SE, EUDC-I, NOIDA
33/11 KV SUBSTATION, SECTOR-18 FIRST FLOOR, OPPOSITE SAB MALL, NOIDA
WORK OF REPLACEMENT OF DAMAGED 33 11 KV VCB
2022_PVVNL_716437_1
53/EUDC-I/2022-23
Open Tender
Electrical Works
Item Rate
UNDER EUDD-VII NOIDA
Please refer Tender documents.
2 documents required · 2 mandatory
₹1,180
EE, EUDD-VII, NOIDA
₹3,130
1 Aug 2022
21 Jul 2022
1 Aug 2022
21 Jul 2022
1 Aug 2022
21 Jul 2022
Amount
FOLLOWING WORK EPLACEMENT OF DAMAGE & NON REPAIRABLE 33/11 KV VCB SITUATED AT 33/11 KV S/S SECTOR-62 GREEN BELT, NOIDA IN THE AREA OF EUDSD-II, NOIDA:-
CARRIAGE OF NEW 11 KV V.C.B. INCOMING C.T.R. 600/300/5A (01 NO.) AND 11 KV V.C.B. OUTGOING C.T.R. 400/200/5A (05 NOS.) FROM GHAZIABAD/ SHAHIBABAD/NOIDA/JE STORE TO SITE OF WORK WITH SAFE LOADING AND UNLOADING AT BOTH ENDS.
LABOUR CHARGES FOR REPLACEMENT OF 11 KV V.C.B. INCOMING C.T.R. 600/300/5A (01 NO.) AND 11 KV V.C.B. OUTGOING C.T.R. 400/200/5A (05 NOS.) WITH ALL ACCESSORIES AND ERRECTION OF ABOVE NEW 11 KV V.C.B. INCOMING C.T.R. 600/300/5A (01 NO.) AND 11 KV V.C.B. OUTGOING C.T.R. 400/200/5A (05 NOS.) WITH REMOVING AND RECONNECTING 11 KV INCOMING AND OUTGOING CABLES, REMOVING AND REFIXING OF EARTHING AND WIRING AS REQUIRED IN VCB, ALL TESTING OF NEW VCB ETC WITH PROPER SAFETY TO COMPLETE THE WORK ETC IN ALL RESPECT.
CARRIAGE OF DAMAGED & NON REPAIRABLE 11 KV V.C.B. INCOMING C.T.R. 600/300/5A (01 NO.) AND 11 KV V.C.B. OUTGOING C.T.R. 400/200/5A (05 NOS.) WITH ALL ACCESSORIES FROM SUB-STATION TO ELECTRICITY STORE WITH SAFE LOADING AND UNLOADING AT BOTH ENDS.
PROVIDING AND INSTALLATION OF CHEMICAL EARTHING FOR NEW VCB BRAKER (WITH ALL MATERIAL AND LABOUR) AFTER INSTALLATION RESISTANCE SHOULD BE LESS THAN ONE OHM. AS PER FOLLOWING :- Note :- The all material and labour shall be provided by the contractor with 12 month guarantee for resistance value less than one OHM and should be checked 06 months after proper installation.
Providing of earth elctrode for chemical earthing Pipe in pipe type proper hot deep galvanization dia 80 mm length 3 mtr - 50mm x 6mm terminal connection hole dia 8mm The cavity between the pipe & pipe is filled with conductive mixture - for hermetically filling inside the cavity i.e. between secondary conductor & primary conductor, crystalline compound is to be injected in the electrode assembly. It is a combination of high conductivity metal alloys, copper & aluminum power, conductive carbon / cement and bonding material etc the electrode should be sealed from both the ends. The outer pipe of the elctrode should be galavanized the characteristics of this compound is highly cnductive, non magnetic & non corrosive in G.I. Including providing of backfill compound each elctrode should be supplied with bags of 25 kg x 2 bfc compound (ground resistance enhancement powder 50 kgs each CPRI tested for new 11 KV VCB Braker.
Providing and fixing of GI strip of size 50 mm x 6 mm suitable for new 11 KV VCB Braker.
Providing and fixing of PVC Pit covers for above earthing electrode terminals.
R. P. T. Electrical
Kunal Electricals
Sanneer Electricals Private Limited
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .