MAINT REPAIR REPLACEMENT REROUTING OF LT ELECTRICAL PANEL AND LT PANEL AND MAINT OF DG SETS PANELS AT VARIOUS LOCATION AND AT SP MARG, TPT COY, 2 SIGNAL COY AND CONNECTING AREA OF AGE E M-III UNDER GE U W S DELHI CANTT-10
2026_MES_794164_1
GE/WS/Token No-55 OF 2026-27
Open Tender
Civil Works
Item Rate
270 days
GE U W S DELHI CANTT-10
Please refer Tender documents.
6 documents required · 6 mandatory
₹500
GE U W S DELHI CANTT-10
₹80,000
Yes
15 Oct 2026
15 Oct 2026
9 Nov 2026
15 Oct 2026
6 Nov 2026
31 Oct 2026
| Sl No | Description | Qty | Unit | Est. Rate | Est. Amount |
|---|---|---|---|---|---|
| 1 | Taking down old unsv LT control panel board of any size of bus bar capacity and deposited to MES store yard, taken on charge in salvage ledger as directed by Engr-in-charge | 7 | EACH JOB | - | - |
| 2 | Supply installation, commissioning and testing LT panel outdoor type made out of 3.15 mm thick CRCA sheet (manufactured through CPRI approved manufacturers), floor mounted duly Powder Coated, dust and vermin proof with front opening arrangement with and incl foundation with PCC 1:2:4 type B1, MS channel base frame etc complete comprising of aluminium bus bar of capacity 500 Amps 4 Nos of strip 415 volts and cabinet for housing MCCBs, metering equipments, all accessories prewire with copper cable of suitable capacity. All MCCBs should be connected with aluminium busbar as per there capacities and comprising of following accessories
Incoming
(i) MCCB TPN, 400 Amps, breaking capacity 36 KA-01 Nos
Outgoing
(i) MCCB TP 200 Amps, breaking capacity 36 KA :- 02No.
(ii) Fully Automatic Star Delta Starter type ML-2 complete set - 02 No,
(iii) Digital type voltmeter (0-500 Volts) -01 No
(iv) Digital type Amp meter 0-100 Amps with CT’s & selector switch - 01 No.
(v) Indicator Lamps(LED type) for motor ON/OFF indication-01 set | 1 | EACH JOB | 100 | ₹100 |
| 3 | Supply installation, commissioning and testing LT panel outdoor type made out of 3.15 mm thick CRCA sheet (manufactured through CPRI approved manufacturers), floor mounted duly Powder Coated, dust and vermin proof with front opening arrangement with and incl foundation with PCC 1:2:4 type B1, MS channel base frame etc complete comprising of aluminium bus bar of capacity 600 Amps 4 Nos of strip 415 volts and cabinet for housing MCCBs, metering equipments, all accessories prewire with copper cable of suitable capacity. All MCCBs should be connected with aluminium busbar as per there capacities and comprising of following accessories
(a) MCCB 4 pole 400 Amp, rupturing capacity of 36 KA (As In-coming) -01 No
(b) MCCB 4 pole 250 Amps, rupturing capacity of 36 KA (As Outgoing)-02 Nos
(c) Fully Automatic Star Delta Starter type ML-3 complete set - 02 No,
(d) Set of Indicating lamp (one set) set of three.
(e) Digital type volt meter (0-500 volts) with selector switch - 01 No.
(f) Digital type Amp meter 0-100 Amps with CT’s & selector switch - 01 No. | 1 | EACH | 22 | ₹22 |
| 4 | Supply installation, commissioning and testing LT panel outdoor type made out of 3.15 mm thick CRCA sheet (manufactured through CPRI approved manufacturers), floor mounted duly Powder Coated, dust and vermin proof with front opening arrangement with and incl foundation with PCC 1:2:4 type B1, MS channel base frame etc complete comprising of aluminium bus bar of capacity 200 Amps 4 Nos of strip 415 volts and cabinet for housing MCCBs, metering equipments, all accessories prewire with copper cable of suitable capacity. All MCCBs should be connected with aluminium busbar as per there capacities and comprising of following accessories
(a) MCCB 4 pole 160 Amp, rupturing capacity of 10 KA (As In-coming) -01 No
(b) MCCB 4 pole 63 Amps, rupturing capacity of 10 KA (As Outgoing)-02 Nos
(c) Fully Automatic Star Delta Starter type ML-1.5 complete set - 02 No,
(d) MCB DP 32 Amps,10 KA-02 Nos
(e) Set of Indicating lamp (one set) set of three.
(f) Digital type volt meter (0-500 volts) with selector switch - 01 No.
(g) Digital type Amp meter 0-100 Amps with CT’s & selector switch - 01 No. | 1 | EACH | 22 | ₹22 |
| 5 | Supply installation, commissioning and testing LT panel board, outdoor type, floor mounted, dust and vermin proof, CPRI approved factory made , fabricated out of 3 mm thick CRCA sheet suitable for accommodate the followings and for 3 phase 415 volts 50 Hz, AC supply,incl foundation with PCC 1:2:4 type B1, MS channel base frame etc complete and bus bar chamber with aluminium bus bar of 800 amp rating for 3 phase and 4 wire system duly insulated with heat shrinkable sleeved as per colour code, supported on epoxy insulators-01 set common earth bus of suitable size at bottom in side panel board with two earth terminals out side panel board, cable alley, cable glands with independent plates at bottom and complete panel board painted with powder coating in siemens grey colour all as approved & comprising as under:-
Incoming
i) MCCB TPN, 650A, , breaking capacity 50 KA-01 Nos
Out Going
(a) MCCB TP, 200A, , breaking capacity 50 KA-03 Nos
(b) Fully Automatic Star Delta Starter type ML-3 complete set - 03 No,
(c) Digital type voltmeter (0-500 Volts) -01 No
(d) Digital type Amp meter 0-100 Amps with CT’s & selector switch - 01 No.
(e) Indicator Lamps(LED type) for motor ON/OFF indication-01 set | 1 | EACH | 22 | ₹22 |
| 6 | Supply and fixing in replacement, installation, testing and commissioning of feeder pillar box ,outdoor type cubical shape,three phase, 4 wire, Al bus bar for phases and neutral made out of CRCA sheet 3.15 mm thick ,factory fabricated , CPRI approved , powder coated ,dust and vermin proof , provn for ventilation , angle iron frame and four legs of 50x50x6mm thick angle iron ,2 ft long grouted on PCC foundation of height not less than 30 cm from the ground level , grouting properly and of suitable size to accommodate the items mentioned below and having separate compartment /chambers for cable gallery busbar ,switch gear etc all as specified and comprising of following including necessary cable connections to the MCCBs, voltmeter, Ammeter and cable lugs etc .
(a) Al bus bar with PVC sleeve suitable for 200 amps for phase & 200 Amp for neutral - 01Set.
(b) Voltmeter,digital type 0- 500 volt,with selector switch - 01 set
(c) Ammeter Digital type 0-100Amps, with selector switch and CT'-1set
(d) Phase indicating lamps LED type ( red , yellow, blue) 01 set
(e) Incoming MCCB 100 Amp 3 pole 25 KA with adjustable thermal and fixed magnetic release -01 No
(f) outgoing MCCB 63 Amp 3 pole 16 KA with adjustable thermal and fixed magnetic release -02No
(g) FASD Starter ML 1.5 FASD with MS sheet enclosure -01 Nos Make-L&T
(h) Analog time switch -01 No
(j) Single phase preventer-01 No
(k) Phase sequence corrector for complete three phase system - 01 Set | 3 | EACH | 23 | ₹69 |
| 7 | Supply,fixing,connecting and testing ON LOAD change over switch,4 pole,415 volt,AC,with SS enclosure,side handle operated including necessary electrical connection of 400 Amps capacity complete all as specified and directed by Engr-in-charge. | 1 | EACH | 24 | ₹24 |
| 8 | Supply and fixing in replacement, installation, testing and commissioning of automatic security ligthing control panel with enclosure, MCB/MCCB incomer, outgoing MCBs, contactors, manual/electronic timer, selector switches, indicating lamps, internal wiring terminal blocks, earthing, labeling all necessary accessories for complete and proper operation , provn for ventilation , angle iron frame and four legs of 50x50x6mm thick angle iron ,2 ft long grouted on PCC foundation of height not less than 30 cm from the ground level ,and taking down the existing from site complete all as specified and directed by Engr-in-Charge.
i) MCB TP , 32A, , breaking capacity 25 KA-01 Nos
ii) Power contactor 32Amps -01 nos
iii) Analog timer -01 | 2 | EACH | 25 | ₹50 |
| 9 | Excavation in trenches not exc 1.5 Mtr wide and not exc 1.5 Mtr deep for pipe line in ordinary soft/loose soil getting out and levelling of bottom surface to required level complete all as specified and directed. | 178.92 | CUM | 26 | ₹4,651.92 |
| 10 | Returning filling in, including spreading, leveling, watering and well ramming in layers not exc 25 cm thick complete all as specified and directed. | 168.92 | CUM | 27 | ₹4,560.84 |
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 0.46 MB
BOQ_890683.xls
BOQ • 0.33 MB
tender.pdf
Tender Documents • 0.77 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .