Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹44.1 LAccepted-AOC 357 A NEW CHOUKSEY NAGAR LAMBAKEDA BHOPAL M P | BHOPAL | MADHYA PRADESH | L1 | Accepted-AOC tender accepted | |
| 2 | L2₹47.2 L+₹3.0 L (6.87%)Rejected-Finance | L2 | Rejected-Finance not lowest | |
| 3 | L3₹47.9 L+₹3.8 L (8.59%)Rejected-Finance | L3 | Rejected-Finance not lowest | |
| 4 | L4₹49.2 L+₹5.0 L (11.4%)Rejected-Finance | L4 | Rejected-Finance not lowest |
Tender Value
₹49.2 L
EMD Value
₹50,000
Closing Date
8 Jul 2020, 5:00 pmClosed
Project Engineer MPPHIDCL Bhopal Division-02
Project Engineer MPPHIDCL Bhopal Division-02 MPPHIDCL BHADBHADA RAOD BHOPAL
CONSTRUCTION OF 33/0.4 KV, 1X500 KVA SUB STATION WORK (IN EXISTING GRID) FOR NEW DIAL 100 BUILDING, RADIO HEAD QUARTER BHOPAL, M.P.
2020_MPPHC_94879_1
03/2020-21
Open Tender
Electrical Works
Item Rate
45 days
Bhopal
AS PER NIT
5 documents required · 5 mandatory
₹5,000
Project Engineer MPPHIDCL Bhopal Division-02
₹50,000
6 Oct 2020
23 Jun 2020
10 Jul 2020
23 Jun 2020
8 Jul 2020
23 Jun 2020
Amount
Supply of support for overhead line RS joist /'H' Beam of I.S. standard including drilling of required hole etc. complete H - Beam 152 x 152mm, Std weight 37.1 Kg / Mtr
Erection of RS Joist pole / 'H' Beam / steel tubular / steel rail pole strut in cement concrete 1:3:6 (1cement:3coarse sand: 6 aggregate 40mm nominal size) foundation including excavation and refilling and secured with holding clamps, nuts and bolts, etc. as required.
Supplying and erection of stay set complete with 19/20mm.dia 1.8 metre long stay rod, turn buckle, ancher plate of size 300mm x 300mm x 7.5mm, thimble, stay clamps, bow tightener, 7/4.00 dia G.I. stay wire etc. in cement concrete M-10 (1 Cement : 3 Coarse and : 6 granded stone aggregate 40mm nominal size) foundation including excavation and back refilling etc. as required.
PAINTING OF POLES :-Primer coat over new steel and other metallic surface with red oxide/ zinc chromide paint complete with supply of material labour etc. including preparation of surface.
PAINTING OF POLES:-Final coat with aluminium paint, brushing complete including material and labour.
Supply, fabrication and erection of Angle/Chanel/Flat iron fitting for over head line & sub-station etc such as 'D'bracket, cross arms, top clamp, 'V' cross arms,Back/Support clamps or other similar work etc. including nut bolts of required size, making holes, fabrication,welding, cutting, etc. and painting with one coat of red oxide paint & two coat of aluminium paint as required as per specification.
Supplying and erection of 33kV (10 KN) Polymer pin insulator complete with long steel head G.I. pin, nut, washer etc. as required
Supplying and erection of 33kV (45 KN) Polymer disc insulators for 33KV overhead lines with galvanized insulator fittings, ball and socket type, and complete with galvanized strain clamp, bolts, nuts, washers etc. as required.
Supplying installing, testing & commissioning of outdoor H.T., AB switch assembly set gang operated with brass contact parts, including required GI pipe operating rod, handle & locking arrangement on On-Off position conforming to IS complete with required material and installing on existing DP structure to complete the job as required as per specification.(Set of 3 nos.) 33kV, 600A.
Supplying installation testing and commissioning of 400/600 Amp. triple pole outdoor type two stack and three Insulator padestals per phase, manual operated rotating type Isolator complete with fixed and moving contact of hard drawn electrolytic copper flat, 8 mm dia GI od for fixed and moving arching horn, 32 mm dia GI pipe for operating handle, 19mm dia GI pipe for phase coupler,brass bush and trust bearing, isolator base channel, post insulator, padlock with key, earth/without earth switch and other required accessories etc. complete as required. 33 KV Isolator 400/600 Amp with earth switch (set of 3Nos. for 3 phases)
Supplying installing, testing & commissioning D.O. fuse assembly with brass part contact for 33 or 11/0.4 KV DP Structure set of 3 Nos. with fuse barrel i/c required fuse element & other materials as per specification on existing D.P. structure as required.101 33kV (S.O.R 42.57.2 page No-101)
Supplying and erection of single piece non-linear resistor polymer type lightning arrestor (Set of 3 Nos.) for 3 wire, 33kV overhead lines/ sub-station with rated voltage of 27kV (rms) with a nominal discharge current rating of 10 KA and complete with galvanized clamping arrangement, G.I. bolts, nuts, washer etc. as required.
Supply & fixing anti climbing device with 2 ply G.I. barbed wire 1 Kg. per pole complete as per specification.
Supply, laying and fixing of G.I. earth coil of 4mm dia G.I. wire having 120 turns of nearly 50mm dia. and 3 mt. long tail in existing pit duly earthed with pole etc complete as required as per specification.
Supplying and fixing 33/11/0.4 KV enamel coated danger board size 200x250mm with clamp on existing HT/LT structure / poles.
Supplying and drawing of stranded Aluminium Steel Reinforced (ACSR) confirming to IS:398-1976 of approved make, stringing, making off complete with binding at existing insulator, jointing, jumpering, tearing off, connecting etc. as required and clearing of obstacles (if any) etc. ACSR 0.1 sq inch (100 Sq.mm Al. EQ. ) - (Dog)
Supplying and drawing guard wire/earth wire/bearer wire 18.62 mm2 (4.87mm. Dia / 6swg) G.I. including stringing, binding at existing insulators or brackets, jointing, jumpering, connecting & cradle etc. as required and clearing of obstacles (if any)
Providing and erecting hot dipped galvanized octagonal poles in single section made from 3mm thick sheet having lockable weather proof flush door junction box complete erected in an approved manner on provided foundation. Suitable size & type of foundation bolts 4 nos. 'J' type (EN8 grade) 7 mtrs. Height, 130 X 70mm A/F, 220x220x12mm base plate, 4 nos. X 20 x 700mm bolt .
Providing and erecting hot dipped galvanized octagonal poles in single section made from 3mm thick sheet having lockable weather proof flush door junction box complete erected in an approved manner on provided foundation. Suitable size & type of foundation bolts 4 nos. 'J' type (EN8 grade) 9 mtrs. Height, 155 X 70mm A/F, 260x260x16mm base plate, 4 nos. X 24 x 750mm bolt .
Designing & casting with M-20 reinforcement cement concrete foundation suitable for Octagonal poles considering the safe soil bearing capacity at site as 10 T/sqm at 2 mtrs. Depth including excavation, foundation nut bolts in an approved manner.
TRANSFORMERS : ( Copper wound )Supplying installing, connecting, testing and commissioning of 3 Phase, 50 Hz, 11/0.433 KV or 33/0.433 KV, Delta/Star connected, Aluminium/Copper wound, oil filled, Indoor/outdoor type, Distribution/Station transformer of accepted standard specification with accessories such as drain & filter valve, earthing terminals, lifting arrangements of suitable size, with cable box dehydrating breather with silica gel of suitable size, Conservator tank, air release devise, Rating & diagram plate including CI rollers, Radiators with shut off valve, Cable end boxes on HT & LT side bushings, Explosion vent with diaphragm, Off load tap changing switch, Buchholz relay, thermometer pocket with 6” dial type thermometer & OTI, wherever required complete with first filling of oil with installation on existing DP structure or foundation etc. complete as per specification BIS AND BEE.. The no load and full load losses should not be more than as mentioned below.500 KVA 33/.433 KV (Copper wound with tap changing arrangement) NLL 0.8 KW & FLL 6.5 KW.contracor has to arrange time to time factory visits for client including all types of type and routine tests at different stages.
Earthing with Copper Earth plate 600mm X 600mm X 3mm thick including accessories and providing masonary encloser in cement mortor, cover plate having locking arrangement on the top and G.I. watering pipe 20mm dia 2.7 Metre long etc. (but without charcoal or coke and salt) complete as required.
Add Extra for using salt and charcoal / coke for G.I. Plate or Copper plate earth electrode as required including excavation in hard rock and refilling the pit with black soil.
Providing & fixing 25mm X 5mm copper strip in 40mm dia G.I.pipe (B class) from earth electrode as required.
Providing & fixing 25mm X 5mm G.I.strip in 40mm dia G.I. Pipe (B class) from earth electrode as required.
Supplying and laying 50mm X 6mm G.I. strip at 0.5 metre below ground level / surface as strip earth electrode including jointing etc. as required.37.15
Chemical Earthing:- supplying and ereting earth pit ofminimum bore dia.150mm size, approved make safe earthing electrode consisting Pip-in pipe technology as per IS3043-1987 made of corrosion free G.I. pipe with constant ohmic value surrounded by highly conductive compound with high charge dissipationsuitable for effective and maintenance free earthing as metioned below.37.40.2 with 3 mtr.pipe of 80mm outer dia. 40 mm inner dia and 14mm terminal dia. In soft rock/marshy soil with 50 kgs.(two bag) Back filling compound
Supplying and fixing following accessories of approved make with all required materials and labour as required suitable upto Dog conductor PG clamp
Supplying and fixing following accessories of approved make with all required materials and labour as required suitable upto Dog conductor Tee clamp
Supplying and fixing following accessories of approved make with all required materials and labour as required suitable upto Dog conductor Bimetallic clamp
CHEQURE PLATE : Supplying, fabricating and installation of 6 mm thick MS chequered plate of required size with hook and finishing the same as required.
PVC HEAT SHRINKABLE SLEEVES : Providing PVC heat shrinkage sleeve colour coated as required as per specification. 33 KV
SUB STATION EQUIPMENTS :Supplying of T&P required for 33/11 KV sub-station like 30 feet long double sliding aluminium ladder, DC and tubular spanner set, hand gloves, discharge rod, three ton capacity tirfur, insulated screw driver set, two ton capacity chain pully block, insulated cutting plier set, hammer (1 kg.), phawara, pickaxe, crobars, rechargeable torch, magger, electrical tool kit, earth tester, first aid box etc. complete as required by MPSEB.
SHOCK TREATMENT CHART : Supplying and fixing in position best quality electric shock treatment chart written in Hindi and English duly framed in wooden frame and covered with glass as required and duly fixed in control room as directed.
FIBRE GLASS ROD : Supplying of 20 feet long, telestone type fibre glass earth discharge rod suitable for 11/33 KV power supply earth discharge rod suitable for 11/33 KV power supply complete with earthing chain, rubber grip etc. as required and as per ISS.
CHAIN LINK FENCING :Providing and fixing of chain link fencing surrounding the existing 33/11KV Sub-Station on angle post of size 50x50x6mm, 3.50mtr. long and top end of post shall be 50x50x6mm, 3.50mtr. long and top end of post shall be 50x50x6mm, 3.50mtr. long and top end of post shall be bended 45 degree outside for barbed wire laying in 5 layers and to fabricate it in frame shape for fixing of chain link 2.5mtr. height of size 10 SWG GI wire and spacing of 75x75mm on frame duly welded with MS flat 20x3mm on all sides of frame or fixed with nut & bolt, including providing of gates of switchyard shall be made of 2" dia B class MS pipe and GI fensing shall be used to enclose the pipe frame work with angle iron of iron bracing and duly pipe frame work with angle iron of iron bracing and duly pipe frame work with angle iron of iron bracing and duly painted all the items by two coats of red oxide and two coats of synthetic enamel paint including digging of pit in all type of soil / rock as required. The depth of burying of angle post shall be 0.5 mtr. and filling with 1:3:6 cement concrete of 30 cm. dia. around the post as required. Measurements shall be done in RM of chain link used at site.
CURRENT TRANSFORMER : ( C.T.) :Supplying, installation, testing and commissioning of single phase oil filled outdoor type dual ratio current transformer, wound or bar primary and of the rated burden within the error limits complete as per IS specifications. For measuring CT's the burden is 15 VA and of 1.0 class and for protection CT's the burden is 15 VA and 5 P 10 class. The CT's should be as per IS:2705-1981 33 KV CT, 300 -150/5 Amp or 200-100/5 Amp. or100-50/5 Amp
POTENTIAL TRANSFORMER : ( P.T.) Supplying, installation, testing and commissioning of oil filled out door type single phase, 50 Hz, 33 KV/110 V, or 11 KV/110V, 100VA burden, class 1.0 voltage transformer complete as per IS 3156 33 KV/110V PT
DC PANEL : Supplying, installation, testing and commissioning of DC Panel of suitable size of 14 SWG CRCA sheet duly painted with two coats of red oxide and two coats of synthetic enamel paint consisting 1 no. DP MCB 32 amp. and 12 nos. SP MCB 10 amp. suitable for DC supply withneutral link as required as per specification.
AC PANEL : Supplying, installation, testing and commissioning of AC Panel of suitable size of 14 SWG CRCA sheet duly painted with two coats of red oxide and two coats of synthetic enamel paint consisting 1 no. SPN MCB 32 amp. and 12 nos. SP MCB 10 amp. suitable for AC supply with neutral link as required as per specification.
BATTERY AND BATTERY CHARGER : Supplying, installation, testing and commissioning of 100AH capacity 30 volt (15 No cells each of 2.0 Volt) NICAD battery bank and other necessary materials etc. complete as required.
BATTERY AND BATTERY CHARGER : Supplying, installation, testing and commissioning of 30 volt 20A battery charger suitable of above battery bank with initial charging capacity capability in a duly painted MS enclosure complete with provision for keeping the 30 volt battery in the same enclosure complete as required as per specifications.
RUBBER MAT :Supplying and laying in position of ISI marked rubber mat rated for 1100 volts grade and 12.5 mm thick. Size 1000mm x 2000mm.
CIVIL WORK : Earth work in excavation by mechanical means (Hydraulic Excavator) / manual means in all kind of soil, moorum,hardrocks, copra etc and for all types and sizes of foundations, drains, and trenches for pipes and cables with a free lead upto 50m and 1.5m lift, including disposed excavated stuff to be leveled and neatly dressed. Eexcavation by mechanical means (Hydraulic Excavator) / manual means for all types and sizes of foundations, drains, and trenches for pipes and cables with a free lead upto 50m and 1.5m lift, including stacking of disposed excavated stuff. In:Hard rock (Blasting prohibited)
Supplying, stacking and spreading of nominal size metal 40 mm(red/white)
Providing and laying in foundation/plinth, mechanically mixed 1:2:4 (1 cement, 2 sand, 4 metal) cement concrete with 20 mm BT nominal size graded stone aggregates including ramming in layers, curing complete including cost of form work and cost of cement.
Supply and fabrication of Iron work for reinforcement mild steel / tar steel, tested fixed in position complete i/c cutting, bending, all handling and binding with binding wire placing in position etc. complete
COPPER CONTROL CABLES : Supplying, laying connecting and testing of PVC / XLPE heavy duty control cable confirming to relevant IS specifications 1100 volts grade armoured of approved make with copper conductor in existing trench with clamp as required. The rate include for making cable end termination with suitable size brass cable gland and 2 core x 2.5 sqmm. copper cable.
COPPER CONTROL CABLES : Supplying, laying connecting and testing of PVC / XLPE heavy duty control cable confirming to relevant IS specifications 1100 volts grade armoured of approved make with copper conductor in existing trench with clamp as required. The rate include for making cable end termination with suitable size brass cable gland and 4 core x 2.5 sqmm. copper cable.
COPPER CONTROL CABLES : Supplying, laying connecting and testing of PVC / XLPE heavy duty control cable confirming to relevant IS specifications 1100 volts grade armoured of approved make with copper conductor in existing trench with clamp as required. The rate include for making cable end termination with suitable size brass cable gland and 8 core x 2.5 sqmm. copper cable.
COPPER CONTROL CABLES : Supplying, laying connecting and testing of PVC / XLPE heavy duty control cable confirming to relevant IS specifications 1100 volts grade armoured of approved make with copper conductor in existing trench with clamp as required. The rate include for making cable end termination with suitable size brass cable gland and 12 core x 2.5 sqmm. copper cable.
CABLE ROUTE MARKERS SLABS : Supplying and instllation of precast RCC cable route marker slabs (of size 300 mm width, 600 mm height and 100 mm thickness) in cement concrete 1:2:4 (1 cement; 2 course sand; 4 graded stone aggre gate 20 mm nominal size), suitable steel reinforcement, mec mechanically mixing, smooth finishing with cement on outer surface, engraved letter of "L.T. CABLE" and arrow marker (<---->) on both sides, painting of cable route marker slab with yellow colour, letter in black colour and arrow with red colour or as directed by engineer incharge.
CABLE TRENCHES : Preparation of permanent cable trench of required size including excavation in all type of soil/rock providing base concrete of 1:4:8 ratio of 20 cm thick size providing 50 mm dia PVC sleeve pipe in base concreting at 10 meter intervals intervals for clearing of water, 20 cm thick brick masonary wall on both side of trench of required height, plastering etc. complete with providing and fixing angle iron of 50x50x5mm size duly painted with two coats of red oxide, duly embedded in brick masonry at a distance of every 1 meter lengthwise in trench, above 20cm. from finished base of trench including providing and fixing of required size of flat clamps and removing of waste soil up to a lead of 50 meters. 450x750mmclear inside)
FLAG STONE :Supplying and fixing of flag stone of following size as required 900 X 450 X 50 mm
FLAG STONE :Supplying and fixing of flag stone of following size as required 900 X 600 X 50 mm
FLAG STONE :Supplying and fixing of flag stone of following size as required 600 X 600 X 50 mm
(STREET LIGHTING FOR LANDSCAPE) Supplying, Installation, Fixing & testing of street light luminairies of erating at 140-270 V ac Supply with p.f.more than 0.9 & the total system wattage of 45 W. The luminaire should have pressuure die cast aluminium housing with thermal management &rubber gasket to ensure IP-65 class of protection with required LED lamps etc. Equivalent to Philips make model BRP 320 1X24 LED Make – Philips/Thorm/Schredder/GE
Supplying & fixing of I/1.5meter long dully bended as desired GI bracket including painting suitable for above poles street light fixtures. (1)Single bracket
Supplying & fixing of I/1.5meter long dully bended as desired GI bracket including painting suitable for above poles street light fixtures. (2)Double bracket
Supply and fixing of following B class Ms.s pipe for exhaust with thermal insulation and aluminium clading in overall length of pipe ,as flexible pipe ,rain cowl etc including clamping of pipe ,bends ,reducer as required ,suitable opening valve if required etc complete as required .150mm dia
Supply of XLPE Insulated power cable (confirming IS-7098 Part-1) 1100 Volt grade, 1 core/ 2 core/ 3 1/2 core/ 4 core ISI Marked with Alu. Stranded/ Solid conductore 4 CORE ARMOURED 25 Sq.mm.
Laying of one number armoured/ unarmoured power cable 1.1 kv grade of size not exceeding 25 Sq.mm. in the existing RCC Hume/ Stone ware/ G.I. pipe/ surface in existing trench as required
Supplying and installing Double wall corrugated pipes (DWC) of HDPE (IS 14930 Part II- marked) for cable laid underground with necessary material and at required depth upto 90 cm below road/ ground surface, including excavation, back filling with excavated material, ramming and making the surface good. 50.00 mm outside dia.
JAGDAMBA FOUNDATION
M/s. Abdul Sattar Farooqui
B L JAIN
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .