Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹8.9 LAccepted-AOC NEAR SVN UNIVERSITY NARSINGHPUR ROAD SIRONJA SAUGOR MP 470228 | SAUGOR | SAGAR | MP | 470228 | L1 | Accepted-AOC Being lowest and reasonable bidder | |
| 2 | L2₹10.9 L+₹1.6 L (17.2%)Rejected-Finance 58 CHANDRALOK BLDG MAYO HOSPITAL ROAD NAGPUR 440018 | NAGPUR | NAGPUR | MAHARASHTRA | 440018 | L2 | Rejected-Finance Other than lowest bidder | |
| 3 | L3₹11.7 L+₹2.4 L (25.7%)Rejected-Finance 1 A BASEMENT 30 31 RAJA HOUSE NEHRU PALACE NEW DELHI 110 019 | SOUTH EAST | DELHI | 110019 | L3 | Rejected-Finance Other than lowest bidder |
| Sl No | Description | Qty | Unit | Paragon Electrotechnics L2 | MONA GENERATOR SEVICES PVT. LTD. L3 | M/S JAINENDRA KUMAR JAIN L1 |
|---|---|---|---|---|---|---|
| 1.00 | S & F for Double Wall Corrugated High Density Polymer Ethyl (HDPE) pipe of size 50mm outer diameter and 38 mm inner Diameter for laying of Electric cable with IS 14930 (part 2) 2001 and 6 mm thickness laid in trenches, wall, floor, pole including bends, sockets and other connected accessories complete all as specified and directed by Engineer- in -Charge. | 300 | RM | 55 ₹16,500 | 75 ₹22,500 | 50 ₹15,000 Lowest |
| 2.00 | S & F for Double wall Corrugated High Density Polymer Ethyl (HDPE) pipe of size 63mm outer diameter and 50 mm inner Diameter for laying of Electric cable with IS 14930 (part 2) 2001 and 6 mm thickness laid in trenches, wall, floor, pole including bends, sockets and other connected accessories complete all as specified and directed by Engineer- in -Charge. | 100 | RM | 65 ₹6,500 Lowest | 108 ₹10,800 | 75 ₹7,500 |
| 3.00 | S & F for Double wall Corrugated High Density Polymer Ethyl (HDPE) pipe of size 90mm outer diameter and 75 mm inner Diameter for laying of Electric cable with IS 14930 (part 2) 2001 and 6 mm thickness laid in trenches, wall, floor, pole including bends, sockets and other connected accessories complete all as specified and directed by Engineer- in -Charge. | 200 | RM | 110 ₹22,000 | 153 ₹30,600 | 90 ₹18,000 Lowest |
| 4.00 | M & L for boring of holes under road, pavement, hard standing by trenches technology using Ultra sounding technique and necessary machine including HDPE pipe of 150 mm dia suitable for 0.4 mpa working pressure complete all as specified and directed. | 15 | RM | 2,500 ₹37,500 | 945 ₹14,175 | 650 ₹9,750 Lowest |
| 5.00Supplying, laying, testing and Commissioning cable XLPE insulated aluminium conductor, stranded, armoured, PVC sheathed, LT 1100 Volt grade, heavy duty as per IS-7098 and providing suitable lugs and cable glands, laid in trenches/ ducts/fixed to wall/ roof/ poles including taking down existing cables complete all as specified and directed for following sizes: - | ||||||
| 5.01 | 35 sqmm, 3.5 core | 100 | RM | 320 ₹32,000 Lowest | 339 ₹33,900 | 438 ₹43,800 |
| 5.02 | 50 sqmm, 3.5 core | 100 | RM | 430 ₹43,000 Lowest | 456 ₹45,600 | 685 ₹68,500 |
| 5.03 | 25 sqmm, 3.5 core | 100 | RM | 260 ₹26,000 | 279 ₹27,900 | 230 ₹23,000 Lowest |
| 5.04 | 16 sqmm, 4 core | 300 | RM | 215 ₹64,500 | 229 ₹68,700 | 145 ₹43,500 Lowest |
| 6.00 | Taking down old unserviceable LT panel and Supply, Installing, Testing and Commissioning of outdoor type LT feeder pillar box of suitable size, pedestal mounted, CPRI approved factory made totally enclosed, dust and vermin proof, shutter in front and in rear side made of 3.15 mm thick CRCA sheet, duly fabricated and having proper locking arrangement in both front and rear door with 4 side slanting roof duly projected and painted to both internal and external surfaces with powder coating paint in heat process of sheet and suitable for 500 volts, 50 Hz, 3 phase 4 wire system, fully compartmentalized design with 4 Nos aluminium bus bars suitable for 150 Amps mounting on insulator, pre wired with suitable size of copper wire short circuit rating 50 KA (Arms) for one second including suitable aluminium earth strip (Not less than 20x3mm) for internal connection to the switches/MCCBs all as specified and comprising with and including following accessories and mounted on PCC Platform made out of PCC 1:3:6, 100 mm thick, 1 Mtr all around the panel board complete with the following items housed in: - | 1 | EACH | 1,05,000 ₹1,05,000 | 1,15,591 ₹1,15,591 | 75,850 ₹75,850 Lowest |
Tender Value
₹10 L
EMD Value
₹20,000
Closing Date
12 Feb 2026, 6:00 pmClosed
AGE (I) AF Sonegaon, Nagpur
Bldg P-51, 44 Wing AF Station Sonegaon, Nagpur 440005
REPAIR /REPLACEMENT OF LT PANEL AND ITS CONNECTED ACCESSORIES AT ZONE A AND ZONE B AT AF STN SONEGAON NAGPUR
2026_MES_749657_1
8560/E8
Open Tender
Electrical and Maintenance Works
Item Rate
180 days
Sonegaon
As per NIT
8 documents required · 8 mandatory
₹500
Yes
AGE (I) AF Sonegaon
₹20,000
Yes
10 Mar 2026
22 Jan 2026
19 Feb 2026
22 Jan 2026
12 Feb 2026
5 Feb 2026
22 Jan 2026 - 4 Feb 2026
S & F for Double Wall Corrugated High Density Polymer Ethyl (HDPE) pipe of size 50mm outer diameter and 38 mm inner Diameter for laying of Electric cable with IS 14930 (part 2) 2001 and 6 mm thickness laid in trenches, wall, floor, pole including bends, sockets and other connected accessories complete all as specified and directed by Engineer- in -Charge.
S & F for Double wall Corrugated High Density Polymer Ethyl (HDPE) pipe of size 63mm outer diameter and 50 mm inner Diameter for laying of Electric cable with IS 14930 (part 2) 2001 and 6 mm thickness laid in trenches, wall, floor, pole including bends, sockets and other connected accessories complete all as specified and directed by Engineer- in -Charge.
S & F for Double wall Corrugated High Density Polymer Ethyl (HDPE) pipe of size 90mm outer diameter and 75 mm inner Diameter for laying of Electric cable with IS 14930 (part 2) 2001 and 6 mm thickness laid in trenches, wall, floor, pole including bends, sockets and other connected accessories complete all as specified and directed by Engineer- in -Charge.
M & L for boring of holes under road, pavement, hard standing by trenches technology using Ultra sounding technique and necessary machine including HDPE pipe of 150 mm dia suitable for 0.4 mpa working pressure complete all as specified and directed.
Supplying, laying, testing and Commissioning cable XLPE insulated aluminium conductor, stranded, armoured, PVC sheathed, LT 1100 Volt grade, heavy duty as per IS-7098 and providing suitable lugs and cable glands, laid in trenches/ ducts/fixed to wall/ roof/ poles including taking down existing cables complete all as specified and directed for following sizes: -
35 sqmm, 3.5 core
50 sqmm, 3.5 core
25 sqmm, 3.5 core
16 sqmm, 4 core
Taking down old unserviceable LT panel and Supply, Installing, Testing and Commissioning of outdoor type LT feeder pillar box of suitable size, pedestal mounted, CPRI approved factory made totally enclosed, dust and vermin proof, shutter in front and in rear side made of 3.15 mm thick CRCA sheet, duly fabricated and having proper locking arrangement in both front and rear door with 4 side slanting roof duly projected and painted to both internal and external surfaces with powder coating paint in heat process of sheet and suitable for 500 volts, 50 Hz, 3 phase 4 wire system, fully compartmentalized design with 4 Nos aluminium bus bars suitable for 150 Amps mounting on insulator, pre wired with suitable size of copper wire short circuit rating 50 KA (Arms) for one second including suitable aluminium earth strip (Not less than 20x3mm) for internal connection to the switches/MCCBs all as specified and comprising with and including following accessories and mounted on PCC Platform made out of PCC 1:3:6, 100 mm thick, 1 Mtr all around the panel board complete with the following items housed in: -
INCOMING :-
MCCB Four Pole 100 amps, 25 KA breaking capacity, microprocessor release adjustable, 440 volt AC module, 01 No (in coming).
Indicator Lamps (LED type) & Bakelite fuse showing R, Y, B Phase - 01 Set
Digital frequency meter 40-60 Hz - 01 No.
BUSBAR: - 150 Amps rated aluminium bus bar TPN duly insulated with coloured PVC sleeve as per standard colour code and rigidly mounted on Bakelite/DMC insulator bus bar support (Square/ round) insulators of suitable size and good insulation resistance.
OUT GOING
MCCB Four Pole 63 Amps, 16 KA breaking capacity, fixed type thermal magnetic, 440 volt AC module, 03 Nos. (Outgoing) (01 No Spare).
MCB TPN 40 Amps, 10 KA breaking capacity, 440 volt AC module, with earth fault relay = 02 Nos (Outgoing).
Taking down old unserviceable LT panel and Supply, Installing, Testing and Commissioning of outdoor type LT feeder pillar box of suitable size, pedestal mounted, CPRI approved factory made totally enclosed, dust and vermin proof, shutter in front and in rear side made of 3.15 mm thick CRCA sheet, duly fabricated and having proper locking arrangement in both front and rear door with 4 side slanting roof duly projected and painted to both internal and external surfaces with powder coating paint in heat process of sheet and suitable for 500 volts, 50 Hz, 3 phase 4 wire system, fully compartmentalized design with 4 Nos aluminium bus bar suitable for 150 amps mounting on insulator, pre wired with suitable size of copper wire short circuit rating 50 KA (Arms) for one second including suitable aluminium earth strip (not less than 20x3mm)for internal connection to the switches/MCCBs all as specified and comprising with and including following accessories and mounted on PCC Platform made out of PCC 1:3:6, 100 mm thick, 1 Mtr all around the panel board complete with the following items housed in: -
INCOMING :-
MCCB Four Pole 125 Amps, 36 KA breaking capacity, microprocessor release adjustable, 440 volt AC module, 01 No (in coming).
Indicator Lamps (LED type) & Bakelite fuse showing R, Y, B Phase - 01 Set
Digital frequency meter 40-60 Hz - 01 No.
BUSBAR: - 200 Amps rated aluminium bus bar TPN duly insulated with coloured PVC sleeve as per standard colour code and rigidly mounted on Bakelite/DMC insulator bus bar support (Square/ round) insulators of suitable size and good insulation resistance.
OUT GOING
MCCB Four Pole 63 Amps, 16 KA breaking capacity, fixed type thermal magnetic, 440 volt AC module, 03 Nos. (Outgoing) (01 No Spare).
MCB TPN 40 Amps, 10 KA breaking capacity, 440 volt AC module, with earth fault relay = 02 Nos (Outgoing).
MCCB Four Pole 100 Amps, 25 KA breaking capacity, fixed type, 440 volt AC, 01 No. (Outgoing).
Taking down old unserviceable LT panel and Supply, Installing, Testing and Commissioning of outdoor type LT feeder pillar box of suitable size, pedestal mounted, CPRI approved factory made totally enclosed, dust and vermin proof, shutter in front and in rear side made of 3.15 mm thick CRCA sheet, duly fabricated and having proper locking arrangement in both front and rear door with 4 side slanting roof duly projected and painted to both internal and external surfaces with powder coating paint in heat process of sheet and suitable for 500 volts, 50 Hz, 3 phase 4 wire system, fully compartmentalized design with 4 Nos aluminium bus bar suitable for 400 amps mounting on insulator, pre wired with suitable size of copper wire short circuit rating 50 KA (Arms) for one second including suitable aluminium earth strip (not less than 20x3mm)for internal connection to the switches/MCCBs all as specified and comprising with and including following accessories and mounted on PCC Platform made out of PCC 1:3:6, 100 mm thick, 1 Mtr all around the panel board complete with the following items housed in: -
INCOMING :-
MCCB Four Pole 125 Amps, 36 KA breaking capacity, microprocessor release adjustable, 440 volt AC module, 01 No (in coming).
Indicator Lamps (LED type) & Bakelite fuse showing R, Y, B Phase - 01 Set
Digital frequency meter 40-60 Hz - 01 No.
BUSBAR: - 200 Amps rated aluminium bus bar TPN duly insulated with coloured PVC sleeve as per standard colour code and rigidly mounted on Bakelite/DMC insulator bus bar support (Square/ round) insulators of suitable size and good insulation resistance.
OUT GOING
MCCB Four Pole 100 Amps, 25 KA breaking capacity, fixed type thermal magnetic, 440 volt AC module, with earth foult relay, 01 No. (Outgoing).
MCCB Four Pole 63 Amps, 25 KA breaking capacity, fixed type thermal magnetic, 440 volt AC module, with earth foult relay = 03 Nos. (Outgoing).
MCB, 40 Amps, SPN, fixed type thermal magnetic relay with breaking capacity 10KA, at 415 Volts = 02 Nos (Outgoing).
Taking down old unserviceable LT panel and Supply, Installing, Testing and Commissioning of outdoor type LT feeder pillar box of suitable size, pedestal mounted, CPRI approved factory made totally enclosed, dust and vermin proof, shutter in front and in rear side made of 3.15 mm thick CRCA sheet, duly fabricated and having proper locking arrangement in both front and rear door with 4 side slanting roof duly projected and painted to both internal and external surfaces with powder coating paint in heat process of sheet and suitable for 500 volts, 50 Hz, 3 phase 4 wire system, fully compartmentalized design with 4 Nos aluminium bus bar suitable for 400 amps mounting on insulator, pre wired with suitable size of copper wire short circuit rating 50 KA (Arms) for one second including suitable aluminium earth strip (not less than 20x3mm)for internal connection to the switches/MCCBs all as specified and comprising with and including following accessories and mounted on PCC Platform made out of PCC 1:3:6, 100 mm thick, 1 Mtr all around the panel board complete with the following items housed in: -
INCOMING :-
MCCB Four Pole 125 Amps, 36 KA breaking capacity, microprocessor release adjustable, 440 volt AC module, 01 No (In coming).
Indicator Lamps (LED type) & Bakelite fuse showing R, Y, B Phase - 01 Set
Digital frequency meter 40-60 Hz - 01 No.
BUSBAR: - 200 Amps rated aluminium bus bar TPN duly insulated with coloured PVC sleeve as per standard colour code and rigidly mounted on Bakelite/DMC insulator bus bar support (Square/ round) insulators of suitable size and good insulation resistance.
OUT GOING
MCCB Four Pole 125 Amps, 25 KA breaking capacity, fixed type thermal magnetic, 440 Volts AC module, 03 Nos (Outgoing).
MCCB Four Pole 63 Amps, 25 KA breaking capacity, fixed type thermal magnetic, 440 Volt AC module, with earth fault relay = 02 Nos (Outgoing).
MCB 63 Amps, with breaking capacity 10 KA at 415 volts = 02 Nos (Outgoing).
Taking down old unserviceable LT panel and Supply, Installing, Testing and Commissioning of outdoor type LT feeder pillar box of suitable size, pedestal mounted, CPRI approved factory made totally enclosed, dust and vermin proof, shutter in front and in rear side made of 3.15 mm thick CRCA sheet, duly fabricated and having proper locking arrangement in both front and rear door with 4 side slanting roof duly projected and painted to both internal and external surfaces with powder coating paint in heat process of sheet and suitable for 500 volts, 50 Hz, 3 phase 4 wire system, fully compartmentalized design with 4 Nos aluminium bus bar suitable for 400 amps mounting on insulator, pre wired with suitable size of copper wire short circuit rating 50 KA (Arms) for one second including suitable aluminium earth strip (not less than 20x3mm)for internal connection to the switches/MCCBs all as specified and comprising with and including following accessories and mounted on PCC Platform made out of PCC 1:3:6, 100 mm thick, 1 Mtr all around the panel board complete with the following items housed in: -
INCOMING :-
MCCB Four Pole 100 Amps, 25 KA breaking capacity, microprocessor release adjustable, 440 Volt AC module, shunt trip and earth fault relay = 01 No (Incoming).
Indicator Lamps (LED type) & Bakelite fuse showing R, Y, B Phase - 01 Set
Digital frequency meter 40-60 Hz - 01 No.
BUSBAR: - 200 Amps rated aluminium bus bar TPN duly insulated with coloured PVC sleeve as per standard colour code and rigidly mounted on Bakelite/DMC insulator bus bar support (Square/ round) insulators of suitable size and good insulation resistance.
OUT GOING
MCCB Four Pole 63 Amps, 25 KA breaking capacity, fixed type thermal magnetic, 440 Volts AC module with earth foult relay, 03 Nos (Outgoing).
MCB SPN 63 Amps, Adjustable Thermal Magnetic relay with breaking capacity 10 KA at 415 volts = 02 Nos (Outgoing).
MCB SPN 32 Amps, Adjustable Thermal Magnetic relay with breaking capacity 10 KA at 415 volts = 01 No (Outgoing).
Taking down old unserviceable LT panel and Supply, Installing, Testing and Commissioning of outdoor type LT feeder pillar box of suitable size, pedestal mounted, CPRI approved factory made totally enclosed, dust and vermin proof, shutter in front and in rear side made of 3.15 mm thick CRCA sheet, duly fabricated and having proper locking arrangement in both front and rear door with 4 side slanting roof duly projected and painted to both internal and external surfaces with powder coating paint in heat process of sheet and suitable for 500 volts, 50 Hz, 3 phase 4 wire system, fully compartmentalized design with 4 Nos aluminium bus bar suitable for 400 amps mounting on insulator, pre wired with suitable size of copper wire short circuit rating 50 KA (Arms) for one second including suitable aluminium earth strip (not less than 20x3mm)for internal connection to the switches/MCCBs all as specified and comprising with and including following accessories and mounted on PCC Platform made out of PCC 1:3:6, 100 mm thick, 1 Mtr all around the panel board complete with the following items housed in: -
INCOMING :-
MCCB Four Pole 125 Amps, 36 KA breaking capacity, microprocessor release adjustable, 440 Volt AC module, shunt trip and earth fault relay = 01 No (Incoming).
Indicator Lamps (LED type) & Bakelite fuse showing R, Y, B Phase - 01 Set
Digital frequency meter 40-60 Hz - 01 No.
BUSBAR: - 200 Amps rated aluminium bus bar TPN duly insulated with coloured PVC sleeve as per standard colour code and rigidly mounted on Bakelite/DMC insulator bus bar support (Square/ round) insulators of suitable size and good insulation resistance.
OUT GOING
MCCB Four Pole 63 Amps, 25 KA breaking capacity, fixed type thermal magnetic, 440 Volts AC module with earth foult relay, 03 Nos (Outgoing).
MCB SPN 63 Amps, Adjustable Thermal Magnetic relay with breaking capacity 10 KA at 415 volts = 02 Nos (Outgoing).
MCCB Four Pole 100 Amps, 25 KA breaking capacity, fixed type thermal magnetic, 440-volt AC module, with earth fault relay = 01 No (outgoing)
Decarbonising cleaning of existing LT panel cubical type of size 10 feet x 7 feet x 1.5 feet painting with two coats of synthetic enamel paint by using spray gun with incoming partition 01 No and outgoing partitions – 20 Nos including consists of bus bar and circuit chamber, metering chambers CTs and relays chamber, checking the bus bar joints, bus bar and circuits spouts, cleaning and applying bus bar insulation tape to the bus bar, checking the current transformer, applying Monoplast compound at the bus bar joints after tightening of joint, replaced new suitable size of lugs/ suitable copper control cable and reassembling , if any rusted sheet replaced with new sheet as per existing size complete all as per specified and directed. Note: - Cost of lubricant/ cleaning agents (CRC & rust remover) / hardware like springs / bolts/ nuts/ washers, lugs/ suitable cooper cable cost of labour, T&P required for replacement shall be etc shall be deemed to be included in the rate quoted.
S & F LED indicating Lamps for R, Y, B Phases complete including taking down old Unserviceable lamp complete all as specified and directed.
M & L for scrapping down rusted, fallen paint from the Electrical LT panel situated at 44WING/TXR Area including rail/channel of base using mechanical scrapers, brushes, sand paper etc and removing the old paint to the complete outer surfaces and repainting external surfaces with black/yellow (strip) colour with applying a coat of red oxide zinc chrome primer on the both internal & external portion where base metal is exposed, painting spray one coat of synthetic enamel paint for outdoor type panel including MCCB's specific cabinet complete all as specified and directed.
Earthing with galvanised iron earth plate electrode 600 x 600 mm & 6 mm thick buried directly in ground (earth pit not less than 2.25 metre deep below normal GL) with top of earth plate not less than 1.5 metre below GL connected to GI earth strip 32 x 6 mm connected to Earthing lead by means of bolts, nuts, check nuts and washers of galvanised iron or steel with & including ; PCC 1:3:6 C1 pit with cover of RCC 1:1.5:3 A1 40 mm thick reinforced with 3 Nos, 6 mm dia bars both way, watering arrangements with 20 mm GI medium grade pipe ISI marked, GI funnel with GI mesh, filling with mixture of common salt & charcoal in alternate layers, necessary excavation and earth works in any type of soil, including test point, testing & commissioning, complete. Note: - GI earth strip & protection pipe with GI pipe protection shall be measured & paid separately.
GI strip of size 32 x 6 mm as earth continuity conductor as main earthing lead fixed to wall on batten or recesses as chases or buried in ground or drawn in pipe fixed to pole or any other indicated situation complete all as specified and directed.
Excavation in trenches not exc. 1.5 meter wide and not exc 1.5 meter in depth and getting out in any type of soil for laying of cable, pipe etc., complete all as specified and directed.
Returning filling in and including spreading, levelling, watering and well ramming in layers not exc. 25cm thick, complete all as specified and directed.
Removal of excavated materials to a distance not exc. 50 meter and depositing where directed at a level not exc. 1.5 meter above the starting point complete all as specified and as directed.
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 0.63 MB
TD8560LTPANEL.pdf
Tender Documents • 1.07 MB
BOQ_839566.xls
BOQ • 0.36 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .