Tender Value
₹34.9 L
EMD Value
₹69,800
Closing Date
7 Aug 2026, 6:00 pmClosed
GE (AF) Jaisalmer
GE (AF) Jaisalmer
REPAIR/ MAINT TO FIRE ALARM SYSTEM AND MISC WORK AT AIR FORCE STATION
2026_MES_770137_2
8420/GE/E8
Open Tender
Miscellaneous Works
Item Rate
180 days
GE (AF) Jaisalmer
As per tender documents
7 documents required · 7 mandatory
₹500
GE (AF) Jaisalmer
₹69,800
Yes
3 Sept 2026
18 Jul 2026
10 Aug 2026
18 Jul 2026
7 Aug 2026
25 Jul 2026
| Sl No | Description | Qty | Unit | Est. Rate | Est. Amount |
|---|---|---|---|---|---|
| 1 | Comprehensive maintenance of complete Fire alarm system addressable type AT 15 AFH including taking down carefully of existing faulty fire alarm detection system/ detectors from existing location ie roof surface, false ceiling surface or above or in between false ceiling and roof surface including removing of false ceiling of any type and refixing the same after repair /replacement of fire detector work and making good the existing distrubed surface to match with the existing surface complete fire alarm system, including minor repairs & control wiring ,testing with SMOKE DETECTER TESTER functionality of all components, cleaning all device in control panels shall be carried out as necessary, testing of fire alarm system, as directed by Engineer-in-Charge/ Users at various locations in GE (AF) Jaisalmer.
Service engineer to ensure serviceability of fire alarm system as follows:-
(i) Check all connection of control panel
(ii) Check all sensor, detectors & call points.
(iii) test detector and call point in each zone as required.
(iv) Testing of alarm sounders.
(v) Cleaning of control panel and wirings.
MAKE:-Siemens
NOTE 1 FOR item no 1
.The entire scope of work specified under BOQ/Schedule ‘A’, Item No. 1.00 & 2.00 including repair /replacement of any defective parts of the fire alarm system , shall be executed exclusively through the Original Equipment Manufacturer (OEM) i.e., M/s Siemens PVT LTD & M/s Honeywell International INC or their accredicted/authorized agency.The contractor shall upload/submit a scanned copy of the Intent of Memorandum of Understanding (MoU) executed with the above OEM in Cover No. 1, along with his bid application.Further, the contractor shall also submit the hard copy of the said MoU along with his application before the last date of bid submission. Failure to upload/submit the MoU (both scanned copy and hard copy) shall result in summary rejection of the bid, and Cover No. 2 shall not be opened under any circumstances.However before commencement of work ,the contractor shall mandatorily submit the final and fully executed MOU/Agreement With the OEM.No work Shall be permitted to start without submission of the final MOU
NOTE 2 FOR item no 1
-01. Contractor will be responsible to keep update of fire alarm system, serviceable condition.
02. Contractor Shall Maintain all the Documents and Produce to the Concerned Engineer in charge as and when required /preparation of RAR.
03. Contractor shall give the Demo and training for all duty staffs as when required about the fire alarm System. the below note.
04. Necessary T & P required will be included in quoted rate.
05.Spares required for replacement, shall be measured and paid for seperately under respective items here in after
06.Service engineer to ensure serviceability of fire alarm system as follows:-
(i) Check all connection of control panel
(ii) Check all sensor, detectors & call points.
(iii) test detector and call point in each zone as required.
(iv) Testing of alarm sounders.
(v) Cleaning of control panel and wirings.
NOTE 3 FOR item no 1
1. Attending break down maintenance and replacement of unserviceable spare parts with new ones as required at site complete all as specified and directed by Engineer-in-charge
2. In case of any breakdown, the contractor shall ensure that the fault is rectified and the system is made fully operational within 48 hours from the time of reporting. Immediate site visit by the authorized service personnel within this period shall be mandatory. Failure to comply with the above timeline shall attract a penalty of ₹2,000/- (Rupees Two Thousand only) per day of delay, recoverable from the contractor’s dues, in addition to any other action as deemed fit by the Engineer-in-Charge.
3. The repair and maintenance of Fire Alarm system should be done through OEM or through the authorised service provider of the OEM.
4.The contractor/OEM shall ensure strict adherence to all applicable safety standards, statutory regulations, and OEM-recommended safety practices during the installation, operation, and maintenance. It shall be the contractor’s responsibility to ensure that all safety devices, protective features, and emergency systems are fully functional at all times. In the event any safety-related deficiency, defect, or potential hazard is observed, whether or not specifically mentioned in this contract, the contractor shall immediately notify the Engineer-in-Charge in writing and take corrective action within the stipulated time as directed. Failure to comply with safety requirements or to report any such issue shall render the contractor solely and fully responsible for any accident, damage, or loss arising therefrom, and the contractor shall bear all consequences, including penalties, legal liabilities, and costs, without any liability on the part of the department. | 9 | Each Month | - | - |
| 2 | Comprehensive maintenance of complete Fire alarm system addressable type AT ATC including taking down carefully of existing faulty fire alarm detection system/ detectors from existing location ie roof surface, false ceiling surface or above or in between false ceiling and roof surface including removing of false ceiling of any type and refixing the same after repair /replacement of fire detector work and making good the existing distrubed surface to match with the existing surface complete fire alarm system, including minor repairs & control wiring ,testing with SMOKE DETECTER TESTER functionality of all components, cleaning all device in control panels shall be carried out as necessary, testing of fire alarm system, as directed by Engineer-in-Charge/ Users at various locations in GE (AF) Jaisalmer.
MAKE:-Honeywell
NOTE 1 FOR item no 2
.The entire scope of work specified under BOQ/Schedule ‘A’, Item No. 1.00 & 2.00 including repair /replacement of any defective parts of the fire alarm system , shall be executed exclusively through the Original Equipment Manufacturer (OEM) i.e., M/s Siemens PVT LTD & M/s Honeywell International INC or their accredicted/authorized agency.The contractor shall upload/submit a scanned copy of the Intent of Memorandum of Understanding (MoU) executed with the above OEM in Cover No. 1, along with his bid application.Further, the contractor shall also submit the hard copy of the said MoU along with his application before the last date of bid submission. Failure to upload/submit the MoU (both scanned copy and hard copy) shall result in summary rejection of the bid, and Cover No. 2 shall not be opened under any circumstances.However before commencement of work ,the contractor shall mandatorily submit the final and fully executed MOU/Agreement With the OEM.No work Shall be permitted to start without submission of the final MOU
NOTE 2 FOR item no 2
-01. Contractor will be responsible to keep update of fire alarm system, serviceable condition.
02. Contractor Shall Maintain all the Documents and Produce to the Concerned Engineer in charge as and when required /preparation of RAR.
03. Contractor shall give the Demo and training for all duty staffs as when required about the fire alarm System. the below note.
04. Necessary T & P required will be included in quoted rate.
05.Spares required for replacement, shall be measured and paid for seperately under respective items here in after
06.Service engineer to ensure serviceability of fire alarm system as follows:-
(i) Check all connection of control panel
(ii) Check all sensor, detectors & call points.
(iii) test detector and call point in each zone as required.
(iv) Testing of alarm sounders.
(v) Cleaning of control panel and wirings.
NOTE 3 FOR item no 2
1. Attending break down maintenance and replacement of unserviceable spare parts with new ones as required at site complete all as specified and directed by Engineer-in-charge
2. In case of any breakdown, the contractor shall ensure that the fault is rectified and the system is made fully operational within 48 hours from the time of reporting. Immediate site visit by the authorized service personnel within this period shall be mandatory. Failure to comply with the above timeline shall attract a penalty of ₹2,000/- (Rupees Two Thousand only) per day of delay, recoverable from the contractor’s dues, in addition to any other action as deemed fit by the Engineer-in-Charge.
3. The repair and maintenance of Fire Alarm system should be done through OEM or through the authorised service provider of the OEM.
NOTE 3 FOR item no 2
1. Attending break down maintenance and replacement of unserviceable spare parts with new ones as required at site complete all as specified and directed by Engineer-in-charge
2. In case of any breakdown, the contractor shall ensure that the fault is rectified and the system is made fully operational within 48 hours from the time of reporting. Immediate site visit by the authorized service personnel within this period shall be mandatory. Failure to comply with the above timeline shall attract a penalty of ₹2,000/- (Rupees Two Thousand only) per day of delay, recoverable from the contractor’s dues, in addition to any other action as deemed fit by the Engineer-in-Charge.
3. The repair and maintenance of Fire Alarm system should be done through OEM or through the authorised service provider of the OEM.
4.The contractor/OEM shall ensure strict adherence to all applicable safety standards, statutory regulations, and OEM-recommended safety practices during the installation, operation, and maintenance. It shall be the contractor’s responsibility to ensure that all safety devices, protective features, and emergency systems are fully functional at all times. In the event any safety-related deficiency, defect, or potential hazard is observed, whether or not specifically mentioned in this contract, the contractor shall immediately notify the Engineer-in-Charge in writing and take corrective action within the stipulated time as directed. Failure to comply with safety requirements or to report any such issue shall render the contractor solely and fully responsible for any accident, damage, or loss arising therefrom, and the contractor shall bear all consequences, including penalties, legal liabilities, and costs, without any liability on the part of the department. | 9 | Each Month | - | - |
| 3 | Physical inspection & general servicing of complete Fire alarm system conventional type at various locations including taking down carefully of existing faulty fire alarm detection system/ detectors from existing location ie roof surface, false ceiling surface or above or in between false ceiling and roof surface including removing of false ceiling of any type and refixing the same after repair /replacement of fire detector work and making good the existing distrubed surface to match with the existing surface complete fire alarm system, including minor repairs & control wiring ,testing with SMOKE DETECTER TESTER functionality of all components, cleaning all device in control panels shall be carried out as necessary, testing of fire alarm system, as directed by Engineer-in-Charge/ Users at various locations in GE (AF) Jaisalmer.
Service engineer to ensure serviceability of fire alarm system as following location :-
NBC HALL, BASE OPS-TWCC,GDCC,IPSS,,SRE,757 SU,3002 SQN,RPA tech flite ,Signal Sec,dtcom,Afnet Site 1 &2 ,265 SU,CCU hanger,MFU hanger,Storage site Hanger,2212 SQN,2212 tech flt,306 TRU,GCA ,Refueling sec,Auditorium,MRSAM Hanger,UG ATC
NOTE 2 FOR item no 3
-01. Contractor will be responsible to keep update of fire alarm system, serviceable condition.
02. Contractor Shall Maintain all the Documents and Produce to the Concerned Engineer in charge as and when required /preparation of RAR.
03. Contractor shall give the Demo and training for all duty staffs as when required about the fire alarm System. the below note.
04. Necessary T & P required will be included in quoted rate.
05.Spares required for replacement, shall be measured and paid for seperately under respective items here in after
06.Service engineer to ensure serviceability of fire alarm system as follows:-
(i) Check all connection of control panel
(ii) Check all sensor, detectors & call points.
(iii) test detector and call point in each zone as required.
(iv) Testing of alarm sounders.
(v) Cleaning of control panel and wirings.
4.The contractor/OEM shall ensure strict adherence to all applicable safety standards, statutory regulations, and OEM-recommended safety practices during the installation, operation, and maintenance. It shall be the contractor’s responsibility to ensure that all safety devices, protective features, and emergency systems are fully functional at all times. In the event any safety-related deficiency, defect, or potential hazard is observed, whether or not specifically mentioned in this contract, the contractor shall immediately notify the Engineer-in-Charge in writing and take corrective action within the stipulated time as directed. Failure to comply with safety requirements or to report any such issue shall render the contractor solely and fully responsible for any accident, damage, or loss arising therefrom, and the contractor shall bear all consequences, including penalties, legal liabilities, and costs, without any liability on the part of the department. | 9 | Each Month | - | - |
| 4 | Supply and fix in replacement testing and comissioning of fire alarm detector heat and smoke combination conventional type as per existing make and model complete all as specified and directed.
Make:AGNI/GST/Notifier | 45 | EACH | - | - |
| 5 | Supply and fix in replacement testing and comissioning of fire alarm detector heat conventional type as per existing make and model complete all as specified and directed.
Make:AGNI/GST/Notifier | 38 | Each | - | - |
| 6 | Supply, installation, testing, commissioning and replacement of Manual call point, alarm status indicated by LED, 24V DC operation, NC & NO output complete all as specified and directed by Engineer-in-Charge.
Make:AGNI/GST/Notifier | 29 | Each | - | - |
| 7 | Supply and fixing Remote Response Indicator (RI) having visual indication device above/below of false celling suitable for Automatic Fire Detection & Alarm System complete all as specified and directed by Engr-in-Charge.
Make:AGNI/GST/Notifier | 25 | Each | - | - |
| 8 | Supply and fix in repiars, Conventional Type Sounder Cum Strobe with mounting base, continuous normal operation for atleast 50 minutes with sound level 65db- 120db measured at 1.5m with sound output variation +5db complying complete all as specified and directed with the following specifications:-
(a) Power-12/ 24 V DC or 110 /220V AC, 1Ph, AC, 50Hz
(b) Range- As applicable.
(c) visual indication.
Make:AGNI/GST/Notifier | 20 | Each | - | - |
| 9 | Supply & fixing in repair Fire Alarm Sounders/Hooters / Sirens Electronic type horizontal single stage continuous normal operation for atleast 50 minutes with sound level 65 DB to 120 DB measured at 1.5 Mtr with sound output variation of + 5 DB 500 mtrs range complete all as specified and directed by Engineer-in-Charge.
Make:AGNI/GST/Notifier | 2 | Each | - | - |
| 10 | Supply, installation, testing, commissioning and replacement of 2 Zone, Microprocessor based Fire Alarm Control Panel as per IS-15908:2011 standard, Certified for safety standard IEC 62368-1:2018, standby battery backup with built in charging, Fire/Fault status LED indication, SMPS System, keypad for panel operation, System Indication, Standby status indication, Low Battery warning with tone, Zone wise Isolation facility with loop voltage cut off complete all as specified and directed by Engineer-in-Charge.
Make:AGNI/GST/Notifier | 1 | Each | - | - |
stage.html
html • 0.03 MB
tech_bid_open.pdf
tech_eval.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 0.49 MB
8420Tenderdocuments.pdf
Tender Documents • 1.33 MB
BOQ_873016.xls
BOQ • 0.31 MB
8420Tenderletter.pdf
PDF • 0.25 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .