 1 V DC 000014 R-1.
Close push button, Part No ISF A616199R 1106.
Open push button, Part No ISAF 616199R1104.
Motor and gear assembly, 24V DC, Part No NHP 201491 R1.
2 PA mechanism with hex rod, Part No NHP 101985R002.
Switch element S 826E/L, Part No NZN 000859P11.
L Shape ON/OFF lever, Part No NHP417818P1.
Linkage between K & A, Part No NHP 201703R1.
Insulating washer K-A mech interlock, Part No NHP408187P1.
Indicating lamp LED type
Push Button plate
On/Off indicator (Mech)
Operating Shaft
Z lever
Relay Coil
Trip Coil
M & L for carrying overhauling / servicing of 33 KV Outdoor type VCB by adjustment of spring operated control mechanism assembly with checking and adjustment of stops, opening springs and shock absorber, oiling/greasing of all moving parts with recommended lubricant for smooth functioning from local and remote panel complete all as specified and directed. NOTE : All repair/servicing/overhauling and calibration work shall be carried out by the manufacturers authorised representative/OEM
Calibration and testing of VCB 33 KV remote control panel relays and checking & cleaning/decarbonising its moving & fixed contacts and ensure physical healthiness with visual check for healthy tripping of over current and earth fault, adjust tripping time, flag setting, ratio setting, instantaneous time setting etc as per installed capacity of transformer to be saved at maximum short circuit current with considering percentage impedance of transformer with artifical current injunction on primary side with current injunction machine and checking physical tripping verification of WTI and OTL, oil low level alarm bucholz alarm and trip, ensuring smooth functioning of VCB from local and remote switch complete all as specified directed. NOTE : All repair/servicing/overhauling and calibration work shall be carried out by the manufacturers authorised representative/ OEM & Calibration test report to be submitted indicating before & after settings duly signed by contractor & Engg -in-charge. .
Material and labour for replacement of old rubber insulating mat of size 2Mx1MX25 MM Thick for HT equiment ISI Marked complete all as specified and as directed by Engr-in-charge. Make Jyoti or equivalent make as specified in PS to Appx 'B' of tender documets
S& F in replacement of insulator pin type porcelain vitreous white brown or green including galvanized MS spindle two GI Washers and one GI Nut 150 mm height 150 mm dia for 11000 volts grade complete all as specified and as directed by Engr-in-charge. .
M&L for Hard core of broken stone aggregate of Granite, basalt or trap gauge above 40mm and n exc 63 mm for loose filling at E/M installation complete all as specified and as directed by Engr-in-charge.
Supply, jointing and testing in replacement of outdoor type cable end termination joint ,heat shrinkable) suitable for aluminium conductor cable of size 240 Sqmm to 300 Sqmm x 3 Core, 11000 Volts grade complete all as specified and as directed by Engr-in-charge.
Supply, jointing and testing in replacement of outdoor type cable end termination joint ,heat shrinkable) suitable for aluminium conductor cable of size 120 Sqmm to 185 Sqmm x 3 Core, 11000 Volts grade complete all as specified and as directed by Engr-in-charge. .
Supply, jointing and testing in replacement of outdoor type cable end termination joint ,heat shrinkable) suitable for aluminium conductor cable of size 50 Sqmm to 95 Sqmm x 3 Core, 11000 Volts grade complete all as specified and as directed by Engr-in-charge.
Supply jointing and testing in replacement of indoor type cable end termination joint (heat shrinkable) suitable for aluminium conductor cable of size 240 Sqmm to 300 Sqmm x 3 Core, 11000 Volts grade complete all as specified and as directed by Engr-in-charge.
Supply jointing and testing in replacement of indoor type cable end termination joint (heat shrinkable) suitable for aluminium conductor cable of size 120 Sqmm to 185 Sqmm x 3 Core, 11000 Volts grade complete all as specified and as directed by Engr-in-charge. .
Supply jointing and testing in replacement of indoor type cable end termination joint (heat shrinkable) suitable for aluminium conductor cable of size 50 Sqmm to 95 Sqmm x 3 Core, 11000 Volts grade complete all as specified and as directed by Engr-in-charge.
Supply jointing and testing in replacement of straight through joint (heat shrinkable) suitable for aluminium conductor cable of size 240 sqmm to 400 sqmm x 3 Core 11000 Volts grade complete all as specified and as directed by Engr-in-charge. .
Supply jointing and testing in replacement of straight through joint (heat shrinkable) suitable for aluminium conductor cable of size 120 sqmm to 185 sqmm x 3 Core, 11000 Volts grade complete all as specified and as directed by Engr-in-charge. .
Supply jointing and testing in replacement of straight through joint (heat shrinkable) suitable for aluminium conductor cable of size 50 sqmm to 95 sqmm x 3 Core, 11000 Volts grade complete all as specified and as directed by Engr-in-charge. .
Cleaning and preparation of old painted surface of HT six pole structure complete and painting with one coat of aluminium paint including channels, cross arms and making black & white strips with synthetic enamelled paint of 30cm height, each alternative strip upto 1.5 mtr height and writing pole numbers with yellow synthetic enamelled paint after making circular base with black synthetic enamelled paint and applying two coats of white wash on PCC coping complete all as specified and as directed by Engr-in-charge.
Maintenance and complete overhauling of 11 KV VCB of existing make/type/model/ capacity including disassembling of operating mechanism parts well cleaning with petrol and CRC-226 and replacing unserviceable spare parts reassembling of parts including well cleaning the complete panel board,main busbar,decarbonizing all joints busbar CTS,PTS, spouts metal parts and making VCB perfect operating in manual and electric mode and calibration & checking of tripping system of 11 KV circuit breaker through IDMT over current and earth fault relay at plug setting infented inservice by primary current injection method to ensure proper function of trip coil control circuit etc. during fault condition setting by expert from authorised agency of state electricity board including submission of calibration certificate complete all as specified and directed.Note:- Spare parts required to make VCB functional will be measure and paid separately under respective items and labour element for spare parts shall deemed to be included in this item.
Supply only following spare parts of HT 11 KV VCB all as directed. ( Make of VCB : C&G/ABB/L&T)
Shunt Tripping coil
Volt meter 0 to 15 KV digital type with complete wiring
Ammeter 0/20 to 100/200 Amp digital type with complete wiring
Breaker control switch 10A 660V
Electronic hooter
Push botton Actuators with carrier & contact element- non -illuminated flush spring return push button with 1 NO blockl, 22mm dia Red colour
Push botton Actuators with carrier & contact element- non -illuminated flush spring return push button with 1 NC blockl, 22mm dia Green colour.
Integrated LED pilot lamp suitable for operating at ( AC/DC) Red colour
Integrated LED pilot lamp suitable for operating at ( AC/DC) yellow colour
Integrated LED pilot lamp suitable for operating at ( AC/DC) blue colour
Integrated LED pilot lamp suitable for operating at ( AC/DC) green colour
Toggle switch assembly
Fuse holders for british pattern fuse links as per IS,13703 2A
Fuse holders for british pattern fuse links as per IS,13703 5A
TNC control switch
Panel Heater Switch
Closing coil
Vaccum interupter for indoor VCB
Spout incomming side
Spout outgoing side
VCB operating Handle
Backelite Seat
S&F in repair strip type heater 40/60 watt approx 4"/6" in length complete all as specified and as directed by Engr-in-charge.
Supply, installation,testing and commisioning in replacement of control/charging motor for 11 KV, VCB type as per existing make & model complete all as specified and as directed by Engr-in-charge.
Supply and fixing,testing,commisioning in replacement of Numerical earth fault and over current protection relay 33 KV with Aux supply of 20 to 110V AC/DC with 2 NO+2NC contact of existing make including neccesary wiring complete all as specified and as directed by Engr-in-charge. Note: All T&P & accesories for testing is carried out by contractor and no extra payment to be done for testing.
Supply and fixing,testing,commisioning in replacement of Numerical earth fault and over current protection relay 11 KV with Aux supply of 20 to 110V AC/DC with 2 NO+2NC contact of existing make & model including neccesary wiring complete all as specified and as directed by Engr-in-charge. Note: All T&P & accesories for testing is carried out by contractor and no extra payment to be done for Testing.
Maintenance of 11 KV Main Power House comprising of checking of HT LT terminals,replacement of rusted nut bolts washer,cleaning of Panels,S/stn Rooms, painting the yard Gete,shutters, Room Gates with one coat of synthetic enamel paint as required and writing the designation of equipments in english alphabets/letters as specified and mainly the following:- (a) Step down Transformer 500/400 KVA, 11KV / 415 Volt - 05 Nos. (b) Step down Transformer 160 KVA, 11KV / 415 Volt - 01 Nos. (c) 11 KV indoor VCB, up to 630 Amps, 250 MVA with bus coupler - 07 Nos. (d) LT Control panel of various capacities - 05 Nos. (e) Voltage stablizer, 3 phase, indoor, 415 volt, 500 KVA - 02 Nos. (f) Iron Gate -02 Nos (g) All remaining structure misc-01 lot (h) Rolling shutters =04 Nos
Labour & transportation for shifting of 11/0.433 KV transformer from one location to another location with in 7 AF Hospital area and making connections and testing complete all as specified and as directed by Engr-in-charge. Note : Safe transportation of transformer for shifting is responsibility of contractor.
Supply and laying in replacement of HT high voltage insulation mat made of elastomeric polymers material having a high insulation registance thus imparting total safety to human being from any leakage current having high insulation resistance of class A of size 2.5 mm thick and 1 m width suitable for 11 KV confirming to IS-15652 : 2006 including pasting of mat with SR-998 by adding thinner as per requirement complete all as specified and as directed by Engr-in-charge.
Supply and fixing in replacement of cable route markers made of galvanised iron with embossing of HT Cable supporting MS angle of 75 cm long, for HT cable route marking duly embedded in and incl PCC (1:3:6) foundation up to 30 cm incl excavation and earth work complete all as specified and as directed by Engr-in-charge.
Maintenance of six pole structure by disconnecting all incoming and out going joint and UG cable end terminal joint from GOD etc and rewinding/renewal of all joint with fresh joint & jumper cable with connector,nut bolts washer,HT taping including treatment of GOD contacts with conducting jelly complete all as specified and as directed.
Supply and Fix HT insulation tapes (10 mtr length) ISI Marked for terminating high voltage cables for insulation sealing of connection of wire and cable for bus bar insulation, transformer terminal insulation etc complete all as specified and as directed by Engr-in-charge.
Supply and Fix HT 11 KV Post insulators fixed on HT Busbar chambers with nut bolt washers as existing size complete all as specified and as directed by Engr-in-charge.
S&F in repairs cable jointing kit for 33 KV (Earthed) grade cable for outdoor termination heat shrink type end joint complete with jointing material and accessories suitable for 3 core XLPE armoured aluminium conductor cable of size 300 sqmm complete all as specified and as directed by Engr-in-charge.
S&F in replacement pin type, porcelain, vitreous, white, brown or green insulator including one galvanised mild steel spindle, two galvanised iron washers and one galvanised iron nut, 150mm height, 150mm dia for 33000 volts grade complete all as specified and as directed by Engr-in-charge.
Taking down top cover and refixing after proper cleaning,minor repairs of any, greasing and oiling of ball bearings,spring and runners complete of steel rolling shutters of area exceeding 5 sqm but n.exc 10 sqm complete all as specified and directed by Engineer-in-charge.
Dehydration,centrifusing & filtration of transformer oil of 3.15 MVA 33/11 KV transformer by mobile centrifusing & dehydation machine minimum capacity 1000 Ltrs/hours till the desired value of insulation of transformer oil electric strength as 70 KV at a gap 2.5 mm is obtained complete all as specified and directed. Note : Test Report to be submitted for BDV value before & after filtration of transformer complete all as specified and as directed by Engr-in-charge. .
Dehydration,centrifusing & filtration of transformer oil of 2 MVA 33/11 KV transformer by mobile centrifusing & dehydation machine minimum capacity 1000 Ltrs/hours till the desired value of insulation of transformer oil electric strength as 70 KV at a gap 2.5 mm is obtained complete all as specified and directed. Note : Test Report to be submitted for BDV value before & after filtration of transformer complete all as specified and as directed by Engr-in-charge. .
Supply and topping of new insulation oil (transformer oil IS-335 of 1983 marked) filtered and tested upto 70 KV di-electric strength at 2.5 mm gap in insulated sealed drum duly ISI marked complete all as specified and directed.Make :- HP/ BPL/ IOC/ SAVITA or equivalent as per Appx 'B' of Particular Specifications. NOTE : (i) Purchase Voucher and test certificate will be produced by Contractor at the time of claiming payment. (ii) Before topping up transformer oil sealed container shall be got checked at MES store yard.
Supply & Fixing in replacement of Battery Bank of 15 Battery with 2 volt each with all connected accesories along with float cum Boost charger suitable for 30 volt with all connected leads all as specified & directed by Engr-in-charge.
Repair to earth pit & earth pit cover of any type and size by using PCC 1:2:4 and plastering in CM 1:3 complete including excavation,returning filling and removal etc complete all as specified and directed by Engineer-in-charge.
Supply and fixing porcelain transformer bushing with complete stud with brass nut bolt washers complete of 36 KV IS:3347 suitable for 33/11 KV, 3.15/2 MVA transformer complete all as specified and directed by Engineer-in-charge.
Maintenance and complete overhauling and testing of 11 KV , SF-6 Load break switch consist of two no. incommer & one no. Outgoing of existing make/ type/model/capacity including disassembling of operating mechanism parts, well cleaning with petrol and CRC-226 and replacing unserviceable parts, and accessories, oiling / greasing of moving parts includng reassembling fine setting of mechanism well cleaning and decarbonization of arc control pot fixed and moving contacts ,hinges contacts and replacement of unserviceable parts insulating oil and reassembling and making Load break switch in perfect operation including well cleaning the complete panel board, main busbar, carbonizing all joints,busbar CTs,PTs spouts metal parts and components etc and checking of fuse system complete all as specified and directed by Engineer-in-charge. Note:- (a)Spare parts i.e HRC fuses holders,TNC switch,Alarm meter,Ampere meter,nut bolts,operating handles, indication bulbs required to make functional will be included in the quoted rate. (b) Replacement of burnout control wiring of existing size required to make functional system is included in the quoted rate.
Material and labour for replacement of PG clamps, Parallel grove clamps, tee, clamps and GI nuts, bolts of required size and other connectors for connecting ACSR conductors for jumpring as per site complete all as specified and directed by Engineer-in-charge.
Supply, installation, testing and commissioning of the indoor type current transformer HT 11 KV ratio 50/25/5+5 of input VA-15 type KCT-02 conforming to IS-2705 Part-I of 1981, 50 HZ, HSV-12 KV accuracy limit factor ACP-10 insulation level class-1, 28/75 short time terminal current and hrs duration 13.1 KA for 3 second suitable for SF-6/VCB of existing capacity complete all as specified and directed by Engineer-in-charge.
Supply, installation, testing and commissioning of the indoor typee 11 KV PT of ratio 11 KV/rt 3/110/vt 3/110 v/rt 3 class 0.5-3, burden 50 VA -50 VA, insulation level 28/75 KV, voltage factor 1.2 Cont and 1.9 for 30 sec, conforming to IS 3156 complete all as specified and directed by Engineer-in-charge.
Supply installation and testing of outdoor type (CTs) 33 KV current transformer -03 Nos Dry Type Polycrete having CT ratio 100/50/5+5 for connecting 33 KV side of Transformer bushing class 5P 15 VA burden suitable for protection, metering and different operation complete all as specified and directed by Engineer-in-charge.
Supply, installation, testing and commissioning of the outdoor typee 33 KV PT as existing at site conforming to IS 2705 complete all as specified and directed by Engineer-in-charge.
Supply and fix in replacement copper bus bar strips in the transformer studs for cable connections of exsiting size and capacity including necessary fabrication work with fresh nut bolts washers complete all as specified and directed by Engineer-in-charge.
S&F in replacement of air breather assembly complete with fresh blue colour silica Gel suitable for power transformer of capacity 3.15/2 MVA
S&F for in replacement of OTI Gauge suitable for power transformer of capacity 3.15/2 MVA complete all as specified & directed by Engr-in-charge.
S&F for in replacement of WTI Gauge suitable for power transformer of capacity 3.15/2 MVA complete all as specified & directed by Engr-in-charge.
Supply, laying & testing in replacement of PVC insulated, PVC sheathed cable galvanised steel strip or wire armoured, electric control cables (Heavy duty) with stranded copper conductor of size 1.5 Sqmm 4 core complete all as specified and directed by Engineer-in-charge.
Supply, laying & testing in replacement of PVC insulated, PVC sheathed cable galvanised steel strip or wire armoured, electric control cables (Heavy duty) with stranded copper conductor of size 1.5 Sqmm 8 core complete all as specified and directed by Engineer-in-charge.
S&F for in replacement of connector cable connector with suitable connector in PVC Box as per existing terminals complete with suitable control cable connector fixed at 33 KV Yard complete with testing of control cable connection complete all as specified and directed by Engineer-in-charge.
Servicing & Maintenance of existing 33 KV MRS switch Yard at Chandmari Sub Stn Comprising of 33 KV GODs, Air Break Switchs,Insulators,CTs,PTs,Lightening arrestors,33/11 KV transformer = 2 Nos, tightening of conductors,replacement of joints it any,checking of transformer bushings, studs of etc duly applying petroleum jelly after cleaning the contact from the rust and deposited carbon including tightening of all the loose connections making good for operation including replacement of burnt,rusted nut bolts as existing including cleaning and preparation of old painted surface of HT Gantry system complete pertains to 7 AF Hospital HT suply system complete all as specified and directed by Engineer-in-charge.
Supply and fixing in replacement of HT 11 KV busbar outdoor type weather and vermin proof factory fabricated CPRI approved duly painted with two coat of enamelled paint,pedestal type made out of mild steel sheet 3.15 mm thick,factory made using angle iron 40 mm x 40 mm x 6 mm and 500 mm high,front opening double door shutter weather proof,rust proof, dust proof with provision of rubber gasket and locking arrangement including HT bush,insulator & busbar (80 x6 mm) with colour code - 03 Nos and making connection with suitable size of thimbles, nuts, bolts and washers etc incl necessary earth work to fix 60 cm above ground level complete all as specified and directed by Engineer-in-charge..
Supply and fixing in replacement to cross arms / angle frame / MS sheet to made out bracings supports / clamp , back plates fabricated from structural steel sections nut bolt washers cutting welding to hot /cold drilling holes for bolts in any shape or size as indicated incl painting in two coats using synthetic enameled paint over one coat of red oxide primer as well as dismantling of existing MS work complete all as specified and directed.
Supply and fixing steel tubular electric pole, swaged type pole of overall length 11 meter having maximum tensile strength 42 Kgf/mm2 of type 410 SP-55 conforming to IS-2713-1980. respectively in true vertical position, complete with CI base plate, pole cap, bolts, nuts & screws including taking down old pole any type complete all as specified with and including the following:- (i) Excavation in post hole not exceeding 1.5 Mtr wide & 2 Mtr deep for pole foundation & getting out in hard / dense soil, returning, filling in the excavated soil after fixing the pole in foundation, ramming earth around in layers n.exc 25 cm thick and disposal of surplus soil to a distance n.exc 50 meters. (ii) M&L for providing PCC 1:4:8, type D-2 ( using 40 mm graded stone aggregate) in base of pole of size 1200mm x 600mm x 150 mm all as specified and directed. (iii) M&L for providing PCC 1:3:6, type C2 ( using 40 mm graded stone aggregate) in foundation 1200mm x 600mm x 1800 mm (sub base as mass concrete) for concrete encasing the pole up to GL all as specified and directed. (iv) M&L for providing PCC 1:2:4, type B-1 (using 20 mm graded stone aggregate) for plinth block /Collar above GL, 300 mm high and 450 mm x 450 mm square or as directed by Engr-in-Charge complete all as directed and as specified. (v) M&L for painting of pole externally with two coats of black bituminous paint up to planting depth. The remaining portion of exterior shall be painted with one coat of red oxide primer and above plinth block/ concrete collar with two coats of aluminium paint including preparation of surfaces including painting of 30 cm wide black and yellow bands (strips) 5 Nos with synthetic enamel paint in alternate layers upto the height of 1.5 Mtr above plinth block and writting pole number and feeder location by white synthetic enamel paint with proper letter size complete all as specified and directed by Engineer-in-charge.
Unbinding from insulators and Restringing/Restretching ACSR conductor of any size on HT/LT poles including binding with 2mm dia aluminium binding wire all as specified & directed by Engineer-in-charge. Note : 1. Cost of binding wire shall be included in the rate.
Unbinding and Restringing/Restretching of GI earth wire 04mm dia on HT poles and including wire with 1.63mm dia GI binding wire all as specified & directed.Note : 1. Cost of binding wire shall be included in the rate.
Supplying, straining of alumunium conductor steel reinforced (ACSR) in any specification making interconnection of net work fixing on existed structure/pole and replacement of unsv conductor on existed poles complete all as specified and directed. (Note :-Sagging length of ACSR conductor shall be deemed included in the quoted unit rates).
Supplying, drawing and fixing of continuous GI earth wire/gaurd/cradles of 4mm dia including GI binding wire 1.63 mm and GI holding hook on HT poles incl taking down old rusted GI wire all as specified and directed by Engineer-in-charge.
S&F in replacement of disc type insulator, poprcelain, vitreous in single disc assy for tension with tension clamps for conductors, working pressure 11000 volts of size 145 mm gigh and 255 mm dia ball complete all as specified and directed by Engineer-in-Charge.
S&F in replacement of insulators pin type porcelain viterous white brown or green including one galvanised MS spindle, two GI washer & one GI nut 150 mm height,150 mm dia for 11 KV grade complete all as specified and directed by Engineer-in-Charge.
Cutting/ trimming of tree branches up to 1.5 mtr distance on both sides of HT over head line and hanging over HT over head line including collection and depositing the retrieved timber at a place as directed by Engineer-in-charge. Note :- 1. Distance between two poles consider as one span. 2. The contractor must ensure that there must be no damage to HT conductor/pole because of falling of tree branches. If any damage occur due to this, the repair will be done by the contractor at his own and no extra payment will be paid to contractor in this effect.
Supply,and fixing in replacement of Fire extinguisher CO2 type 4.5 kg capacity Cylinder ISI marked IS : 15683 class 13 B type of fire fitted with PVC bend horn complete all as directed.Make Cease fire/Omex/Minimax
Supply and installion in replacement of ABC type fire extinguisher 9 kg capacity ISI marked confirming to IS 15683 with & discharge pipe etc as required.Make Cease fire/Omex/Minimax
Toping up/Refill and testing Dry chemical powder fire extinguisher ABC ,5 kg capacity ISI marked IS: 15683 with operating temp (+5)oC to (+55) 0C for class 4 A type of fire filled wity MAP ABC Powder complete all as specified and directed.Make Ceasefire /Omex/Minimax
Toping up/Refill and testing CO2 type fire extinguisher 4.5 kg capacity with squeeze grip valve operating temp (-30)o to (55) 0C for class 13 B type ISI marked confirming to IS 15683 with PVC bend horn complete all as specified and directed.Make Cease Fire /Omex/Minimax
M&L for detection of HT/LT fault by using fault locator machine hiring from civil authority complete all as specified and directed by Engr-in -Charge. Note :- In one length of cable from Panel/DB/Transformer to Panel/Transformer all faults considered as single job complete all as specified and directed.
Supply and fixing in replacement of danger notice plate of HT 25x20 cm, 1.6mm thick, MS sheet, vitreous enamelled white, with letters, figuers and conventional skull and bones in signal red colour and fixed with MS clamps made out of flat iron 25x3 mm, nuts-bolts, complete all as specified and directed.
S&F heat shrink LT end joints of size 120 sqmm to 150 sqmm complete all as specified and directed.
S&F heat shrink LT end joints of size 185 sqmm to 240 sqmm complete all as specified and directed.
S&F heat shrink LT end joints of size 300 sqmm to 400 sqmm complete all as specified and directed.
S&F heat shrink LT straight through joints of size 120 sqmm to 150 sqmm complete all as specified and directed.
S&F heat shrink LT straight through joints of size 185 sqmm to 240 sqmm complete all as specified and directed.
S&F heat shrink LT straight through joints of size 300 sqmm to 400 sqmm complete all as specified and directed.
Bharat Sales Corporation
santosh electronics
M/s Sohanil Construction
SUSHMANAND ENGINEERING WORKS
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .