GARRISON ENGINEER
GE AF LEH PIN 194101 C/O 56 APO
PROVN OF MOBILE EARTHPITS FOR OP LOCATIONS AND FALSE CEILING AND CERTAIN ELECTRICAL FITTINGS IN MT OFFICE AT AF STN LEH
2021_MES_409222_2
GE AF-29/2020-21
Open Tender
Electrical and Maintenance Works
Item Rate
180 days
GE AF LEH
Please refer Tender documents.
8 documents required · 8 mandatory
₹500
GE AF LEH
₹6,000
Yes
10 Apr 2021
8 Feb 2021
27 Feb 2021
8 Feb 2021
25 Feb 2021
12 Feb 2021
Amount
Portable (mobile) Macronite earthing system complete with UL464 approved copper bonded earth rod 17.2mm dia 4.5 mtrs long electrode (1.5 mtr each brazed with 3mm thick copper plates of 250mm dia 03 Nos) buried in chemical mixture in appropriate quantity as specified by the manufacturer filled in a container of dia 300mm and 900 mm high made out of 3.15mm MS sheet. The copper plates to be brazed with copper rods and the complete earthing system as given in the digram enclosed. The macronite compound is to be used as per manufacturer's recommendation to obtain 1.0 ohms earth resistance value. Necessary ingredients and other items to be used as per manufacturer design and obtain desired value complete all as specified and directed. Note : (i) Payment shall be made only after satisfactory testing to the entire satisfaction of GE. The contractor has to make alternate earthing in case test result not found satisfactory without any extra cost to the Govt.and the quoted rate shall be deemed to include this provision. (ii)The contractor shall submit 1 year guarantee for earth resistance below 1 ohms and earth neutral voltage less than 1 volts. Make of Chemical - Macronite or equivalent as approved by GE.
Point wiring for one light/Fan/bell point controlled by one switch one way in & including PVC conduit or casing and capping as per site requirement using FRLS PVC unsheathed multistrand copper conductor cable 1.5 sqmm single core including 3 mm thick plastic laminated sheet cover over PVC / wooden Box and including earth continuity insulated PVC unsheathed(green colour) 1.5 sqmm copper earth wire connected to common earth dolly and making good the disturbed surfaces to match with existing complete all as specified and as directed. Note : (a) wiring shall be done by using proper colour coding. Make of wire : Polycab/Finolex/Havells
Switch piano, flush type 5 Amps One Way 230 volts complete all as specified and as directed.
ENDURA Slim Pro Plus PANEL 36W LED 5700K LED fitting with LED prisumatic optival modular luminaire suitable for Reccesses mounting complete all as specified and as directed. with HF electronic driver. Make: Havells / Bajaj/Crompton
Sheet metal enclosure double door for DB's TPN 4 way 415 V having 200 Amp rated busbar complete all as specified and directed.
MCB 63 Amp TPN/FP fixed type thermal magnetic type 415 volts 50 Hz 25 KA, complete with all accessories as required on site & as directed.
MCB 32 Amp TPN/FP fixed type thermal magnetic type 415 volts 50 Hz 25 KA, complete with all accessories as required on site & as directed.
Sub main wiring complete with four run (for 3x phase & neutral) of 4 sqmm FRLS PVC sheathed copper conductor cable along with one run earth wire 4 sqmm FRLS PVC copper conductor drawn through in & including PVC casing caping or PVC conduit as required on site complete all as directed. Note: Copper conductor 4 run and one run of copper earth wire alongwith casing caping shall be measured as one length. Make : Polycab/Finolex/Havells
Sheet metal enclosure TPN with three pin and earth plug and socket 15 amp complete with one triple pole MCB 16 to 32 Amps for controlling the socket complete all as specified and directed.
Earthing complete with galvanised steel earth plate electrode 60x60cmx6mm thick, buried directly in ground (earth pit not less than 2.25meters deep below ground level) with top edge of the plate not less than 1.5meters below normal ground level, connected to galvanised earth lead wire 4.0mm dia by by means of bolts, nuts, check nuts and washers of galvanised iron or steel all as shown in electrical plate No 5 connected to earth test point all as specified and directed. Note: On testing after completion of earthing, if earth resistance of earthing is not found satisfactory, it will be redone by the contractor on his risk and cost.
M/S LIBE & CO
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .