Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹43.6 LAccepted-AOC | L1 | Accepted-AOC Lowest | |
| 2 | L2₹45.8 L+₹1.9 L (4.27%)Rejected-Finance 58 CHANDRALOK BUILDING MAYO HOSPITAL ROAD NAGPUR 440 018 | NAGPUR | MAHARASHTRA | 440018 | L2 | Rejected-Finance Not Lowest | |
| 3 | L3₹46.4 L+₹2.4 L (5.45%)Rejected-Finance 58 CHANDRALOK BLDG MAYO HOSPITAL ROAD NAGPUR 440018 | NAGPUR | NAGPUR | MAHARASHTRA | 440018 | L3 | Rejected-Finance Not Lowest |
| Sl No | Description | Qty | Unit | Chinmaya Enteprises L1 | Paragon Electrotechnics L3 | M/S. ELECTROPOWER TECHNOLOGIES L2 |
|---|---|---|---|---|---|---|
| 1.00 | Taking down the unserviceable LT cable of any size from tranches/ walls /floor etc complete all as specified and as directed.
Note :- laying of cable route is same as old cable route . | 200 | RM | 10 ₹2,000 | 8 ₹1,600 Lowest | 10 ₹2,000 |
| 2.00 | Supply and laying in trenches or fixing in walls / poles or drawing through pipe XLPE insulated, screened,PVC bedded, galvanised steel strip, electric power cables (heavy duty) with aluminium conductor, 1100 volts, grade cross sectional area 16 Sqmm, 4 core including testing after laid and jointed all as specified and as directed
Note:- Excavation and earth work, cable protection shall be measured and paid separetely. | 200 | RM | 240 ₹48,000 Lowest | 240 ₹48,000 Lowest | 250 ₹50,000 |
| 3.00 | Excavation in trenches in soft/loose of soil not exceeding 1.5 meter wide and not exceeding 1.5M in depth for laying of Cables, poles, stay and getting out of excavated material complete all as specified and directed. | 43.2 | CUM | 250 ₹10,800 Lowest | 280 ₹12,096 | 260 ₹11,232 |
| 4.00 | Returning, filling in, including spreading, leveling, watering and well ramming in layers not exceeding 25cm thick each, excavated soil in trenches after the cables have been laid and tested complete all as specified and directed. | 38.53 | CUM | 70 ₹2,697.1 Lowest | 70 ₹2,697.1 Lowest | 75 ₹2,889.75 |
| 5.00 | Removal of surplus soil to a distance not exc. 50m and deposited where directed at a level not exc. 1.5 m above the starting point all as specified and as directed . | 4.67 | CUM | 70 ₹326.9 Lowest | 70 ₹326.9 Lowest | 70 ₹326.9 Lowest |
| 6.00 | Supply and fix in repair Double wall Corrugated High Density Polymer Ethyl (HDPE) pipe For laying of Electric cable of size 50 mm outer diameter and 38 mm inner Diameter with IS 16285 (part 2):2001 laid in trenches, wall, floor, pole including bends, sockets and other connected accessories complete all as specified and directed | 180 | RM | 60 ₹10,800 Lowest | 60 ₹10,800 Lowest | 60 ₹10,800 Lowest |
| 7.00 | Material and labour for testing the cables with high voltage DC testing machine and locating the fault in the cables by fault locating machine to pin point exact position of fault, disconnecting faulty 1100 Volt LT cables of different sizes from both ends, removal of Fault, Re-connections and testing of cables after removal of fault complete all as specified and directed.
Notes : (i) All T&P and other accessories required for checking and finding of fault in cable shall be provided by the Contractor
(ii) Charges/rent of the fault locating mobile machine, operator, engineer, electricians etc shall be deemed to included rate quoted by Contractor.
(iii) Checking and finding fault upto 05 places of same route of the cable will be considered as one Job. | 4 | Each Job | 5,000 ₹20,000 | 5,000 ₹20,000 | 4,800 ₹19,200 Lowest |
| 8.00 | Supply and fix in repair Heat shrinkable straight through cable jointing kit for 1100 Volts grade cable joint complete with jointing material and accessories suitable for 3.5 core XLPE armoured aluminium conductor cable of size 120 Sqmm to 240 Sqmm.
Note :- Any Excavation and earth work, Returning and filling, Removing involved shall be included in quoted rate. | 4 | Each | 3,500 ₹14,000 Lowest | 3,500 ₹14,000 Lowest | 3,600 ₹14,400 |
| 9.00 | All as per item No. 8 but cable size 70 Sqmm to 95 Sqmm all complete as specified and directed. | 4 | Each | 3,200 ₹12,800 Lowest | 3,300 ₹13,200 | 3,400 ₹13,600 |
| 10.00 | All as per item No. 8 but cable size 16 Sqmm to 50 Sqmm all complete as specified and directed. | 4 | Each | 3,000 ₹12,000 Lowest | 3,000 ₹12,000 Lowest | 3,200 ₹12,800 |
Tender Value
₹45 L
EMD Value
₹90,000
Closing Date
13 Dec 2025, 6:00 pmClosed
Garrison Engineer
Military Engineer Services, Garrison Engineer, Cantt Area, Kamptee 441001
REPAIR / REPLACEMENT / MAINT OF ELECTRIC RCC / STEEL POLE, UG CABLE, PAINTING OF POLES / PANELS, SOLAR / FLOOD / STREET LIGHTS AND CONNECTED ACCESSORIES AT T LINE AREA MICTS, 299 AREA, SHIVAJI ENCLAVE AREA AND CERTAIN LOCATIONS UNDER GE KAMPTEE
2025_MES_741167_1
8851/E8
Open Tender
Civil Works
Item Rate
180 days
Kamptee
All as per NIT
8 documents required · 8 mandatory
₹500
GE Kamptee
₹90,000
Yes
2 Jan 2026
22 Nov 2025
15 Dec 2025
22 Nov 2025
13 Dec 2025
6 Dec 2025
Amount
Taking down the unserviceable LT cable of any size from tranches/ walls /floor etc complete all as specified and as directed. Note :- laying of cable route is same as old cable route .
Supply and laying in trenches or fixing in walls / poles or drawing through pipe XLPE insulated, screened,PVC bedded, galvanised steel strip, electric power cables (heavy duty) with aluminium conductor, 1100 volts, grade cross sectional area 16 Sqmm, 4 core including testing after laid and jointed all as specified and as directed Note:- Excavation and earth work, cable protection shall be measured and paid separetely.
Excavation in trenches in soft/loose of soil not exceeding 1.5 meter wide and not exceeding 1.5M in depth for laying of Cables, poles, stay and getting out of excavated material complete all as specified and directed.
Returning, filling in, including spreading, leveling, watering and well ramming in layers not exceeding 25cm thick each, excavated soil in trenches after the cables have been laid and tested complete all as specified and directed.
Removal of surplus soil to a distance not exc. 50m and deposited where directed at a level not exc. 1.5 m above the starting point all as specified and as directed .
Supply and fix in repair Double wall Corrugated High Density Polymer Ethyl (HDPE) pipe For laying of Electric cable of size 50 mm outer diameter and 38 mm inner Diameter with IS 16285 (part 2):2001 laid in trenches, wall, floor, pole including bends, sockets and other connected accessories complete all as specified and directed
Material and labour for testing the cables with high voltage DC testing machine and locating the fault in the cables by fault locating machine to pin point exact position of fault, disconnecting faulty 1100 Volt LT cables of different sizes from both ends, removal of Fault, Re-connections and testing of cables after removal of fault complete all as specified and directed. Notes : (i) All T&P and other accessories required for checking and finding of fault in cable shall be provided by the Contractor (ii) Charges/rent of the fault locating mobile machine, operator, engineer, electricians etc shall be deemed to included rate quoted by Contractor. (iii) Checking and finding fault upto 05 places of same route of the cable will be considered as one Job.
Supply and fix in repair Heat shrinkable straight through cable jointing kit for 1100 Volts grade cable joint complete with jointing material and accessories suitable for 3.5 core XLPE armoured aluminium conductor cable of size 120 Sqmm to 240 Sqmm. Note :- Any Excavation and earth work, Returning and filling, Removing involved shall be included in quoted rate.
All as per item No. 8 but cable size 70 Sqmm to 95 Sqmm all complete as specified and directed.
All as per item No. 8 but cable size 16 Sqmm to 50 Sqmm all complete as specified and directed.
Supply and fix in repair LED street light luminaires of capacity 60 watts with pressure die cast aluminium housing heat resistance toughened glass, IP 66 protection and efficacy minimum 120 Lumen per watt, complete with driver, including three core copper flexible wire of size 0.75 Sqmm for connection from street light fitting to OH line or junction box, fixing accessories and complete all as specified and directed.
All as per item No. 11 but LED Street light of capacity 90 Watt, all complete as specified and directed.
All as per item No. 11 but LED Street light of capacity 120 Watt, all complete as specified and directed.
S&F in repair LED driver for 45W to 60W LED street light fittings complete all as specified and as directed.
Supply and fixing of smart integrated 30 Watt Smart Bright, All in one Solar Street Light, including suitable hanging bracket, Overcharged & deep discharge protection for battery, MPPT solar charge controller, LiFePO4 lithium Ferro Phosphate battery, maintenance free system, inbuilt BMS system, IP-65, lumen output ≥ 1500 Lm, Colour temp 5700K, Surge protection 5 KV, 50000 burning hrs (min), including nuts, bolts, washers, complete all as specified and directed.
Supply and fixing of smart integrated 36/40 Watt Smart Bright, All in one Solar Street Light including galvanized steel pole (6 Mtr pole height) with suitable bracket for hanging, with Infra Red Remote, with built in mono crystalline panel, Lithium ferro phospate (LiFePO4) Battery , MPPT charge controller and PIR sensor with colour teperature 6000-6500 K, including nuts, bolts, washers, excavation /earth work, PCC 1:4:8 type D-2 using 40mm aggregate for pole foundations of suitable size recommended by the manufacturer and using PCC 1:2:4 B-1 for coping with suitable of size including necessary formwork etc, complete all as specified and directed.
Supply and fix of Tiranga Led Rope Light Indian Tricolor Strip Light (Orange + White + Green) Colour in Single Strip | Independence Day/Republic Day Rope Light for complete 9 meter pole (SP-31), Plug and Play Waterproof IP65 Strip Light, Complete with driver and all fixing arrangements, complete all as specified and directed.
Supply and fixing in replacement LED flood light 200 watt, Warm white 230 V AC outdoor type with thermal management in multiple optics and equipped with IP66 protection, with impact and corrosion resistant complete with driver and lamp complete, including three core copper flexible wire of size 1.50 Sqmm for connection from street light fitting to OH line or junction box, with taking down old unserviceable flood light complete all as specified and directed.
All as per item No. 18 but LED flood light 100 watt, all complete as specified and directed.
Supply and fix in repairs thermoplastic cable entry junction boxes of size 250 x 200 x 105 mm and IP-65 protection level with metric knock out fixed on poles with MS clamps, nuts, bolts and washers including MCB SPN, 6-32 amps, 'C' series, breaking capacity 10 KA, 'C' curve 240 volts, 50Hz including necessary incoming and outgoing electric connection with suitable size of copper lugs etc., separate (detachable) gland plate, bakelite connector 4 way 20 amp, dust and vermin proof, front door opening with hinges and locking arrangement, complete all as specified and as directed.
Supply and fix in repair bracket for street light fittings made out of 32 mm dia GI pipe of light grade 1.5 m long each bent to shape & size required & fixed to pole with and including flat iron clamps 02 Nos made out of 30 x 5 mm flat iron including GI Nuts, bolts and washers and painting of clamps and street light brackets with two coat of aluminium paint over a coat of red oxide primer and fittings bracket to street light fitting including taking down old unserviceable bracket of any shape and size all as specified and as directed.
Supply, erecting & fixing in replacement of steel tubular swaged pole complete with base plate, pole cap, nut bolt washer etc type 410 SP-31 (9.00 meters long) swaged poles conforming to IS 2713 (Part-I to III) 1980 all as specified including two coats of black bitumen paint through out internally and externally upto planting depth and applying two coats of aluminum paint over one coat of red oxide primer (externally) and Numbering of poles as directed including excavation /earth work, PCC 1:4:8 type D-2 using 40mm aggregate for pole foundations of size 600x600x1500mm height upto ground level and using PCC 1:2:4 B-1 for coping with size 450x450x300mm including necessary formwork complete with including taking down old unserviceable pole all as specified and as directed.
Materials and labour as in replacement for earthing complete with galvanized earth plate electrode 600 x 600 x6mm thick burried directly in ground vertically to a depth not less than 2.25 M below normal ground level ) with top edge of the plate not less than 1.50 M below normal ground level , connected to and including GI wire 4.0 mm as earth lead soldered and riveted to earth plate by means of nuts, bolts, check nuts & washers, of galvanized iron or steel with connected to test point and testing on completion including 40mm GI light grade pipe for earth lead protection from earth point to earth plate, including provn adequate quantity of charcoal dust mixed with 35 % common salt to a packed thickness of not less than 32 cm in alternate layers of charcoal and salt on all sides of earth plate with 20mm bore medium grade GI Pipe for watering,GI check nut, funnel and wire mesh with and including all necessary excavation & earth work in soft/loose soil, returning filling in, removal of surplus soil to a distance 50 metre, PCC 1:3:6 type C-1 as in earth pit, 40 mm thick RCC cover using cement concrete 1:2:4 type B-1 reinforced with & including 8 mm dia mild steel TMT bar @ 100 mm c/c Both way with suitable handle for lifting arrangement & including form work complete all as specified and shown in electrical plate No 3 of MES SSR Part I 2009 and as directed. NOTES:- (a) On testing, after completion of Job, if desired earth resistance is not obtained, the earthing shall be redone at without any extra cost by contractor.
Supply and fixing in repair retro reflective boards in shape of rectangle of size 1.0 m x1.4 m made out of 2 mm thick stainless steel both side bounded/pasted with high prismatic (iv) sheet mannufactured by avery dennison or 3 M with desired letters/logos designed as directed the board shall be supplied with and including stainless steel frame made out of 25 mm dia pipe in frame around duly welded with and including stainless steel sheet and stainless steel posts of 38 mm dia and full length of 2.20 m one side and 2.8 m other side complete all as specified and directed. ( Note :(i) Rate for fixing of boards with PCC 1:2:4 type B2 filling of size 45x45x60 cm to be incl in unit rate. (ii) The board should be written description as direction given by Engineer-in-Charge)
Supply and fixing in replacement 1100 volts grade heavy duty cable PVC insulated aluminium conductor, 4 sqmm 2 core, served with inner sheathing of PVC tape and overall PVC sheathed in service connections suspended by insulating hangers not more than 1 metre apart including 4mm suspension wire.
All as per item No. 25 but 6 sqmm 2 core, all complete as specified and directed.
All as per item No. 25 but 10 sqmm 2 core, all complete as specified and directed.
S & F in replacement 1100 Volts grade Copper conductor, PVC insulated, round sheathed (flexible), industrial cable, 1.5 sqmm 3 core.
Supply and fixing in replacment Automatic Load Transfer Switch Changeover 63 Amps, 4 Pole with CM 331 Controller, 415 Volts, with 16 A DP MCB for protection with all control wiring , incoming and outgoing connection with cable lugs, washers, nutbolts, Sheet Enclosure Box (2mm thick sheet ) which is suitable of outdoor and accessories complete with taking down old unserviceable changeover switch all as specified and as directed.
All as per item No. 29 but Automatic Load Transfer Switch Changeover 100 Amps, all complete as specified and directed.
S&F in replacement ONLOAD Changeover switch 320 Amps, 4 Pole, 415 V in sheet steel enclosure suitable for fixing on wall at existing position, including with all incoming and outgoing connection with cable lugs, washers, nutbolts and accessories complete with taking down old unserviceable changeover switch all as specified and directed.
All as per item No. 31 but ONLOAD Changeover switch 200 Amps all complete as specified and directed.
All as per item No. 31 but ONLOAD Changeover switch 100 Amps all complete as specified and directed.
All as per item No. 31 but ONLOAD Changeover switch 63 Amps all complete as specified and directed.
Supply, fixing and testing in replacement of Automatic Street light Timer Switch using combination of NATURE SWITCH for automatic switching of street lights based on LUX level of natural light consisting with Sensor (Natural Switch) along with suitable power contractor, MCB and support terminals should be enclosed in pole/ wall mountable SMC enclosure made out of Rust proof, Electric shock proof, termite proof and FR grade SMC junction Box conforming to IP 54 protection of capacity 12 KW 3 phase, current range 40 Amps, 4 wire (3 separate power contactor) including all accessories and fixing arrangement all as specified and directed.
Supply and fixing in replacement of Contactor of type MU-2P series (rating 16 A / 25A / 40A) suitable for existing Automatic Street light Timer Switch complete with taking down old unserviceable Contactor all as specified and as directed.
Supply and fixing in replacement of Contactor of Freedom series, 3 pole (rating 18 A / 25A / 40A) suitable for existing Automatic Street light Timer Switch complete with taking down old unserviceable Contactor all as specified and as directed.
Material and labour for cable route indicator made out of PCC (1:2:4) type B1 of size 60cm x 15cm x 5cm thick grouted in PCC (1:2:4) type B1 pillar fo size 30 cm x 30 x 45 cm in ground with and including necessary foam work and making on board MES LT Cable (1100 Volt) with arrow indicating cable path (marking shall be engraved and colour painted), complete all as specified and directed.
M&L for loose filling with aggregate of gauge 20 mm crushed stone back colour suitable for spreading in electrical sub stn after preparation site by removing all type of debris, removing unwanted soil, and spreading lime powder beneath the aggregate all as directed.
M&L for preparing surfaces of electric poles of any type of following sizes including MS cross arms, MS clamps, street light brackets, bracket clamps, cable protection pipe stay etc of any sizes and shape & dusting, cleaning the surface complete and applying one coat of primer and two coat of aluminium paint completely, alternate layer of yellow and black paint of 150 mm strip at the bottom of pole 1.5 mtr above coping with synthetic enamel paint all as specified and as directed by Engineer-in-Charge. (a) Height of rail /tubular poles exceeding 7.5 Mtrs upto 11 Mtrs above ground level.
All as per item No. 40 but height of steel tubular poles 7.5 Mtrs above ground level .
M&L for preparing surfaces of electric poles of RCC type of any sizes including MS cross arms, MS clamps, street light brackets, bracket clamps, cable protection pipe stay etc of any sizes and shape & dusting, cleaning the surface complete and applying one coat of primer and two coat of weather proof paint completely and alternate layer of yellow and black synthetic enamelled paint of 150 mm strips at the bottom of pole 1.5 mtr above coping all as specified and as directed.
M&L for preparing surfaces of electric Two pole Structures of any make and height of pole up to 10 Mtrs above ground level including MS cross arms, AB Switch pipe, DO Fuse assembly, MS clamps, brackets, bracket clamps, cable protection pipe stay etc of any sizes and shape & dusting, cleaning the surface complete and applying one coat of aluminium paint complete all as specified and directed.
M&L for preparing surfaces of electric Four pole Structures of any make and height of pole up to 10 Mtrs above ground level including MS cross arms, AB Switch pipe, DO Fuse assembly, MS clamps, brackets, bracket clamps, cable protection pipe stay etc of any sizes and shape & dusting, cleaning the surface complete and applying one coat of aluminium paint complete all as specified and directed.
M&L for writing pole No. with letters of size 25 mm height on pole/ plate with Black synthetic enamelled paint complete all as specified and directed.
Supply and fixing of 3M Scotchlite Reflective Tape of width 50 mm, water proof, for alternate layer of yellow and black / red tape 300 mm from bottom of pole upto 1.5 mtr above, complete all as specified and directed.
M&L for Spray painting to existing LT Panel of any capacity / size / type including mounting angle with two coats of approved colour synthetic enamel paint complete including dusting, cleaning of existing dust before applying synthetic enamel paint and writing feeder name with approved colour synthetic enamel paint complete all as specified and directed.
Cleaning of sub station area by uprooting all types vegitation, shrubs, weeds, saplings and creepers of unwanted trees complete with the help of spade, axes, crowbars, and thereafter chemical spraying will be done and other mechanical means after taking necessary electrical shutdown from concerned incharge of various sub stns of Military Stn Kamptee.
Trimming of tree branches touching of Over head Elecctrical Lines upto 2.5 mtr distance from conductors after taking necessary shutdown from concerned incharge all as directed . (Note : Space between two poles will be measured as distance in RM irrespective of nos of conductors).
Materials and labour as in replacement for earthing complete with galvanized steel earth plate electrode 600x600x6mm thick buried directly in ground vertically to a depth not less than 2.25m below ground level with top edge of earth plate not less than 1.5m below ground level connected to galvanized iron earth strip 32 x 6 mm by means of bolts, nuts, check nuts, washers of galvanized iron and connected to main switch/control board upto 7.5m away from the earth electrode including excavation earth work, PCC chamber, RCC cover slab char coal, watering pipe, wire mesh lugs, earth lead protection pipe 40 mm bore, light grade 7.5m long as applicable and as per plate No. 3 of SSR 2009 and all as specified. (a) Excavation and earth work in any type of soil. (b) Drilling of holes in electrode (c) PCC pit in cement concrete (1:2:4) type B-1 (d) 40 mm thick Pre-cast RCC cover with suitable handle. (e) Funnel with watering pipe of GI 20 mm nominal bore ,medium grade & copper lug etc. (f) 40 mm nominal bore medium grade GI protection pipe 7.50 m long for protection of earthing lead. (g) Requisite quantity of charcoal and common salt. (h) Connection to earthing test point and testing on completion.
Material and labour for transformer platform of size 2.5m x 2.5m x 1.6m height ( 0.6 m below ground level and 1.0 mtr above ground level) comprising of PCC M-7.5 grade (nominal mix) using 40mm graded crushed stone aggregate as in foundation brick work of one brick thick using old size brick in cement mortar 1:6, rendering 15mm thick in cement mortar 1:4 on all exposed brick surface finished smooth using extra cement, filling in approved earth, providing 150mm thick slab M-25 grade (nominal mix) on top reinforced with 12mm dia TMT bars and finishing top surface with 15mm thick plastering in cement mortar 1:4 finished even and smooth using extra cement, including GI pipe light grade 80mm dia of suitable height for cable protection on LT and HT side, white washing of transformer plinth and including suitable brick steps one side of the platform to reach on the platform, details of transformer to be provided on transformer plinth on GI plate, including earthwork, complete all as specified and directed. Note:- Excavation and earth work and PCC shall be included in quoted rate.
M&L for Diesel Generator Set platform of size 4.0 m x 2.25 m x 0.70 m height comprising of PCC 1:2:4 grade (nominal mix) using 40mm gradred crushed stone aggregate in foundation, providing 150mm thick hardcore of broken stone or boulders of gauge n exc. 63 mm and 150mm thick RCC slab M-25 grade (Nominal Mix) on top reinforced with 12mm dia TMT bars and finishing top surface with 15mm thick plastering in cement mortar 1:4 finished even and smooth using extra cement complete all as specified and directed. Note:- (excavation and earth work and PCC shall be Included in quoted rate).
Material & labour and T&P for disconnecting Cable connections, shifting of Transformer / DG Set, installing, testing and commissioning of Transformer / DG Set Outdoor/Indoor type of any capacity from one location to other location within the defence land (Kamptee and Nagpur) complete all as specified and directed. Note : Cost of materials required for connecting, commissioning and testing of Transformer / DG Set shall be deemed to be included in quoted rate.
NOTE:- SCHEDULE OF CREDIT (Amount shall be deducted offline from the total quoted amount to workout the net contract sum to be considered for acceptance.) [(-) Rs. 32,172.00]
M/S. ELECTROPOWER TECHNOLOGIES (BID ID -3501441)
Paragon Electrotechnics (BID ID -3503051)
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 0.24 MB
BOQ_829922.xls
BOQ • 0.39 MB
Tenderdocument8851.pdf
Tender Documents • 0.76 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .