| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | 1₹5.9 LAccepted-Finance | ₹5.9 L | 1 | Accepted-Finance Admitted |
| 2 | 2₹6.0 LAccepted-Finance | ₹6.0 L | 2 | Accepted-Finance Admitted |
| 3 | Rejected-Technical | - | - | Rejected-Technical FDR not submitted |
| 4 | Rejected-Technical | - | - | Rejected-Technical FDR not submitted |
| 5 | Rejected-Technical 1008 A PREMIER ENGINEERING COMPANY PURVI RITHANI MEERUT DELHI ROAD MEERUT UTTAR PRADESH 250103 INDIA UDYAM UP 56 0002873 09AARFP4205H1Z1 R M | MEERUT | UTTAR PRADESH | 250103 | - | - | Rejected-Technical FDR not submitted |
| Sl No | Description | Qty | Unit | R S Electricals L2 | GOGIA BROTHERS L1 |
|---|---|---|---|---|---|
| 1.01 | Dismantling of the old structure & their components of panel, removing of cable connection & shifting the panel from site to store | 1 | Job | 7,800 ₹9,204 | 7,450 ₹8,791 |
| 1.02 | LT Distribution panel sheet steel enclosure made out of 2mm CRCA sheet totally enclosed, powder coated free standing, floor mounted type, dust& vermin proof, outward opening, lockable doors having hidden hinges and a bolted back cover both using non-deteriorating neoprene rubber gaskets to provide IP-54 protection. Each part of the fabricated panel will be strictly subjected to seven tank treatment. The various components, assemblies and sub equipment’s of the panel will be as per standard given in relevant IS. The bus bar of the panel will be shaped out of high conductivity, electrolytic conductor and shall be liberal sized in aluminum. The control wiring of the panel will be done with PVC flexible copper wires of 1.5mm cross section. Each wire will be terminating with a ferule crimped to the wire, size 1500MM x1200x375mm. Having following components of approved make. | 1 | Nos. | 1,18,000 ₹1,39,240 | 1,14,800 ₹1,35,464 |
| 1.03 | MCCB 415V, Four Pole High breaking capacity 36KAor higher 50Hz,250Amp with spreader - Make L&T/Siemens | 1 | Nos. | 34,000 ₹40,120 | 33,900 ₹40,002 |
| 1.04 | MCCB 415V, TP 3phase High breaking capacity 36KA or higher 50Hz,125Amp with spreader - Make L&T/Siemens | 2 | Nos. | 27,600 ₹32,568 | 27,000 ₹31,860 |
| 1.05 | MCB Single pole 6Amp. Make L&T/Siemens | 3 | Nos. | 615 ₹725.7 | 600 ₹708 |
| 1.06 | MCB Triple pole 63Amp. Make L&T/Siemens | 2 | Nos. | 3,600 ₹4,248 | 3,490 ₹4,118.2 |
| 1.07 | MCB Triple pole 32Amp. Make L&T/Siemens | 2 | Nos. | 2,300 ₹2,714 | 2,260 ₹2,666.8 |
| 1.08 | Over load relay 45-75 amp Make: L&T/Siemens | 2 | Nos. | 8,800 ₹10,384 | 8,700 ₹10,266 |
| 1.09 | Over load relay 4.5 -7.5 amp Make: L&T/Siemens | 2 | Nos. | 3,000 ₹3,540 | 2,900 ₹3,422 |
| 1.10 | Digital Amp. Meter Make AE/L&T | 3 | Nos. | 3,600 ₹4,248 | 3,510 ₹4,141.8 |
Tender Value
Refer Docs
EMD Value
₹11,800
Closing Date
30 Jan 2026, 3:30 pmClosed
EE(EnM)M-12
D-Block Saket
Renovation - Improvement in the Existing LT System at Pocket A-14 Kalkaji Extension BPS under Tughlakabad Constituency AC-52.
2026_DJB_285349_5
NIT No. 29/EE(EnM)M-12/2025-26
Open Tender
Miscellaneous Works
30 days
EE(EnM)M-12
Please refer Tender documents.
3 documents required · 3 mandatory
₹500
EE(EnM)WnSS-II
₹11,800
7 Mar 2026
22 Jan 2026
30 Jan 2026
22 Jan 2026
30 Jan 2026
22 Jan 2026
Dismantling of the old structure & their components of panel, removing of cable connection & shifting the panel from site to store
LT Distribution panel sheet steel enclosure made out of 2mm CRCA sheet totally enclosed, powder coated free standing, floor mounted type, dust& vermin proof, outward opening, lockable doors having hidden hinges and a bolted back cover both using non-deteriorating neoprene rubber gaskets to provide IP-54 protection. Each part of the fabricated panel will be strictly subjected to seven tank treatment. The various components, assemblies and sub equipment’s of the panel will be as per standard given in relevant IS. The bus bar of the panel will be shaped out of high conductivity, electrolytic conductor and shall be liberal sized in aluminum. The control wiring of the panel will be done with PVC flexible copper wires of 1.5mm cross section. Each wire will be terminating with a ferule crimped to the wire, size 1500MM x1200x375mm. Having following components of approved make.
MCCB 415V, Four Pole High breaking capacity 36KAor higher 50Hz,250Amp with spreader - Make L&T/Siemens
MCCB 415V, TP 3phase High breaking capacity 36KA or higher 50Hz,125Amp with spreader - Make L&T/Siemens
MCB Single pole 6Amp. Make L&T/Siemens
MCB Triple pole 63Amp. Make L&T/Siemens
MCB Triple pole 32Amp. Make L&T/Siemens
Over load relay 45-75 amp Make: L&T/Siemens
Over load relay 4.5 -7.5 amp Make: L&T/Siemens
Digital Amp. Meter Make AE/L&T
Digital Volt Meter-Make AE/L&T
Motor protection RelayM-10 type Make: L&T/Siemens/Protech
Power contactor 220V 3phase 110Amp. Make L&T/Siemens
Power contactor 220V 3phase 70Amp. Make L&T/Siemens
Power contactor 220V 3phase18Amp. Make L&T/Siemens
Star delta timer on delay make: L&T/Siemens
Indicating lights LED type RYB & On/OFF, Make: L&T /Siemens
Current Transformer250/5& 100/5 Make AE /Advance/Saviour
On load change over switch 200Amp. Open execution type Make:L&T/HPL
Supply of 35 sq mm Copper Cable single core, Make: Havells/ polycab / Grandlay/ Finolex
Loading, unloading by crane or heavy labor and cartage up to site cleaning & dressing the surface for
Installation of the panel at site on base frame, laying of cable, termination of cable both incoming &out going side
Testing & commissioning of panel, as per required parameters with relevant IS. testing of the panel prior to switching on as follow :- (1) Continuity and earth testing (2) Meagering of all equipment’s for phase to phase, neutral to body, neutral to earth and phase to earth. (3) checking for all tightness of nut and bolts (4) Alignments of doors etc. (5) Interlocking tests. All function tests
stage.html
html • 0.04 MB
tech_eval.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 1.57 MB
BOQ_377523.xls
BOQ • 0.31 MB
Download all tender documents and submit your bid