Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹2.6 LAdmitted-Finance | ₹2.6 L | L1 | Admitted-Finance |
| 2 | L2₹3.3 LAdmitted-Finance | ₹3.3 L | L2 | Admitted-Finance |
| 3 | L3₹3.6 LAdmitted-Finance | ₹3.6 L | L3 | Admitted-Finance |
| Sl No | Description | Qty | Unit | Gupta Elect and Engg Works L2 | Meena Elect & Engg. Works L3 | Perfect Power Transformer Associates L1 |
|---|---|---|---|---|---|---|
| 0.00Internal inspection of 40 MVA Transformer-I at 132KV Substation Ujhani under Electricity Transmission Division, Budaun with all Cost of Men, Materials, Misc. Consumables, T&Ps etc. Required for Satisfactory Completion of the Work as per Technical Specifications and Direction of the Supervising Engineer, as per Details below : | ||||||
| 1.00 | Safe carriage of 20KL oil storage tank from 220kv Sambhal or designated substation to 132KV Ujhani Substation (Distance approx 100Km) including shifting and loading of oil storage tank from 220KV Sambhal or designated substation and unloading, shifting and placing of same in switchyard/storage place at 132KV Ujhani Substation. | 1 | Job | 18,000 ₹18,000 | 16,500 ₹16,500 | 15,000 ₹15,000 Lowest |
| 2.00 | Drain out of complete Transformer oil in empty oil tanker for internal inspection of Transformer (Centrifuging machine with operator shall be provided by the contractor) | 1 | Job | 15,000 ₹15,000 | 18,000 ₹18,000 | 14,500 ₹14,500 Lowest |
| 3.00 | Opening of inspection plate, dismantling of HV/ L.V side bushings for internal inspection of 40 MVA Transformer at 132 KV Substation Ujhani. | 1 | Job | 24,500 ₹24,500 | 26,000 ₹26,000 | 19,990 ₹19,990 Lowest |
| 4.00 | Internal inspection of 40 MVA Transformer, checking of HV/LV side winding lead of Transformer, tightening of joints, connections and all other components inside the main tank of Transformer. | 1 | Job | 85,000 ₹85,000 | 98,000 ₹98,000 | 74,500 ₹74,500 Lowest |
| 5.00 | Erection of dismantied bushings, Inspection Plate and replacement of gasket of open parts of 40 MVA Transformer. | 1 | Job | 30,000 ₹30,000 | 28,500 ₹28,500 | 25,500 ₹25,500 Lowest |
| 6.00 | Complete evacuation of 40 MVA Transformer main tank and filling of Dry Air/Dry Nitrogen of dew point-50°C or better in vacuum up to pressure of 0.25Kg Cin2 and the again evacuating the Transformer tank after required time interval (approx 12/24 Hrs) using centrifuging machine the work shall including connecting pipe of machine as required measuring due point values of N2 alter ever eyele till the required value is achieved. | 1 | Job | 55,000 ₹55,000 | 60,000 ₹60,000 | 40,000 ₹40,000 Lowest |
| 7.00 | Create the vacuum inside the 40 MVA Transformer before filling the Transformer oil including vacuum standing test. | 1 | Job | 12,500 ₹12,500 | 15,000 ₹15,000 | 9,950 ₹9,950 Lowest |
| 8.00 | Filling of Transformer oil from oil tanker to Transformer main tank after internal inspection of damaged 40 MVA Transformer. (Centrifuging machine with operator shall be provided by the contractor) | 1 | Job | 7,500 ₹7,500 | 9,950 ₹9,950 | 5,500 ₹5,500 Lowest |
| 9.00 | Centrifugine the Transformer oil in mam tank and circulating the Transformer oil through centrifuging machine and taking BDV time to time. (Centrifuging machine shall be provided by the contractor) (approx -20KL) | 1 | Job | 55,000 ₹55,000 | 60,000 ₹60,000 | 40,000 ₹40,000 Lowest |
Tender Value
₹2.7 L
EMD Value
₹3,500
Closing Date
29 Jul 2026, 2:00 pmClosed
SE ETC Bareilly
Electy. Transmission Circle Transmission Campus Near L.I.C. Office Rampur Garden, Bareilly
Internal Inspection of 40 MVA Transformer-I at 132KV Substation Ujhani under Electricity Transmission Division, Budaun
2026_UPTCL_1171911_1
Tender No. 01/ETC(B)/2026-27
Open Tender
Electrical Works
Item Wise
10 days
Budaun
Please refer Tender documents.
2 documents required · 2 mandatory
₹590
SE ETC BAREILLY
₹3,500
31 Jul 2026
23 Jul 2026
29 Jul 2026
23 Jul 2026
29 Jul 2026
23 Jul 2026
| Sl No | Description | Qty | Unit | Est. Rate | Est. Amount |
|---|---|---|---|---|---|
| 0 | Internal inspection of 40 MVA Transformer-I at 132KV Substation Ujhani under Electricity Transmission Division, Budaun with all Cost of Men, Materials, Misc. Consumables, T&Ps etc. Required for Satisfactory Completion of the Work as per Technical Specifications and Direction of the Supervising Engineer, as per Details below : | - | - | - | - |
| 1 | Safe carriage of 20KL oil storage tank from 220kv Sambhal or designated substation to 132KV Ujhani Substation (Distance approx 100Km) including shifting and loading of oil storage tank from 220KV Sambhal or designated substation and unloading, shifting and placing of same in switchyard/storage place at 132KV Ujhani Substation. | 1 | Job | - | - |
| 2 | Drain out of complete Transformer oil in empty oil tanker for internal inspection of Transformer (Centrifuging machine with operator shall be provided by the contractor) | 1 | Job | - | - |
| 3 | Opening of inspection plate, dismantling of HV/ L.V side bushings for internal inspection of 40 MVA Transformer at 132 KV Substation Ujhani. | 1 | Job | - | - |
| 4 | Internal inspection of 40 MVA Transformer, checking of HV/LV side winding lead of Transformer, tightening of joints, connections and all other components inside the main tank of Transformer. | 1 | Job | - | - |
| 5 | Erection of dismantied bushings, Inspection Plate and replacement of gasket of open parts of 40 MVA Transformer. | 1 | Job | - | - |
| 6 | Complete evacuation of 40 MVA Transformer main tank and filling of Dry Air/Dry Nitrogen of dew point-50°C or better in vacuum up to pressure of 0.25Kg Cin2 and the again evacuating the Transformer tank after required time interval (approx 12/24 Hrs) using centrifuging machine the work shall including connecting pipe of machine as required measuring due point values of N2 alter ever eyele till the required value is achieved. | 1 | Job | - | - |
| 7 | Create the vacuum inside the 40 MVA Transformer before filling the Transformer oil including vacuum standing test. | 1 | Job | - | - |
| 8 | Filling of Transformer oil from oil tanker to Transformer main tank after internal inspection of damaged 40 MVA Transformer. (Centrifuging machine with operator shall be provided by the contractor) | 1 | Job | - | - |
| 9 | Centrifugine the Transformer oil in mam tank and circulating the Transformer oil through centrifuging machine and taking BDV time to time. (Centrifuging machine shall be provided by the contractor) (approx -20KL) | 1 | Job | - | - |
stage.html
html • 0.03 MB
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 0.13 MB
BOQ_2200470.xls
BOQ • 0.28 MB
NIT01.pdf
Tender Documents • 0.74 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at [email protected].