| Sl No | Description | Qty | Unit | NATIONAL CONSTRUCTION CO H2 | UNIQUE ENTERPRISE H1 | M/S KARMAKAR AND COMPANY H3 |
|---|---|---|---|---|---|---|
| 1.00 | M&L for servicing / maintenance and calibration of 33 KV VCB outdoor type upto 1250 Amp complete, i.e. IR test, CRM test , Timing Test and Reduce Volatge Test . Disconnecting the main power from 33 KV isolator and control panel of any make type and taking out the breaker parts (any type),cleaning from inside and out side by using CRC-26 spray or any other cleaning agents, greasing the moveable parts.Complete servicing of switchgear including checking the fixed/moving contacts of all the 3 phases adjusting electrical/electronic/mechanical components all as per mfg instruction manual and standard practice. Calibration of relay any type e.g. Earth fault relay/Over current relay,etc of VCB installed at MRS. The fault level setting of these relays shall be in such a way that individual breaker will activate / trip to arrest the fault in local circuit and fault will not travel to main incoming breakers. The servicing & maintenance of 33 KV panel of switchgear shall be carried out through rep of OEM /professional and competent firm / technician / service engineer in this field in the presence of concerned Engr-in-charge and all as per directed.Note :- Contractor will submit testing & calibration report of VCB.The rate quoted by tender shall deemed to include the cost of this provision incl T&P required for VCB calibration and testing. Make-CG/Andrew Yule/Yamuna. Location: MRS. The calibration and servicing shall be carried out by only qualified and experienced person and prior approval shall be obtained from Engr-in-Charge | 6 | Each | 10,800 ₹64,800 | 11,500 ₹69,000 | 10,000 ₹60,000 Lowest |
| 2.00 | Supply and fix in replacement of motor drive mechanism wound for 11KV/33KV VCB/bus coupler of existing make, type,size, capacity, with driving gear and springs complete all as specified and directed by Engr-in-charge. | 3 | Each Set | 10,500 ₹31,500 | 11,800 ₹35,400 | 10,000 ₹30,000 Lowest |
| 3.00 | S&F in repair open/closed auxiliary contacts for contact multiplication (4NO + 4 NC) 16 Amps,30V DC suitable for upto 1250 Amps HT 11 KV & 33 KV VCB fixed all as specified and directed by Engr-in-charge. | 4 | Each | 10,300 ₹41,200 | 10,900 ₹43,600 | 10,000 ₹40,000 Lowest |
| 4.00 | S&F Shunt trip tripping/closing coil assembly 30 Volts, DC suitable for existing sample for 33KV upto 1250 Amps, HT VCB complete incl taking out old assembly of any type and make all as specified and directed by Engr-in-Charge. Make : Seimens or equivalent | 4 | Each | 8,200 ₹32,800 | 8,400 ₹33,600 | 8,000 ₹32,000 Lowest |
| 5.00 | S&F Shunt trip tripping/closing coil assembly 110 Volts, DC suitable for existing sample for 33KV upto 1250 Amps, HT VCB complete incl taking out old assembly of any type and make all as specified and directed by Engr-in-Charge. | 1 | Each | 8,200 ₹8,200 | 8,400 ₹8,400 | 8,000 ₹8,000 Lowest |
| 6.00 | S&F Shunt trip tripping/closing coil assembly 30 Volts, DC suitable for existing sample for 11KV upto 800 Amps, HT VCB complete incl taking out old assembly of any type and make all as specified and directed by Engr-in-Charge. | 8 | Each | 8,500 ₹68,000 | 8,600 ₹68,800 | 8,000 ₹64,000 Lowest |
| 7.00 | S & F in replacement HRC fuse (link type) having capacity 2 to 10 Amp complete all as specified and directed by Engr-in-charge. | 3 | Each | 530 ₹1,590 | 500 ₹1,500 Lowest | 500 ₹1,500 Lowest |
| 8.00 | S&F in replacement Master relay operating voltage 30V DC or as per sample complete all as directed. | 3 | Each | 20,600 ₹61,800 | 20,800 ₹62,400 | 20,000 ₹60,000 Lowest |
| 9.00 | S & F in repair Vaccum interrupter bottle for vaccum circuit breaker for upto 800 Amps in HT panel 11000 volts grade incl taking out old interruter all as specified and directed by Engr-in-charge.Make-Seimens or equivalent | 3 | Each | 31,200 ₹93,600 | 32,000 ₹96,000 | 30,000 ₹90,000 Lowest |
| 10.00 | S & F in repair Vaccum interrupter bottle for vaccum circuit breaker of 1250 Amps in 33000 volts grade Outdoor VCB incl taking out old interruter all as specified and directed by Engr-in-charge.Make-Seimens or equivalent | 3 | Each | 41,500 ₹1,24,500 | 42,600 ₹1,27,800 | 40,000 ₹1,20,000 Lowest |
Tender Value
₹33.8 L
EMD Value
₹67,700
Closing Date
23 Jun 2026, 6:00 pmClosed
GE PANAGARH
GARRISON ENGINEER PANAGARH, MILITARY ENGINEER SERVICES, PO-PANAGARH, DISTT- BURDWAN, STATE-WEST BENGAL PIN-713420
All as per BOQ
2026_MES_767819_1
8500-581/E8
Open Tender
Civil Works
Works
180 days
PANAGARH
As per tender documents
6 documents required · 6 mandatory
₹500
GE Panagarh
₹67,700
3 Jul 2026
26 May 2026
24 Jun 2026
26 May 2026
23 Jun 2026
9 Jun 2026
| Sl No | Description | Qty | Unit | Est. Rate | Est. Amount |
|---|---|---|---|---|---|
| 1 | M&L for servicing / maintenance and calibration of 33 KV VCB outdoor type upto 1250 Amp complete, i.e. IR test, CRM test , Timing Test and Reduce Volatge Test . Disconnecting the main power from 33 KV isolator and control panel of any make type and taking out the breaker parts (any type),cleaning from inside and out side by using CRC-26 spray or any other cleaning agents, greasing the moveable parts.Complete servicing of switchgear including checking the fixed/moving contacts of all the 3 phases adjusting electrical/electronic/mechanical components all as per mfg instruction manual and standard practice. Calibration of relay any type e.g. Earth fault relay/Over current relay,etc of VCB installed at MRS. The fault level setting of these relays shall be in such a way that individual breaker will activate / trip to arrest the fault in local circuit and fault will not travel to main incoming breakers. The servicing & maintenance of 33 KV panel of switchgear shall be carried out through rep of OEM /professional and competent firm / technician / service engineer in this field in the presence of concerned Engr-in-charge and all as per directed.Note :- Contractor will submit testing & calibration report of VCB.The rate quoted by tender shall deemed to include the cost of this provision incl T&P required for VCB calibration and testing. Make-CG/Andrew Yule/Yamuna. Location: MRS. The calibration and servicing shall be carried out by only qualified and experienced person and prior approval shall be obtained from Engr-in-Charge | 6 | Each | - | - |
| 2 | Supply and fix in replacement of motor drive mechanism wound for 11KV/33KV VCB/bus coupler of existing make, type,size, capacity, with driving gear and springs complete all as specified and directed by Engr-in-charge. | 3 | Each Set | - | - |
| 3 | S&F in repair open/closed auxiliary contacts for contact multiplication (4NO + 4 NC) 16 Amps,30V DC suitable for upto 1250 Amps HT 11 KV & 33 KV VCB fixed all as specified and directed by Engr-in-charge. | 4 | Each | - | - |
| 4 | S&F Shunt trip tripping/closing coil assembly 30 Volts, DC suitable for existing sample for 33KV upto 1250 Amps, HT VCB complete incl taking out old assembly of any type and make all as specified and directed by Engr-in-Charge. Make : Seimens or equivalent | 4 | Each | - | - |
| 5 | S&F Shunt trip tripping/closing coil assembly 110 Volts, DC suitable for existing sample for 33KV upto 1250 Amps, HT VCB complete incl taking out old assembly of any type and make all as specified and directed by Engr-in-Charge. | 1 | Each | - | - |
| 6 | S&F Shunt trip tripping/closing coil assembly 30 Volts, DC suitable for existing sample for 11KV upto 800 Amps, HT VCB complete incl taking out old assembly of any type and make all as specified and directed by Engr-in-Charge. | 8 | Each | - | - |
| 7 | S & F in replacement HRC fuse (link type) having capacity 2 to 10 Amp complete all as specified and directed by Engr-in-charge. | 3 | Each | - | - |
| 8 | S&F in replacement Master relay operating voltage 30V DC or as per sample complete all as directed. | 3 | Each | - | - |
| 9 | S & F in repair Vaccum interrupter bottle for vaccum circuit breaker for upto 800 Amps in HT panel 11000 volts grade incl taking out old interruter all as specified and directed by Engr-in-charge.Make-Seimens or equivalent | 3 | Each | - | - |
| 10 | S & F in repair Vaccum interrupter bottle for vaccum circuit breaker of 1250 Amps in 33000 volts grade Outdoor VCB incl taking out old interruter all as specified and directed by Engr-in-charge.Make-Seimens or equivalent | 3 | Each | - | - |
stage.html
html • 0.03 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 0.42 MB
BOQ_859857.xls
BOQ • 0.54 MB
PS581.pdf
Tender Documents • 1.40 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .