SE ETC NOIDA
220 KV SUBSTATION SECTOR-20 NOIDA
annual regular maintenance related works of 6 nos. 5.5 TR capacity ductable A.C, 4 nos. 2 TR capacity window A.C and 2 nos. 2 TR capacity window split conditioners etc. installed in control room and BCU at 220 kV S/S Sec-20 Noida under ETD-I Noida
2021_UPTCL_598436_1
E-T-17/ETCN/2021-22
Open Tender
Electrical Works
Item Rate
365 days
NOIDA
Please refer Tender documents.
2 documents required · 2 mandatory
₹590
EE ETD NOIDA
₹3,000
17 Aug 2021
23 Jun 2021
13 Aug 2021
23 Jun 2021
12 Aug 2021
23 Jun 2021
Amount
Complete servicing and overhauling work of ductable AC 5.5 TR complete cleaning of all parts of indoor & outdoor unit includes filters, cooling/condensing coil by cleaning chemical, adjust the fans axis assembly & electronic expansion valve, all coils joint, repairing of valve set, providing and fixing of damaged nut bolt etc. (as required), & proper cleaning of corrosion by emery paper /cloths, check the operation of all parts of AC for proper operation of each and every stage after assemble the same as per standard design, technical specifications. Routine maintenance/service for one summer season for proper operation of all ACs also included in this work at 220 KV Sub-Station Sector-20 Noida.
Nitrogen (N2) Gas testing by Nitrogen holding at 609 PSIG or each section of ACs conditioning coil and attends the leakage window air conditioner; if any, by repair or replacement of the coil/copper pipe, valve, nut & bolt, sealing kit etc. and fitting the each part of copper coil/pipe by using welding/soldering, bolt tightened, bond and Teflon tape as required for attend the leakages.
Filling of full cooling gas (Mafron R-22) in 05 No ACs as required (up to pressure of 65- 75 N/Sq. MM).
Complete cleaning of inside surface of duct network by vacuum or using of power vacuum air compressor, air hammer, and special nozzles up to standard lists surface deposit limits of by air sweep with other required accessories, robotic camera after the cleaning works. Repairing & Re-fixing of vibration isolators, air take-offs, stack boots and heads, turning vanes, plenums and air terminal units as per technical specifications.
Repairing of fan motor.
Repairing of Contractor.
Repairing of dryer valve set.
Providing & fixing of low pressure switch.
Replacement/Repair of Compressor for various types Air Conditioners of Split type, Daikin/Hitachi Make 2.0 TR.
Work of Complete pressure testing caccum creation & Gas charging with refrigrating gas for various types Air Conditioners of Split type, Daikin/Hitachi Make 2.0 TR
Replacement of damaged copper tubes including re-provision of thermal insulation between indoor unit & outdoor unit the work includes soldering and fitting with proper shape of copper tube for various types Air Conditioners as given below.
Replacement of demaged/defective cooling condensor coil of split AC having 2.0 TR, gas cutting soldering and testing of leakage from cored tube and proper fitting for various types Air Conditioners as given below.
Himalaya Contractor & Suppliers
M/S A K ELECTRICAL
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .