Loading…
India Infra Updates on WhatsApp
Join the Tenderkart WhatsApp channel for India Tender Updates
Loading…
Tender ID
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹34.8 LAccepted-AOC EAST DIGHI TANK OLD LIC COMPOUND GAYA BIHAR 823001 | GAYA | BIHAR | 823001 | L1 | Accepted-AOC MS Vinay Kumar is lowest and accepted | |
| 2 | L2₹35.0 L+₹23,440 (0.67%)Rejected-Finance 30 INDUSTRIAL AREA KOKAR RANCHI 834004 JHARKHAND | RANCHI | JHARKHAND | 834004 | L2 | Rejected-Finance Not Lowest | |
| 3 | L3₹37.2 L+₹2.4 L (6.86%)Rejected-Finance | L3 | Rejected-Finance Not Lowest | |
| 4 | L4₹40.6 L+₹5.8 L (16.7%)Rejected-Finance | L4 | Rejected-Finance Not Lowest | |
| 5 | L5₹42.9 L+₹8.1 L (23.3%)Rejected-Finance | L5 | Rejected-Finance Not Lowest |
Tender Value
₹40.7 L
EMD Value
₹81,400
Closing Date
21 Jun 2023, 6:00 pmClosed
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
Sh Y K Gour
HQ CWE Ranchi, MES, Dipatoli Cantt
PROVN OF HT RING MAIN UNITS FOR NAMKUM AREA UNDER GE RANCHI
2023_MES_596991_1
80599/1473/E8
Open Tender
Electrical and Maintenance Works
Item Rate
180 days
GE Ranchi
Please refer Tender documents.
6 documents required · 6 mandatory
₹500
GE Ranchi
₹81,400
Yes
HQ CWE Ranchi
18 Jul 2023
23 May 2023
28 Jun 2023
23 May 2023
21 Jun 2023
7 Jun 2023
23 May 2023 - 29 May 2023
29 May 2023
Amount
Supply, installation, connection, testing and commissioning of outdoor type 11 KV SF6 insulated, 630 Amps rupturing capacity upto 250 MVA, extensible outdoor fixed type (IP 54), RMU (Ring maint unit). manual operated vacuum circuit Breaker having digital type overload and earthfault protection, ammeter, , inside robotically welded stainless steel 304 (Non Ferrite Non Magnetic Grade) tank having minimum thickness 2.5+0.5 mm having IP 67 Degree of protection RMU should be provided with internal busbars, as well as earthing. Busbars should be of copper, padlock provisions & complete with all accessories. The RMU shall be type tested for internal arc test of not less than 21KA/1 sec as per IEC62271-200. RMU shall be equipped with site replaceable bushing. The earthing busbar shall be provided inside each cable compartment for solid earthing of cable shields. The outer enclosure main door should cover entire part of the switchgear including front cover and cable doors for providing complete IP 54 protection complete all as directed. Note:- (i) RMU will be installed on suitable PCC foundation as per manufactures drawing. (ii) Cost of PCC /Earth work for frundation deemed to be included in the rate quoted complete all as directed.
The unit shall include the following with all necessary standard fittings as required at site. (a) Vaccum circuite Breaker module should consist of following accessories: (i) 630 Amps Vacuum Breaker module for making and breaking of fault current alongwith Earth Switch of full making capacity. VCB should be capable to bear 40 dead short circuit operation. (ii) Short time current - not less than 21 KA 1 Sec (iii) Making Capacity 50 KA (iv) Auxiliary contacts - 1NO + 1NC (v) Power frequency withstand voltage = 28 KV (vi) Impulse withstand voltage - 75Kv (vii) Nominal operating gas pressure - 1.3 (minimum) Bar abs. (viii) front cover mechanism - IP 2X (xi) Cable box for front termination of the cable suitable upto 3 core 95 Sqmm, 11 KV XLPE cable (xii) Right angle boots (push on type) (xiii) Self Powered Microprocessor based Relay (3 O/C & E/F) with standard settings (xiv) Digital ampear meter with RYB (xv) Suitable site replaceable Cable bushings (xvi) Arc proof cable covers with self interlocking mechanism between doors, earth switch, disconnector & VCB (xvii) Capacitive voltage indication fixed type system (xviii) Mechanical indications for breaker ON, OFF, Earth, TRIP, Spring Charged-Discharged.
(b)(i) Microprocessor based IDMT (50, 50N, 51, 51N) relayfor overcurrent, short circuit and earth fault protection (ii) Each RYB phase indications for 1 incoming (Load Breaking Switch) and 2 out going (Compact fixed type VCB). (iii) 1 Cable support bus bars, standard for 3 way unit. (iv) 1 Set Bushings for external busbar connection along with Busbar cover & Sleeved busbars for coupling.
(c) Necessary interlocking arrangement for safety and operations (d) One No. Operation Handle for Manual Operation (e) One No. Manometer. (f) Safety Interlocks Shall be provided as per relevant IEC/IS Standards and Manufacturers directions. (g) Above switchgear shall confirm to all relevant IEC/IS Standards. (h) Manual operation of Vacuum Circuit Breaker. (i) Coupling of RMU and Metering module should be with the help of Bolted type arrangement, so that the coupling at site shall be easy. Plug-in type bushing shall not be acceptable. (j) All cable bushing should be replaceable type. (k) Module should be accommodated as per manufacture's design. (l)RMU cable box shall be front accessible type to have easy access to protection and metering CTs. Vacuum Interupter should be of same make. Cable box should be arc proof with bolted door and interlocked with respective earthing switches. Doors should be removable for the ease access to terminate cables. Note:- (i) The contractor will submit the NABL Accredited lab test reports of the RMU's in original and the same shall be produced well before claiming RAR payment of the RMU. (ii) Pre-despatch inspection shall be carried out by Rep of Accepting Officer. All arrangement for the same shall be arranged by the contractor & shall be considered within quoted rates. Make :- SCHEIDER/ SIEMENS/ ABB /CG/C&S) (iii) Design, drawing of RMU to be submitted by the contractor for approval from the Garrison Engineer before manufacturing.
Supply, installation, connection, testing and commissioning of outdoor type 11 KV SF6 insulated, 630 Amps rupturing capacity upto 250 MVA, extensible outdoor fixed type (IP54), RMU (Ring maint unit). manual operated vacuum circuit Breaker having digital type overload and earthfault protection, ammeter, inside robotically welded stainless steel 304 (Non Ferrite Non Magnetic Grade) tank having minimum thickness 2.5+0.5 mm having IP 67 Degree of protection RMU should be provided with internal busbars, as well as earthing. Busbars should be of copper, padlock provisions & complete with all accessories. The RMU shall be type tested for internal arc test of not less than 21KA/1 sec as per IEC62271-200. RMU shall be equipped with site replaceable bushing. The earthing busbar shall be provided inside each cable compartment for solid earthing of cable shields. The outer enclosure main door should cover entire part of the switchgear including front cover and cable doors for providing complete IP 54 protection complete all as directed. Note:- (i) RMU will be installed on suitable PCC foundation as per manufactures drawing. (ii) Cost of PCC /Earth work for frundation deemed to be included in the rate quoted complete all as directed.
The unit shall include the following with all necessary standard fittings as required at site. (a) Vaccum circuite Breaker module should consist of following accessories: (i) 630 Amps Vacuum Breaker module for making and breaking of fault current alongwith Earth Switch of full making capacity. VCB should be capable to bear 40 dead short circuit operation. (ii) Short time current - not less than 21 KA 1 Sec (iii) Making Capacity 50 KA (iv) Auxiliary contacts - 1NO + 1NC (v) Power frequency withstand voltage = 28 KV (vi) Impulse withstand voltage - 75Kv (vii) Nominal operating gas pressure - 1.3 (minimum) Bar abs. (viii) front cover mechanism - IP 2X (xi) Cable box for front termination of the cable suitable upto 3 core 95 Sqmm, 11 KV XLPE cable (xii) Right angle boots (push on type) (xiii) Self Powered Microprocessor based Relay (3 O/C & E/F) with standard settings (xiv) Digital ampear meter with RYB (xv) Suitable site replaceable Cable bushings (xvi) Arc proof cable covers with self interlocking mechanism between doors, earth switch, disconnector & VCB (xvii) Capacitive voltage indication fixed type system (xviii) Mechanical indications for breaker ON, OFF, Earth, TRIP, Spring Charged-Discharged.
(b)(i)-Microprocessor based IDMT (50, 50N, 51, 51N) relayfor overcurrent, short circuit and earth fault protection. (ii) - Each RYB phase indications for 1 incoming (Load Breaking Switch) and 1 out going (Compact fixed type VCB). (iii) - 1 Cable support bus bars, standard for 2 way unit. (iv) - 1 Set Bushings for external busbar connection along with Busbar cover & Sleeved busbars for coupling.
(c) Necessary interlocking arrangement for safety and operations (d) One No. Operation Handle for Manual Operation (e) One No. Manometer. (f) Safety Interlocks Shall be provided as per relevant IEC/IS Standards and Manufacturers directions. (g) Above switchgear shall confirm to all relevant IEC/IS Standards. (h) Manual operation of Vacuum Circuit Breaker. (i) Coupling of RMU and Metering module should be with the help of Bolted type arrangement, so that the coupling at site shall be easy. Plug-in type bushing shall not be acceptable. (j) All cable bushing should be replaceable type. (k) Module should be accommodated as per manufacture's design. (l)RMU cable box shall be front accessible type to have easy access to protection and metering CTs. Vacuum Interupter should be of same make. Cable box should be arc proof with bolted door and interlocked with respective earthing switches. Doors should be removable for the ease access to terminate cables. Note:- (i) The contractor will submit the NABL Accredited lab test reports of the RMU's in original and the same shall be produced well before claiming RAR payment of the RMU. (ii) Pre-despatch inspection shall be carried out by Rep of Accepting Officer. All arrangement for the same shall be arranged by the contractor & shall be considered within quoted rates. Make :- SCHEIDER/ SIEMENS/ ABB /CG/C&S) (iii) Design, drawing of RMU to be submitted by the contractor for approval from the Garrison Engineer before manufacturing.
Earthing complete including taking down of old one with galvanised steel earth plate electrode of size 60cms x 60cms x 6.0 mm thick as per IS 3043 of 1987 buried directly in to the ground ( earthpit not less than 2.25 m deep below the ground level) with top edge of the plate not less than 1.5 meters below normal ground level, connected to the galvanised earth lead by means of bolts , nuts check nuts and washers of galnanised iron or steel using GI strip 32 x 6 mm as earthing lead as shown in electric plate No-3 of SSR- Part-1 connected to earth strip all as specifed or indicated including testing on completion and necessary excavation and earth work in soft/loose soil, returning filling, disposal of surplus soil, earth pit in PCC 1 :3:6 type C-1 using 20 mm graded stone aggregate, pit, funnel, 15 mm diia meduim grade watering pipe, 40 mm dia GI light grade earth lead protection pipe, CI frame and cover , wire copper lugs etc mesh, charcoal and common salt in alternate layer complete all as directed .
Supply laying testing and commissioning in XLPE insulated screen, PVC badded galvanized steel strip on wire armoured electric, power cables heavy duty with aluminium conductor 11KV/6.6 KV, earthed system cross sectional area 95 Sq mm X 3 core laid in trenches or passing through pipe or fixed to poles complete all as directed.
S & F Cable joint kit for 11 KV(earthed) grade cable for indoor termination heat shrink type joint complete with jointing material and acessories suitable for 03 core XLPE armored aluminium conductor cable of size 95 sq mm complete all as directed
S & FCable joint kit for 11 KV(earthed) grade cable for outdoor termination heat shrink type joint complete with jointing material and acessories suitable for 03 core XLPE armored aluminium conductor cable of size 95 sq mm complete all as directed
Excavation in trenches n. exc 1.5 m wide & n. exc 1.5 m in depth for laying under ground cables/erection of pole and getting out in hard/dense soil, complete all as directed
Returning, filling in including spreading, leveling, watering and well ramming in layers not exceeding 25cm thick complete all as directed
Removal of excavated surplus material (Soil) to a distance n.exc 50 mtr and depositing where directed at a level n.exc 1.5mtr above the starting point complete all as directed
M& L for Sand filling in cable trenches for cable protection with clean dry sand unwashed including gently put in trences complete all as directed
.Supplying and laying un-reinforced precast concrete cable cover class HV type 1 flat size300mmX180mmX40mm complete all as directed.
Raj Construction
Associated Engineers
Roy and Sons Infrastructers
M/S Akash Enterprises
arics infrastructure
Commercial Electric Co.
EASTERN TRADE AGENCY
stage.html
html • 0.06 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .