Loading…
Loading…
| # | Company | Status |
|---|---|---|
| 1 | Admitted-Finance | Admitted-Finance |
| 2 | Admitted-Finance | Admitted-Finance |
Tender Value
Refer Docs
EMD Value
₹18,000
Closing Date
14 May 2024, 11:00 amClosed
Superintending Engineer
office of the S.E., EUDC-II, Sec-18, Noida.
11 KV LINE CONSTRUCTION AND FEEDER BIFURCATION WORK
2024_PVVNL_922236_1
11 KV LINE CONSTRUCTION AND FEEDER BIFURCATION WORK
Open Tender
Electrical Works
Item Rate
60 days
office of the S.E., EUDC-II, Sec-18, Noida.
Attached in DOC
2 documents required · 2 mandatory
₹3,540
S.E. EUDC-II, Noida.
₹18,000
31 May 2024
15 Apr 2024
14 May 2024
15 Apr 2024
14 May 2024
15 Apr 2024
Amount
11KV Chhaparaula feeder Bifurcation work due to untripped supply to consumers
Safe carriage of following stock material, from any of the Store Center of PVVNL to work site including Loading from Store and safe unloading at site for Item No. 3 to 13
PCC 8.5Mtr Pole
ACSR Rabbit Conductor
11KV Pin Poly Pin Insulator with Pin
11KV Disc Insulator with Fitting
Top Channel 125x65x3200mm with Clamp.
T Channel
Dropper Channel
Stone Pad
11KV 3x185sqmm XLPE Cable
Heat Shrinkable outdoor type end termination cable jointing kit suitable for 11KV XLPE 3x185 Sq.mm. cable (Make - Raychem/3M/Denson)
Heat Shrinkable Inddoor type end termination cable jointing kit suitable for 11KV XLPE 3x185 Sq.mm. cable (Make - Raychem/3M/Denson)
Errection of above Following material and Supply and errection of the below material for completing the works as per RESPO.
The excavation of foundation pit in mix soil/normal soil/soft soil & hard rock as per site condition and its back filling and leveling etc. The size of the pit will be (750x450)mm and having depth of 1/6th of the full length of the support. Erection of support, complete with providing & fixing of all G.I.Clamps size of 75x10mm, 65x8mm, G.I.Nut bolt & washer, P.G.Clamp, Stone Pad, Al. Binding wire, 'E' bracket 75x10mm, and other accessories as per drawing. The work includes carriage and handling of supports from sectional store to pit site as well as any fabrication work if required & fixing of cross bracing sets 4.3mtr long, from G.I.Angle 65x65x6mm. The work includes cutting holes and providing G.I.Bolt of 16x40mm size, in the middle of the cross bracing with 01No. spring washer of proper size as per drawing/ as per schedule. Double Pole Structures (a) PCC - 8.5 Mtr. Long Pole
The excavation of foundation pit in mix soil/normal soil/soft soil & hard rock as per site condition and its back filling and leveling etc. The size of the pit will be (750x450)mm and having depth of 1/6th of the full length of the support. Erection of support, complete with providing & fixing of all G.I.Clamps size of 75x10mm, 'F' bracket 75x10mm, G.I.Nut bolt & washer, Stone Pad Al. Binding wire and other accessories as per drawing. The work includes carriage and handling of supports from sectional store to pit site as well as an fabrication work if required. Single Pole (a) PCC - 8.5 Mtr. Long Pole
Grouting of supports in CC 1:3:6 (Cement, sand & 20mm stone grift). Grouting will be done in the block of size (450x450)mm x1/6th of full length of the support, upto ground level, 300mm plinth above the ground level with C.C. 1:3:6 (Cement, Course sand and Stone grift) with muffing as per RESPO. Work includes back filling and proper ramming. Single Pole and Double Pole (a) PCC - 8.5 Mtr. Long Pole
FIXING OF PIN INSULATOR WITH PIN, COMPLETE WORK IN ALL RESPECT.
FIXING OF TOP CHANNEL AS PER SITE REQUIREMENT.
FIXING OF DROPPER CHANNEL AS PER SITE REQUIREMENT.
FIXING OF STONE PAD AS PER SITE REQUIREMENT.
FIXING OF T Channel AS PER SITE REQUIREMENT.
FIXING OF Disc Insulator with Fitting AS PER SITE REQUIREMENT.
Preparation of 11 KV Power Cable ends: Making of 11 KV XLPE Heat shrinkable Indoor jointing kits suitable for 3x185sqmm XLPE Cable after duly plumbing and taping of cable, providing, fixing and crimping of proper size good quality lugs with complete connention in all respect.
Supply of 160mm OD PN-4-PE-80 Grade UV Stabilized HDPE Pipe.(PVVNL GTP APPROVED)
Drilling of dia 220 mm in two parallel bores for Double Curcuit by trenchless method by horizontal boring machine at a depth of 1.50 mtrs to 2.50 mtrs. (as requirement at site) below the ground level with complete work in all respect as per RESPO.
Laying of HDPE Pipe PE-80, PN-6, DN-160mm dia by HDD trenchless method for 11KV, 3x185sq.mm XLPE cable as per site requirement. (PVVNL GTP APPROVED HDPE PIPE SHALL BE SUPPLIED WITH INSPECTION.)
Laying and commissiong of 11KV 3x185sqmm XLPE Cable Double Ckt. in HDPE Pipe dia after digging HDD trenchless method boring including complete connections at both ends after providing and crimping of lugs of proper size for completion of work. as per site requirement.
Digging of pits of size 4 mtr x 4 mtr x 1.5 mtr for cable loop and making risers at double pole and re-filling of pits in proper manner with required material at kacha/pakka and hot mix road. (All Work and material in the scope of contractor)
Laying of 11 KV 3X185 Sq.mm XLPE Cable in the air on cable Riser Double Pole, existing trench cable trench, nala x-ing & G.I.Pipe and making connection complete at both ends.
Laying, spreading, lifting and final sagging of 3 phases ACSR Rabbit conductor in accordance with Line chart includidng binding and fixing of all accessories in 03Nos. Conductor in parallel as per site requirement.
Preparation of 11 KV Power Cable ends: Making of 11 KV XLPE Heat shrinkable outdoor jointing kits suitable for 3x185sqmm XLPE Cable after duly plumbing and taping of cable, providing, fixing and crimping of proper size good quality lugs with complete connention in all respect.
PROVIDING AND FIXING OF Holding Clamps with Nut & BoltsAS PER REQUIREMENT.
PROVIDING AND FIXING OF Best Quality G.I. Pipe 6"dia for Pole Riser with Complete work in all respect.
PROVIDING AND FIXING OF NUT BOLT AND WASHERSAS PER REQUIREMENT.
New 11KV U/G 300 Mtr Duble Circuit Link Line Achheja To Mahak work due to untripped supply to consumers.
Safe carriage of following stock material, from any of the Store Center of PVVNL to work site including Loading from Store and safe unloading at site for Item No. 38 to 44
ST/PCC 11mtr Long Pole.
Top Channel 125x65x3200mm with Clamp.
Dropper Channel
Stone Pad
11KV 3x185sqmm XLPE Cable
Heat Shrinkable outdoor type end termination cable jointing kit suitable for 11KV XLPE 3x185 Sq.mm. cable (Make - Raychem/3M/Denson)
Heat Shrinkable Straigth Trough suitable for 11KV XLPE 3x185 Sq.mm. cable (Make - Raychem/3M/Denson)
Errection of above Following material and Supply and errection of the below material for completing the works as per RESPO.
The excavation of foundation pit in mix soil/normal soil/soft soil & hard rock as per site condition and its back filling and leveling etc. The size of the pit will be (750x450)mm and having depth of 1/6th of the full length of the support. Erection of support, complete with providing & fixing of all G.I.Clamps size of 75x10mm, 65x8mm, G.I.Nut bolt & washer, P.G.Clamp, Stone Pad, Al. Binding wire, 'E' bracket 75x10mm, and other accessories as per drawing. The work includes carriage and handling of supports from sectional store to pit site as well as any fabrication work if required & fixing of cross bracing sets 4.3mtr long, from G.I.Angle 65x65x6mm. The work includes cutting holes and providing G.I.Bolt of 16x40mm size, in the middle of the cross bracing with 01No. spring washer of proper size as per drawing/ as per schedule. Double Pole Structures (a) ST/PCC - 11 Mtr Long Pole.
The excavation of foundation pit in mix soil/normal soil/soft soil & hard rock as per site condition and its back filling and leveling etc. The size of the pit will be (750x450)mm and having depth of 1/6th of the full length of the support. Erection of support, complete with providing & fixing of all G.I.Clamps size of 75x10mm, 'F' bracket 75x10mm, G.I.Nut bolt & washer, Stone Pad Al. Binding wire and other accessories as per drawing. The work includes carriage and handling of supports from sectional store to pit site as well as an fabrication work if required. Single Pole (a) ST/PCC - 11 Mtr Long Pole.
Grouting of supports in CC 1:3:6 (Cement, sand & 20mm stone grift). Grouting will be done in the block of size (450x450)mm x1/6th of full length of the support, upto ground level, 300mm plinth above the ground level with C.C. 1:3:6 (Cement, Course sand and Stone grift) with muffing as per RESPO. Work includes back filling and proper ramming. Single Pole and Double Pole (a) ST/PCC - 11 Mtr Long Pole.
FIXING OF TOP CHANNEL AS PER SITE REQUIREMENT.
FIXING OF DROPPER CHANNEL AS PER SITE REQUIREMENT.
Preparation of 11 KV Power Cable ends: Making of 11 KV XLPE Straight Through suitable for 3x185sqmm XLPE Cable after duly plumbing and taping of cable, providing, fixing and crimping of proper size good quality lugs with complete connention in all respect.
Supply of 160mm OD PN-4-PE-80 Grade UV Stabilized HDPE Pipe.(PVVNL GTP APPROVED)
Drilling of dia 220 mm in two parallel bores for Double Curcuit by trenchless method by horizontal boring machine at a depth of 1.50 mtrs to 2.50 mtrs. (as requirement at site) below the ground level with complete work in all respect as per RESPO.
Laying of HDPE Pipe by HDD trenchless method for 11KV, 3x185sq.mm XLPE cable as per site requirement. (PVVNL GTP APPROVED HDPE PIPE SHALL BE SUPPLIED WITH INSPECTION.)
Laying and commissiong of 11KV 3x185sqmm XLPE Cable Double Ckt. in HDPE Pipe dia after digging HDD trenchless method boring including complete connections at both ends after providing and crimping of lugs of proper size for completion of work. as per site requirement.
Digging of pits of size 4 mtr x 4 mtr x 1.5 mtr for cable loop and making risers at double pole and re-filling of pits in proper manner with required material at kacha/pakka and hot mix road. (All Work and material in the scope of contractor)
Laying of 11 KV 3X185 Sq.mm XLPE Cable in the air on cable Riser Double Pole, existing trench cable trench, nala x-ing & G.I.Pipe and making connection complete at both ends.
Preparation of 11 KV Power Cable ends: Making of 11 KV XLPE Heat shrinkable outdoor jointing kits suitable for 3x185sqmm XLPE Cable after duly plumbing and taping of cable, providing, fixing and crimping of proper size good quality lugs with complete connention in all respect.
PROVIDING AND FIXING OF Holding Clamps with Nut & BoltsAS PER REQUIREMENT.
PROVIDING AND FIXING OF Best Quality G.I. Pipe 6"dia for Pole Riser with Complete work in all respect.
PROVIDING AND FIXING OF NUT BOLT AND WASHERSAS PER REQUIREMENT.
Providing and Driving of MS earth rod of size 20x2500 mm in earth and jointing through G.I. wire of 6 SWG between support and earth electrode by providing proper size of bolts and nuts for pole earthing. Supply Erection, fixing, grouting of stay rod in cement, sand and brick ballast in ration 1:4:8 in Block 600*600*300 mm with binding & nuzzling including providing & fixing of stay insulator complete in all respect with grouting. (All Work and Material in the scope of Contractor)
New 11KV Overhead Link Line (800 ckt Mtr) For Load Transfer Chhaproula To Khera Dharampura feeder work due to untripped supply to consumers.
Safe carriage of following stock material, from any of the Store Center of PVVNL to work site including Loading from Store and safe unloading at site for Item No. 65 to 70
ST/PCC 11mtr Long Pole.
ACSR Rabbit Conductor
11KV Pin Poly Pin Insulator with Pin
11KV Disc Insulator with Fitting
T Channel
Stone Pad
Errection of above Following material and Supply and errection of the below material for completing the works as per RESPO.
The excavation of foundation pit in mix soil/normal soil/soft soil & hard rock as per site condition and its back filling and leveling etc. The size of the pit will be (750x450)mm and having depth of 1/6th of the full length of the support. Erection of support, complete with providing & fixing of all G.I.Clamps size of 75x10mm, 65x8mm, G.I.Nut bolt & washer, P.G.Clamp, Stone Pad, Al. Binding wire, 'E' bracket 75x10mm, and other accessories as per drawing. The work includes carriage and handling of supports from sectional store to pit site as well as any fabrication work if required & fixing of cross bracing sets 4.3mtr long, from G.I.Angle 65x65x6mm. The work includes cutting holes and providing G.I.Bolt of 16x40mm size, in the middle of the cross bracing with 01No. spring washer of proper size as per drawing/ as per schedule. Double Pole Structures (a) ST/PCC - 11 Mtr Long Pole.
The excavation of foundation pit in mix soil/normal soil/soft soil & hard rock as per site condition and its back filling and leveling etc. The size of the pit will be (750x450)mm and having depth of 1/6th of the full length of the support. Erection of support, complete with providing & fixing of all G.I.Clamps size of 75x10mm, 'F' bracket 75x10mm, G.I.Nut bolt & washer, Stone Pad Al. Binding wire and other accessories as per drawing. The work includes carriage and handling of supports from sectional store to pit site as well as an fabrication work if required. Single Pole (a) ST/PCC - 11 Mtr Long Pole.
Grouting of supports in CC 1:3:6 (Cement, sand & 20mm stone grift). Grouting will be done in the block of size (450x450)mm x1/6th of full length of the support, upto ground level, 300mm plinth above the ground level with C.C. 1:3:6 (Cement, Course sand and Stone grift) with muffing as per RESPO. Work includes back filling and proper ramming. Single Pole and Double Pole (a) ST/PCC - 11 Mtr Long Pole.
FIXING OF PIN INSULATOR WITH PIN, COMPLETE WORK IN ALL RESPECT.
FIXING OF STONE PAD AS PER SITE REQUIREMENT.
FIXING OF T Channel AS PER SITE REQUIREMENT.
FIXING OF Disc Insulator with Fitting AS PER SITE REQUIREMENT.
Laying, spreading, lifting and final sagging of 3 phases ACSR Rabbit conductor in accordance with Line chart includidng binding and fixing of all accessories in 03Nos. Conductor in parallel as per site requirement.
PROVIDING AND FIXING OF Holding Clamps with Nut & BoltsAS PER REQUIREMENT.
Providing and Driving of MS earth rod of size 20x2500 mm in earth and jointing through G.I. wire of 6 SWG between support and earth electrode by providing proper size of bolts and nuts for pole earthing. Supply Erection, fixing, grouting of stay rod in cement, sand and brick ballast in ration 1:4:8 in Block 600*600*300 mm with binding & nuzzling including providing & fixing of stay insulator complete in all respect with grouting. (All Work and Material in the scope of Contractor)
PROVIDING AND FIXING OF NUT BOLT AND WASHERSAS PER REQUIREMENT.
New 11 KV Line Link Line of Jon Samana To Sadopur Road work due to untripped supply to consumers. 1.5km
Safe carriage of following stock material, from any of the Store Center of PVVNL to work site including Loading from Store and safe unloading at site for Item No. 85 to 90
PCC 8.5Mtr Pole
11KV 3x70sqmm XLPE Cable
Heat Shrinkable outdoor type end termination cable jointing kit suitable for 11KV XLPE 3x70 Sq.mm. cable (Make - Raychem/3M/Denson)
11KV Pin Poly Pin Insulator with Pin
T Channel
Stone Pad
Errection of above Following material and Supply and errection of the below material for completing the works as per RESPO.
The excavation of foundation pit in mix soil/normal soil/soft soil & hard rock as per site condition and its back filling and leveling etc. The size of the pit will be (750x450)mm and having depth of 1/6th of the full length of the support. Erection of support, complete with providing & fixing of all G.I.Clamps size of 75x10mm, 65x8mm, G.I.Nut bolt & washer, P.G.Clamp, Stone Pad, Al. Binding wire, 'E' bracket 75x10mm, and other accessories as per drawing. The work includes carriage and handling of supports from sectional store to pit site as well as any fabrication work if required & fixing of cross bracing sets 4.3mtr long, from G.I.Angle 65x65x6mm. The work includes cutting holes and providing G.I.Bolt of 16x40mm size, in the middle of the cross bracing with 01No. spring washer of proper size as per drawing/ as per schedule. Double Pole Structures (a) PCC - 8.5 Mtr. Long Pole
The excavation of foundation pit in mix soil/normal soil/soft soil & hard rock as per site condition and its back filling and leveling etc. The size of the pit will be (750x450)mm and having depth of 1/6th of the full length of the support. Erection of support, complete with providing & fixing of all G.I.Clamps size of 75x10mm, 'F' bracket 75x10mm, G.I.Nut bolt & washer, Stone Pad Al. Binding wire and other accessories as per drawing. The work includes carriage and handling of supports from sectional store to pit site as well as an fabrication work if required. Single Pole (a) PCC - 8.5 Mtr. Long Pole
Grouting of supports in CC 1:3:6 (Cement, sand & 20mm stone grift). Grouting will be done in the block of size (450x450)mm x1/6th of full length of the support, upto ground level, 300mm plinth above the ground level with C.C. 1:3:6 (Cement, Course sand and Stone grift) with muffing as per RESPO. Work includes back filling and proper ramming. Single Pole and Double Pole (a) PCC - 8.5 Mtr. Long Pole
FIXING OF PIN INSULATOR WITH PIN, COMPLETE WORK IN ALL RESPECT.
FIXING OF TOP CHANNEL AS PER SITE REQUIREMENT.
FIXING OF DROPPER CHANNEL AS PER SITE REQUIREMENT.
FIXING OF STONE PAD AS PER SITE REQUIREMENT.
FIXING OF T Channel AS PER SITE REQUIREMENT.
Preparation of 11 KV Power Cable ends: Making of 11 KV XLPE Heat shrinkable outdoor jointing kits suitable for 3x70sqmm XLPE Cable after duly plumbing and taping of cable, providing, fixing and crimping of proper size good quality lugs with complete connention in all respect.
Laying, spreading, lifting and final sagging of 3x70sqmm XLPE Cable in accordance with Line chart includidng binding and fixing of all accessories in as per site requirement.
PROVIDING AND FIXING OF Holding Clamps with Nut & BoltsAS PER REQUIREMENT.
Providing and Driving of MS earth rod of size 20x2500 mm in earth and jointing through G.I. wire of 6 SWG between support and earth electrode by providing proper size of bolts and nuts for pole earthing. Supply Erection, fixing, grouting of stay rod in cement, sand and brick ballast in ration 1:4:8 in Block 600*600*300 mm with binding & nuzzling including providing & fixing of stay insulator complete in all respect with grouting. (All Work and Material in the scope of Contractor)
PROVIDING AND FIXING OF NUT BOLT AND WASHERSAS PER REQUIREMENT.
Royal Electrical and Mech. Traders
tech_eval.pdf
boq_comp_chart.xlsx
xlsx
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .