Loading…
Loading…
Tender Value
₹2.4 Cr
EMD Value
₹2.7 L
Closing Date
16 Jan 2026, 12:00 pmClosed
No
No
Single Packet System
Normal Tender
No
Not Applicable
Lowest to Highest
60 days
Expenditure
Capital (Works)
Above/Below/Par
TENDER
15 conditions · 4 needing a document upload
The tenderer must have minimum average annual contractual turnover of V/N or 'V' whichever is less; where V= Advertised value of the tender in crores of Rupees N= Number of years prescribed for completion of work for which bids have been invited. The average annual contractual turnover shall be calculated as an average of "total contractual payments" in the previous three financial years, as per the audited balance sheet. However, in case balance sheet of the previous year is yet to be prepared/ audited, the audited balance sheet of the fourth previous year shall be considered for calculating average annual contractual turnover. The tenderers shall submit requisite information as per Annexure-VIB, along with copies of Audited Balance Sheets duly certified by the Chartered Accountant/ Certificate from Chartered Accountant duly supported by Audited Balance Sheet. The balance sheet and all other financial documents attested /certified by CA's to substantiate fulfilment of financial Eligibility Criteria should be with UDIN, failing which the offer is likely to be rejected without any further reference.
Must have valid Electrical Contractors license issued by Central Govt./any State Govt. valid throughout the contract period.
Must have valid Electrical Supervisor's certificate issued by Central Govt./any State Govt. valid throughout the contract period. Name of the supervisor should be endorsed in Electrical contractor License. If the firm deploys supervisor other than endorsed in the contractor license valid employment documents should be uploaded.
The tenderer must have successfully completed or substantially completed any one of the following categories of work(s) during last 07 (seven) years, ending last day of month previous to the one in which tender is invited:(i) Three similar works each costing not less than the amount equal to 30% of advertised value of the tender, or (ii) Two similar works each costing not less than the amount equal to 40% of advertised value of the tender, or (iii) One similar work costing not less than the amount equal to 60% of advertised value of the tender. Similar nature of work for this work is defined as "Supply, installation, testing and commissioning of HT panels/LT panels, cable laying, wiring/rewiring of any building/office in Central Government or State Government or Public Sector Understandings ( also called Public Sector Enterprise)." for participating in the works tender proposed above.
62 conditions · 6 needing a document upload
GST implemented from 1st july'2017. All the bidder should attach GST registration certificate, Tenderer has to fulfill GST Compliance as per Govt. norms. GST will levied as per instruction circulated time to time.
Tenderers are required to upload their Permanent Account Number (PAN) card.
Declaration of proprietorship/partnership firm and necessary document should be submitted along with tender.
Mandate form should be uploaded as per attached format.
Employment/Partnership etc. of Retired Railway Employees: (a) Should a tenderer i) be a retired Engineer of the gazetted rank or any other gazetted officer working before his retirement, whether in the executive or administrative capacity or whether holding a pensionable post or not, in the Engineering or any other department of any of the railways owned and administered by the President of India for the time being, OR ii) being partnership firm / joint venture (JV) / registered society / registered trust etc have as one of its partners a retired Engineer of the gazetted rank or any other gazetted officer working before his retirement, OR iii) being an incorporated company have any such retired Engineer of the gazetted rank or any other gazetted officer working before his retirement as one of its directors AND in case where such Engineer or officer had not retired from government service at least 1 year prior to the date of submission of the tender THEN the tenderer will give full information as to the date of retirement of such Engineer or gazetted officer from the said service and as to whether permission for taking such contract, or if the Contractor be a partnership firm or an incorporated company, to become a partner or director as the case may be, has been obtained by the tenderer or the Engineer or officer, as the case may be from the President of India or any officer, duly authorized by him in this behalf, shall be clearly stated in writing at the time of submitting the tender. b) In case, upon successful award of contract, should a tenderer depute for execution of the works under or to deal matters related with this contract, any retired Engineer of gazette rank or retired gazetted officer working before his retirement in the Engineering or any other department of any of the railways owned and administered by the President of India for the time being, and now in his employment, then the tenderer will ensure that retired Engineer or retired gazetted officer had retired from government service at least 1 year prior to the date of his employment with tenderer and in case he had retired from service within a year then he possesses the requisite permission from the President of India or any officer, duly authorized by him in this behalf, to get associated with the tenderer. c) Should a tenderer or Contractor being an individual, have member(s) of his family or in the case of partnership firm/ company / joint venture (JV) / registered society / registered trust etc. one or more of his partner(s)/shareholder(s) or member(s) of the family of partner(s)/shareholder(s) having share of more than 1% in the tendering entity employed in gazetted capacity in the Engineering or any other department of the railway, then the tenderer at the time of submission of tender, will inform the authority inviting tenders the details of such persons. Note:-If information as required as per 16.a), b), c) above has not been furnished, contract is liable to be dealt in accordance with provision of clause 62 of Standard General Condition of contract. Format for declaration in this regard is attached with the tender document.
Work experience certificate from private individual shall not be considered. However, in addition to work experience certificates issued by any Govt. Organisation, work experience certificate issued by Public listed company having average annual turnover of Rs 500 crore and above in last 3 financial years excluding the current financial year, listed on National Stock Exchange or Bombay Stock Exchange, incorporated/registered at least 5 years prior to the date of closing of tender, shall also be considered provided the work experience certificate has been issued by a person authorized by the Public listed company to issue such certificates.
In case tenderer submits work experience certificate issued by public listed company, the tenderer shall also submit along with work experience certificate, the relevant copy of work order, bill of quantities, bill wise details of payment received duly certified by Chartered Accountant, TDS certificates for all payments received and copy of final/last bill paid by company in support of above work experience certificate.
The bidder shall submit duly filled Tender Form(Annexure-I) of GCC-2022 updated upto latest correction slip..
Please enter the percentage of local content in the material being offered. Please enter 0 for fully imported items, and 100 for fully indigenous items. The definition and calculation of local content shall be in accordance with the Make in India policy as incorporated in the tender conditions.
Inspection of material is to be done by RITES. Inspection charges of RITES are to be borne by the contractor where necessary as per extant rule (Where the value of purchase order exceeds Rs.5.0 Lakhs).
Guarantee period for the overall work will be 12 (Twelve) months from the date of completion of the work. Any defects, if arises during the guarantee period contractor will be responsible to rectify or replace as the case may be at the discretion of the Railway Administration. Security deposit will be refunded/ released after successful completion of the guarantee period. Also, contractor has to ensure proper functioning of the items covered under specific warranty/guarantee as mentioned in Tender Documents during that period (Warranty/guarantee period will be calculated from the date of commissioning).
Online Payment:- The detailed payment transaction particulars should be attached as attachment.
If the tenderers deliberately gives/give wrong information in his/their tender or creates/create circumstances for the acceptance of his/their tender, the Railway reserves the right to reject such tender at any stage.
The tenderers shall keep the offer open for a minimum period as mentioned in NIT from the date of opening of the tender, within which period the tenderers can not withdraw their offer, subject to the period being extended further if required, by mutual agreement from time to time. Any intervention of the above condition will make the tenderer liable for forfeiture of his security deposit for due performance of the foregoing stipulation.
It shall not be obligatory on the said authority to accept the lowest tender or any other tender, and tenderer(s) shall neither demand any explanation for the cause of rejection of his/ their tender nor the Railway to assign reasons for declining to consider or reject any particular tender or tenders.
If any partner(s) of a partnership firm expires after the submission of its tender or after the acceptance of its tender, the Railway shall deem such tender as cancelled/contract as terminated under clause 61 of the Standard General Conditions of Contract, unless the firm retains its character as per partnership agreement. If a sole proprietor expires after the submission of tender or after the acceptance of tender, the Railway shall deem such tender as cancelled / contract as terminated under clause 61 of the Standard General Conditions of Contract.
Bid Security: (1) (a) The tenderer shall be required to submit the Bid Security with the tender for the due performance with the stipulation to keep the offer open till such date as specified in the tender, under the conditions of tender. The Bid Security shall be as under: Value of the Work and Bid Security : For works estimated to cost up to 1 crore, 2% of the estimated cost of the work. For works estimated to cost more than 1 crore, 2 lakh plus ½% (half percent) of the excess of the estimated cost of work beyond 1 crore subject to a maximum of 1 crore. Note: (i) The Bid Security shall be rounded off to the nearest 100. This Bid Security shall be applicable for all modes of tendering. (ii) Any firm recognized by Department of Industrial Policy and Promotion (DIPP) as 'Startups' shall be exempted from payment of Bid Security detailed above. (iii) Labour Cooperative Societies shall submit only 50% of above Bid Security detailed above. (b) It shall be understood that the tender documents have been issued to the tenderer and the tenderer is permitted to tender in consideration of stipulation on his part, that after submitting his tender he will not resile from his offer or modify the terms and conditions thereof in a manner not acceptable to the Engineer. Should the tenderer fail to observe or comply with the said stipulation, the aforesaid amount shall be liable to be forfeited to the Railway. (c) If his tender is accepted, this Bid Security mentioned in sub para (a) above will be retained as part security for the due and faithful fulfillment of the contract in terms of Clause 16 of the Standard General Conditions of Contract. The Bid Security of other Tenderers shall, save as herein before provided, be returned to them, but the Railway shall not be responsible for any loss or depreciation that may happen thereto while in their possession, nor be liable to pay interest thereon.
The Bid Security shall be deposited either in cash through e- payment gateway or submitted as Bank Guarantee bond from a scheduled commercial bank of India or as mentioned in tender documents. The Bank Guarantee bond shall be as per Annexure- VIA and shall be valid for a period of 90days beyond the bid validity period. In case, submission of Bid Security in the form of Bank Guarantee, following shall be ensured: i. A scanned copy of the Bank Guarantee shall be uploaded on e-Procurement Portal (IREPS) while applying to the tender. ii. The original Bank Guarantee should be delivered in person to the official nominated as indicated in the tender document before closing date for submission of bids (Le. excluding the last date of submission of bids) . iii. Non submission of scanned copy of Bank Guarantee with the bid on e-tendering portal (IREPS) and/or non submission of original Bank Guarantee within the specified period shall lead to summary rejection of bid. iv. The Tender Security shall remain valid for a period of 90 days beyond the validity period for the Tender. v. The details of the BG, physically submitted should match with the details available in the scanned copy and the data entered during bid submission time, failing which the bid will be rejected vi. The Bank Guarantee shall be placed in an envelope, which shall be sealed. The envelope shall clearly bear the identification "Bid for the ***** Project" and shall clearly indicate the name and address of the Bidder. In addition, the Bid Due Date should be indicated on the right hand top corner of the envelope. vii. The envelope shall be addressed to the officer and address as mentioned in the tender document. viii. If the envelope is not sealed and marked as instructed above, the Railway assumes no responsibility for the misplacement or premature opening of the contents of the Bid submitted and consequent losses, if any, suffered by the Bidder.
The successful bidder shall submit the Performance Guarantee (PG) in any of the following forms, amounting to 5% of the original contract value :- (i) A deposit of Cash; (ii) Irrevocable Bank Guarantee; (iii)Government Securities including State Loan Bonds at 5% below the market value; (iv) Pay Orders and Demand Drafts tendered by any Scheduled Commercial Bank of India; (v) Guarantee Bonds executed or Deposits Receipts tendered by any Scheduled Commercial Bank of India; (vi) Deposit in the Post Office Saving Bank; (vii) Deposit in the National Savings Certificates; (viii) Twelve years National Defence Certificates; (ix) Ten years Defence Deposits; (x) National Defence Bonds and (xi) Unit Trust Certificates at 5% below market value or at the face value whichever is less. Also, FDR in favour of FA&CAO (free from any encumbrance) may be accepted.
Performance Guarantee : The successful bidder shall have to submit a Performance Guarantee (PG) within 21 (Twenty one) days from the date of issue of Letter of Acceptance (LOA). Extension of time for submission of PG beyond 21 (Twenty one) days and upto 60 days from the date of issue of LOA may be given by the Authority who is competent to sign the contract agreement. However, a penal interest of 12% per annum shall be charged for the delay beyond 21(Twenty one) days, i.e. from 22ndday after the date of issue of LOA. Further, if the 60thday happens to be a declared holiday in the concerned office of the Railway, submission of PG can be accepted on the next working day. In all other cases, if the Contractor fails to submit the requisite PG even after 60 days from the date of issue of LOA, the contract is liable to be terminated. In case contract is terminated railway shall be entitled to forfeit Bid Security and other dues payable to the contractor against that particular contract, subject to maximum of PG amount. In case a tenderer has not submitted Bid Security on the strength of their registration as a Startup recognized by Department of Industrial Policy and Promotion (DIPP) under Ministry of Commerce and Industry, DIPP shall be informed to this effect. The failed Contractor shall be debarred from participating in re-tender for that work. However the clause may also applicable as amended time to time.
The Performance Guarantee shall be submitted by the successful bidder after the Letter of Acceptance (LOA) has been issued, but before signing of the contract agreement. This P.G. shall be initially valid upto the stipulated date of completion plus 60 days beyond that. In case, the time for completion of work gets extended, the Contractor shall get the validity of P.G. extended to cover such extended time for completion of work plus 60 days.
The value of PG to be submitted by the Contractor is based on original contract value and shall not change due to subsequent variation(s) in the original contract value.
The Performance Guarantee (PG) shall be released after physical completion of the work based on 'Completion Certificate' issued by the competent authority stating that the Contractor has completed the work in all respects satisfactorily. The Security Deposit shall, however, be released only after expiry of the maintenance period and after passing the final bill based on No Claim Certificate from the contractor.
Whenever the contract is rescinded, the Security Deposit shall be forfeited and the Performance Guarantee shall be encashed. The balance work shall begot done independently without risk cost of the failed contractor. The failed contractor shall be debarred from participating in the tender for executing the balance work. If the failed contractor is a JV or a Partnership firm,then every member/partner of such a firm shall be debarred from participating in the tender for the balance work in his/her individual capacity or as a partner of any other JV/partnership firm.
(i) Unless otherwise specified in the special conditions of the contract, the accepted variation in quantity of each individual item of the contract would be upto 25% of the quantity originally contracted, except in case of foundation work (in which no variation limit shall apply). However, the rates for the increased quantities shall be as per sub- para (iii) below. (ii) The Contractor shall be bound to carry out the work at the agreed rates and shall not be entitled to any claim or any compensation whatsoever upto the limit of 25% variation in quantity of individual item of works. (iii) In case an increase in quantity of an individual item by more than 25% of the agreement quantity is considered unavoidable, then same shall be executed at following rates a. Quantities operated in excess of 125% but upto 140% of the agreement quantity of the concerned item, shall be paid at 98% of the rate awarded for that item in that particular tender; b. Quantities operated in excess of 140% but upto 150% of the agreement quantity of the concerned item shall be paid at 96% of the rate awarded for that item in that particular tender; c. Variation in quantities of individual items beyond 150% will be avoided and would be permitted only in exceptional unavoidable circumstances and shall be paid at 96% of the rate awarded for that item in that particular tender. d. Variation to quantities of Minor Value Item: The limit for varying quantities for minor value items shall be 100% (as against 25% prescribed for other items). A minor value item for this purpose is defined as an item whose original agreement value is less than 1 % of the total original contract value. d.(i) Quantities operated upto and including 100% of the agreement quantity of the concerned minor value item, shall be paid at the rate awarded for that item in that particular tender; d.(ii) Quantities operated in excess of 100% but upto 200% of the agreement quantity of the concerned minor value item, shall be paid at 98% of the rate awarded for that item in that particular tender; d.(iii) Variation in quantities of individual minor value item beyond 200% will be avoided and would be permitted only in exceptional unavoidable circumstances and shall be paid at 96% of the rate awarded for that item in that particular tender. (iv) In case of earthwork items, the variation limit of 25% shall apply to the gross quantity of earthwork items and variation in the quantities of individual classifications of soil shall not be subject to this limit. (v) As far as Standard Schedule of Rates (SSOR) items are concerned, the variation limit of 25% would apply to the value of SSOR schedule(s) as a whole and not on individual SSOR items. However, in case of Non Standard Schedule of Rates (SSOR) items, the limit of 25% would apply on GCC April 2022 65 the individual items irrespective of the manner of quoting the rate (single percentage rate or individual item rate).
For settlements of disputes Arbitration provision of relevant clauses of S.E.Railway Standard General Conditions of contract of 2022 with up to date correction slip will be followed. Tenderer should comply with all the provisions with respect to labour given in this tender document, IR Standard General Condition Of Contract 2022 updated with correction slips Issued up to date, relevant statues of government w.r.t labour laws.
The Railway reserves the right of not to invite tenders for any of Railway work or works or to invite open or limited tenders and when tenders are called to accept a tender in whole or in part or reject any tender or all tenders without assigning reasons for any such action.
Before submitting a tender, the tenderer will be deemed to have satisfied himself by actual inspection of the site and locality of the works, that all conditions liable to be encountered during the execution of the works are taken into account and that the rates he enters in the tender forms are adequate and all inclusive to accord with the provisions in Clause-37 of the Standard General Conditions of Contract for the completion of works to the entire satisfaction of the Engineer.
Tenderers will examine the various provisions of The Central Goods and Services Tax Act, 2017(CGST)/ Integrated Goods and Services Tax Act, 2017(IGST)/ Union Territory Goods and Services Tax Act, 2017(UTGST)/ respective state's State Goods and Services Tax Act (SGST) also, as notified by Central/State Govt.& as amended from time to time and applicable taxes before bidding. Tenderers will ensure that full benefit of Input Tax Credit (ITC) likely to be availed by them is duly considered while quoting rates.
The successful tenderer who is liable to be registered under CGST/IGST/UTGST/SGST Act shall submit GSTIN along with other details required under CGST/IGST/UTGST/SGST Act to railway immediately after the award of contract, without which no payment shall be released to the Contractor. The Contractor shall be responsible for deposition of applicable GST to the concerned authority.
In case the successful tenderer is not liable to be registered under CGST/IGST/UTGST/ SGST Act, the railway shall deduct the applicable GST from his/their bills under reverse charge mechanism (RCM) and deposit the same to the concerned authority.
INSPECTION AND TESTING: All materials will be subjected to inspection and test by RITES/authorized railway representative at the Manufacturer's workshop/site before dispatch and no materials shall be dispatched from the Manufacturer's workshop/ site until these are inspected and or approved. The materials may also be inspected by the purchaser or his representative or any organization recommended by the purchaser again at the contractor's depot/works site. The purchaser or his representatives or any organization recommended by the purchaser shall have the right to be present during all stages of manufacturing and shall be offered, free of charge all reasonable facilities for inspection and testing so as to satisfy himself/ themselves that the materials are in accordance with specifications, approved drawings and designs. Any unreasonable delay in inspection will be a reasonable ground for extension of time for completion of work. Not less than 15(fifteen) days notice in writing shall be given by the contractor to the purchaser in order that the purchaser's Engineer may be present if they (i.e.purchaser) so desire, carrying out the inspection and test.
The firm should ensure that minimum wages is to be paid to their employee as per the extant Government rule. It will befirm's responsibility to resolve the issues if any dispute arises regarding non payment of minimum wages to their employees and Railway will not be responsible for this.
The tenderers in case of other than Company/Proprietary firm, Annexure -V(A) shall also be submitted by the each member of a Partnership Firm / Joint Venture (JV) / Hindu Undivided Family (HUF) / Limited Liability Partnership (LLP) etc. as the case may be. Non submission of above certificate by the bidder shall result in summarily rejection of his/their bid. It shall be mandatorily incumbent upon the tenderer to identify, state and submit the supporting documents duly self-attested/digitally signed by which they/he is qualifying the Qualifying Criteria mentioned in the Tender Document.
The Railway reserves the right to verify all statements, information and documents submitted by the bidder in his tender offer, and the bidder shall, when so required by the Railway, make available all such information, evidence and documents as may be necessary for such verification. Any such verification or lack of such verification, by the Railway shall not relieve the bidder of its obligations or liabilities hereunder nor will it affect any rights of the Railway thereunder.
In case of any information submitted by tenderer is found to be false, forged or incorrect at any time during process for evaluation of tenders, it shall lead to forfeiture of the tender Bid Security besides banning of business for a period of up to two years.
In case of any information submitted by tenderer is found to be false, forged or incorrect after the award of contract, the contract shall be terminated. Bid security, Performance Guarantee and Security Deposit available with the railway shall be forfeited. In addition, other dues of the contractor, if any, under this contract shall be forfeited and agency shall be banned for doing business for a period of up to two years.
Any changes in GST rate (increase/decrease) as the casemay be shall applicable in the contract and will be paid by the firm/Railway.
The rates quoted shall be FIRM and shall include all statutory obligations on the part of the contractor.
Restrictions on the Employment of Retired Engineers of Railway Services Within One Year of their Retirement: The Contractor shall not, if he is a retired Government Engineer of Gazetted rank, himself engage in or employ or associate are tired Government Engineer of Gazetted rank, who has not completed one year from the date of retirement, in connection with this contract in any manner whatsoever without obtaining prior permission of the President and if the Contractor is found to have contravened this provision it will constitute a breach of contract and administration will been titled to terminate the contract and forfeit his Performance Guarantee as well as Security Deposit.
In the instant tender departmental valuation has been calculated with GST @ 18% and tenderer need to quote their rates with GST rate @ 18 %.
However, inter se ranking will be done on the quoted value including GST applicable on the date of opening.
Shramikkalyan portal:- (i) Contractor is to abide by the provisions of various labour laws in terms of above clause 54,55, 55-A and 55-B of Indian Railways Standard General Conditions of Contract. In order to ensure the same, an application has been developed and hosted on website 'www.shramikkalyan.indianrailways.gov.in'. Contractor shall register his firm/company etc. and upload requisite details of labour and their payment inthis portal. These details shallbe available in public domain. The registration /updation in Portal shall be done as under: (a)Contractor shall apply for one time registration of his company/firm etc. in the Shramikkalyan portal with requisite details subsequent to issue of Letter of Acceptance. Engineer shall approve the contractor's registration in the portal within 7 days of receipt of such request. (b)Contractor once approved by any Engineer, can create password with login ID (PAN No.) for subsequent use of portal for all Letter of Acceptances (LoAs)issued in his favour. (c)The contractor once registered on the portal, shall provide details of his Letter of Acceptances (LoAs)/ Contract Agreements on shramikkalyan portal within 15 days of issue of any LoA for approval of concerned Engineer. Engineer shall update (if required) and approve the details of LoA filled by contractor within 7 days of receipt of such request.(d)After approval of LoA by Engineer, contractor shall fill the salient details of contract labours engaged in the contract and ensure updating ofeach wage payment to them on shramikkalyan portal on monthly basis. (e)It shall be mandatory upon the contractor to ensure correct and prompt uploading of all salient details of engaged contractual labour & payments made thereof after each wage period. (ii)While processing payment of any'On Account Bill' or 'Final Bill' or release of 'Advances' or 'Performance Guarantee / Security deposit', contractor shall submit a certificate to the Engineer or Engineer's representatives that "I have uploaded the correct details of contract labours engaged in connection with this contract and payments made to them during the wage period in Railway's Shramikkalyan portal at 'www.shramikkalyan.indianrailways.gov.in' till____Month,____Year.
The e-tender or other attached documents connected there with should be digitally signed using digital signature of authorized person only.
If the date of opening happens to be a BANDH or Holiday or Natural calamities, the tender will be opened at the same time on the following working day.
ON ACCOUNT AND FINAL PAYMENT: On account and final payment will be made duly following the Payment Terms attached with the tender document.
In case of increase or decrease in GST rate, same will be either paid by Railway or recovered from the agency as the case may be.
Electrical work for renovation and shifting of DRM building control room,TPC control, Security control, DG room, meeting room, commercial control, Rail madad,fault control etc.,beutification of circulating area of DRM building, renovation of Sr.DSC office and officers chamber at Sr.DFM office.
114-ELC-G-KGP-25-26-33R1~SER
114-ELC-G-KGP-25-26-33R1
Open
Works - General
6 Months
Paschim Medinipur, West Bengal
₹0
₹2.7 L
16 Jan 2026
24 Dec 2025
2 Jan 2026
140 items across 1 schedule
| # | Description | Unit | Qty | Rate | Amount |
|---|---|---|---|---|---|
| 1 | Concealed Wiring of light and fan point by 1.5 Sq. mm, Single Core, Copper wire each for phase & neutral with 1.5 Sq. mm, Single Core, Copper wire for Earthing through PVC Conduit Pipe of Nominal Size 20mm/25mm (as per site requirement) including supply and fixing of all required materials like modular switch, socket, lamp holder, ceiling rose with suitable flush metal boxes, front plate etc. as per specifications mentioned in explanatory note. | Point | 2100.00 | 898 | 18,85,800 |
| 2 | Concealed Sub Circuit wiring by 2.5 sq. mm, Single Core, Copper wire each for phase & neutral with 2.5 Sq. mm, Single Core, Copper wire for Earthing through PVC Conduit Pipe of Nominal Size 25mm including supply and fixing of all required materials like ceiling rose, suitable flush metal boxes, front plate etc. as per specifications mentioned in explanatory note. | Metre | 9500.00 | 182.58 | 17,34,510 |
| 3 | Concealed Sub Circuit wiring by 4 sq. mm, Single Core, Copper wire each for phase & neutral with 4 Sq. mm, Single Core, Copper wire for Earthing through PVC Conduit Pipe of Nominal Size 25mm including supply and fixing of all required materials like ceiling rose, suitable flush metal boxes, front plate etc. as per specifications mentioned in explanatory note. | Metre | 7500.00 | 220.28 | 16,52,100 |
| 4 | Concealed Sub Circuit wiring by 6 sq. mm, Single Core, Copper wire each for phase & neutral with 6 Sq. mm, Single Core, Copper wire for Earthing through PVC Conduit Pipe of Nominal Size 25mm including supply and fixing of all required materials like ceiling rose, suitable flush metal boxes, front plate etc. as per specifications mentioned in explanatory note | Metre | 3500.00 | 285.93 | 10,00,755 |
| 5 | Concealed Three phase Sub Circuit wiring by 10 sq. mm, Single Core, Copper wire each for phase & neutral with 10 Sq. mm, Single Core, Copper wire for Earthing through PVC Conduit Pipe of Nominal Size 25mm including supply and fixing of all required materials like ceiling rose, suitable flush metal boxes, front plate etc. as per specifications mentioned in explanatory note | Metre | 500.00 | 1,030 | 5,15,000 |
| 6 | Concealed Three phase Sub Circuit wiring by 16 sq. mm, Single Core, Copper wire each for phase & neutral with 16 Sq. mm, Single Core, Copper wire for Earthing through PVC Conduit Pipe of Nominal Size 25mm including supply and fixing of all required materials like ceiling rose, suitable flush metal boxes, front plate etc. as per specifications mentioned in explanatory note | Metre | 800.00 | 1,186 | 9,48,800 |
| 7 | Supply of Modular Electrical switches and accessories including Modular 16A Switch- 01 No., Modular 6A/16A- 6 Pin Socket- 01 No., with Stainless Steel boxes, PVC Cover Plate etc. and all other accessories to complete job for concealed wiring as per specifications mentioned in explanatory note | Numbers | 350.00 | 1,316 | 4,60,600 |
| 8 | Fixing and commissioning of Modular Electrical switches and accessories including Modular 16A Switch- 01 No., Modular 6A/16A- 6 Pin Socket- 01 No., with Stainless Steel boxes, PVC Cover Plate etc. and all other accessories to complete job duly concealed in wall structure | Numbers | 350.00 | 34.78 | 12,173 |
| 9 | Supply of Modular Electrical switches and accessories including Modular 16A Switch- 01 No., Modular 6A/16A- 6 Pin Socket- 01 No., with Stainless Steel boxes, PVC Cover Plate etc. and all other accessories to complete job for surface wiring as per specifications mentioned in explanatory note | Numbers | 100.00 | 1,026 | 1,02,600 |
| 10 | Fixing and commissioning of Modular Electrical switches and accessories including Modular 16A Switch- 01 No., Modular 6A/16A- 6 Pin Socket- 01 No., with Stainless Steel boxes, PVC Cover Plate etc. and all other accessories to complete job duly concealed in wall structure | Numbers | 100.00 | 34.78 | 3,478 |
| 11 | Supply of recess/surface mounting 2feetX2feet LED Luminaire with 36 watt with suitable driver as per IS:10322/part 5/sec-2/2012 and IS 16107 (Part2/Sec 1) : 2012 for Recess type or latest. Warranty for free replacement :3 Years or above,Operating Voltage and frequency range :140V to 280 V at 50 Hz AC,Color Rendering Index(CRI) :>/=80,LED chip Efficacy :>/=130 lm/watt, | Numbers | 270.00 | 3,400 | 9,18,000 |
| 12 | Fixing and commissioning of recess/surface mounting 2feetX 2feet LED Luminaire with 24/36 watt with suitable driver,with supply of stainless steel fastener and all other accessories to complete job. | Numbers | 270.00 | 346.85 | 93,649.5 |
| 13 | Supply of 18W (4000-6500k) LED Recess mounted downlighte with pressure die- cast aluminium heat sink & clear PC as a cover in white powder coated finish with Independent electronic LED driver..Warranty for free replacement :2 Years or above,Operating Voltage and frequency range :140V to 280 V at 50 Hz AC,Color Rendering Index(CRI) :>/=80,LED chip Efficacy :>/=120 Lm/Watt. | Numbers | 130.00 | 1,737.9 | 2,25,927 |
| 14 | Fixing and commissioning of 18W (4000- 6500k) LED Recess mounted downlighte with pressure die-cast aluminium heat sink & clear PC as a cover in white powder coated finish with Independent electronic LED driver and all other accessories to complete job. | Numbers | 130.00 | 173.79 | 22,592.7 |
| 15 | Supply of 1 M moduler MS GI Box with Modular Plates and 6A Moduler switch ( to be used for calling bell or others) duly Concealed in wall surface including all other accessories to complete job with latest amendment or specification issued from HQ/GRC. | Numbers | 100.00 | 411 | 41,100 |
| 16 | Fixing and commissioning of 1 M MS GI Box with Modular Plates and 6A Moduler switch ( to be used for calling bell or others) duly Concealed in wall surface including all other accessories to complete job with latest amendment or specification issued from HQ/GRC | Numbers | 100.00 | 41.1 | 4,110 |
| 17 | Supply of 2 M MS GI Box with Modular Plates and 6 A 3 Pin shuttered moduler socket with ISI markingSocket duly Concealed in wall surface including all other accessories to complete job with latest amendment or specification issued from HQ/GRC. | Numbers | 200.00 | 514 | 1,02,800 |
| 18 | Fixing and commissioning of 2 M MS GI Box with Modular Plates and 6 A 3 Pin shuttered moduler socket with ISI markingSocket duly Concealed in wall surface including all other accessories to complete job with latest amendment or specification issued from HQ/GRC if any time to time, including stainless steel fastener, Pin Type Terminal End Lugs as per specification attached. (Wiring will be covered under Shedule item No. as per site requirement). | Numbers | 200.00 | 51.4 | 10,280 |
| 19 | Supply of 3 M MS GI Box with Modular Plates and 6A moduler switch and 6 A 3 Pin shuttered moduler socket with ISI markingSocket duly Concealed in wall surface including all other accessories to complete job with latest amendment or specification issued from HQ/GRC | Numbers | 100.00 | 681 | 68,100 |
| 20 | Fixing and commissioning of 3 M MS GI Box with Modular Plates and 6A moduler switch and 6 A 3 Pin shuttered moduler socket with ISI markingSocket duly Concealed in wall surface including all other accessories to complete job with latest amendment or specification issued from HQ/GRC if any time to time, including stainless steel fastener, Pin Type Terminal End Lugs as per specification attached. (Wiring will be covered under Shedule item No. as per site requirement). | Numbers | 100.00 | 68.1 | 6,810 |
| 21 | Supply of Wall Mounted concealed 100A 8 WAY Busbar chamber ,Busbar made of ETP Grade Copper with 3 Phase indicators and all necessary arrangement(stainless steel fastener,nut,bolt, washer, ,screws etc.) to completethe job. ,Minimum Sheet Thickness properly pretreated and stove enameled/Powder Coated (mm):2 mm. | Numbers | 6.00 | 19,936.1 | 1,19,616.6 |
| 22 | Fixing and commissioning of Wall Mounted Busbar chamber ,Busbar made of ETP Grade Copper with 3 Phase indicators and all necessary arrangement(stainless steel fastener,nut,bolt, washer, ,screws etc.) to completethe job. ,Minimum Sheet Thickness properly pretreated and stove enameled/Powder Coated (mm): 1.6 mm to complete the job as per site requirement. | Numbers | 6.00 | 199.36 | 1,196.16 |
| 23 | Supply of TPN 4-way DB (Glazed Door) consisting with FP 63A, 10kA MCB with 4PP, Type B- 01 no. and SP 20A, 10kA MCB, Type B- 05 nos, SP 16A, 10kA MCB, Type B- 05 nos as outgoing with Cu.bus- bar, Neutral links, Spreader Link and Earth bar etc. Thickness of DB material (in mm): 1.6 mm (CRCA Sheet Steel). Cost includes all other accessories including stainless steel fastener, Pin Type Terminal End Lugs to complete job as per specification attached.MCB as per Description no. SER/ELEC/GS/DESCRIPTION/MCB/REV- 0/NOV 2024,dtd. 18/11/24 or latest. | Set | 35.00 | 10,438 | 3,65,330 |
| 24 | Fixing and Commissioning of TPN 4-way DB (Glazed Door) consisting with FP 63A, 10kA MCB with 4PP, Type B- 01 no. and SP 20A, 10kA MCB, Type B- 05 nos, SP 16A, 10kA MCB, Type B- 05 nos as outgoing with Cu.bus-bar, Neutral links, Spreader Link and Earth bar etc. Thickness of DB material (in mm): 1.6 mm (CRCA Sheet Steel). Cost includes all other accessories including stainless steel fastener, Pin Type Terminal End Lugs to complete job | Set | 35.00 | 616.67 | 21,583.45 |
| 25 | Supply, fixing and commissioning of 0.5 W LED Bulb/Lamp of LED green or LED red for outdoor/Indoor purpose in office room with ceiling rose and wiring to complete the job. | Numbers | 100.00 | 110 | 11,000 |
| 26 | Supply of Wireless Call Bell, Battery Operated ( 10 meters or higher range ). | Numbers | 100.00 | 310 | 31,000 |
| 27 | Fixing and commissioning of Calling Bell with necessary all accessories to complete the job. | Numbers | 100.00 | 15.31 | 1,531 |
| 28 | Supply of exhaust fan of 200mm Rust proof Body & Blade for Durability, Class of insulation Class E, Rated voltage 230 V, 50HZ, AC,Single Phase, speed (RPM): 1250 or more as per site requirement. Frame, Legs Set,Rubber Clamps and Other Hardware included in the scope of supply. | Numbers | 70.00 | 2,080 | 1,45,600 |
| 29 | Fixing and commissioning of Heavy Duty Exhaust Fans as per consignee requirement. | Numbers | 70.00 | 155.14 | 10,859.8 |
| 30 | Laying of LT cable/cables in underground along the road through cable trench etc. as mentioned in explanatory note | Metre | 1650.00 | 148.43 | 2,44,909.5 |
| 31 | Laying of LT cable/cables across the road, track, drain through RCC/GI pipe as mentioned in explanatory note. | Metre | 450.00 | 339.77 | 1,52,896.5 |
| 32 | Laying of LT cable/cables on wall/structure through PVC casing pipe of size 4inches or 3inches with accessories as mentioned in explanatory note. | Metre | 500.00 | 102.07 | 51,035 |
| 33 | Laying of extra cables in the excavated same trench as per consignee requirement. | Metre | 250.00 | 18.42 | 4,605 |
| 34 | Boring/ Punching of underground crossing track with pipe pushing by HDD/manual technology for crossing HT/LT power cable below the railway track/road including jointing of HDPE Pipe etc. | Metre | 400.00 | 1,578.72 | 6,31,488 |
| 35 | Transportation of cables in rolls with or without wooden drums from the store of concerned SSEE or any store of kharagpur to the site of works. | Each | 8.00 | 1,171.11 | 9,368.88 |
| 36 | Supply, erection, testing and commissioning of LT XLPE cable gland made of stainless steel with aluminium lu g s /s o c k e t s (4 Nos.) suitable for termination work of LT 4 Core X 16-25 sq. mm XLPE aluminum conductor armoured cable. | Set | 5.00 | 220.33 | 1,101.65 |
| 37 | Supply, erection, testing and commissioning of LT XLPE cable gland made of stainless steel with aluminium lugs/sockets (4 Nos.) suitable for termination work of LT 4 Core X 70-95 sq. mm XLPE aluminum conductor armoured cable. | Set | 10.00 | 387.39 | 3,873.9 |
| 38 | Supply, erection, testing and commissioning of LT XLPE cable gland made of stainless steel with aluminium lugs/sockets (4 Nos.) suitable for termination work of LT 4 Core X 120-150 sq. mm XLPE aluminum conductor armoured cable. | Set | 5.00 | 444.96 | 2,224.8 |
| 39 | Supply, erection, testing and commissioning of LT XLPE cable gland made of stainless steel with aluminium lugs/sockets (4 Nos.) suitable for termination work of LT 4 Core X 185-300 sq. mm XLPE aluminum conductor armoured cable. | Set | 3.00 | 650 | 1,950 |
| 40 | Erection and commissioning of HDPE pipe of Any size with all accessories to complete job. | Metre | 50.00 | 40.75 | 2,037.5 |
| 41 | Supply of Hot Dip Galvanized (HDG) Perforated Type Cable Tray Width (mm): 150, Height (mm) : 75 (or as per site requirement), Cable Tray Sheet Thickness (mm) 2.5, Length of Cable Tray (mm): 2500 (-5 mm +10 mm), HAVING SLOTTED RUNG SPACING with made up of 50X50X5 angle and 35X4 MS flat with clamp, cover and accessories if required or as suitable as and where required as per consignee required to complete job. | Each | 40.00 | 1,795 | 71,800 |
| 42 | Laying and fixing of Hot Dip Galvanized (HDG) Perforated Type Cable Tray Width (mm): 150, Height (mm) : 75 ( or as per site requirement),Cable Tray Sheet Thickness (mm) 2.5, Length of Cable Tray (mm): 2500 (-5 mm +10 mm), HAVING SLOTTED RUNG SPACING with made up of 50X50X5 angle and 35X4 MS flat with clamp, cover and accessories if required or as suitable as and where required as per consignee required to complete job. | Each | 40.00 | 209.81 | 8,392.4 |
| 43 | Supply of VTPN 4-way DB consisting with FP 125A, 36kA MCCB-01no as incoming and SP 20A,10kA MCB- 12 nos as outgoing with Cu.bus-bar, Neutral links, Spreader Link and Earth bar etc. Thickness of DB material (in mm): 1.6 mm (CRCA Sheet Steel). Cost includes all other accessories including stainless steel fastener, Pin Type Terminal End Lugs with wiring and all other accessories to complete job as per specification attached. | Set | 10.00 | 32,923 | 3,29,230 |
| 44 | Fixing and Commissioning of VTPN 4-way DB consisting with FP 125A, 36kA MCCB- 01no as incoming and SP 20A,10kA MCB- 12 nos as outgoing with Cu.bus-bar, Neutral links, Spreader Link and Earth bar etc. Cost includes all other accessories including stainless steel fastener, Pin Type Terminal End Lugs with wiring and all other accessories to complete job | Set | 10.00 | 575.29 | 5,752.9 |
| 45 | Electric Pole Cutting (Pole to be deposited in Consignee's Store) | Numbers | 30.00 | 1,149.28 | 34,478.4 |
| 46 | Transport of the SST /Rail pole to site, cutting(if required) ,Errection & Commissioning of 5mtr /7 mtr /9mtr length SST /Rail pole having Single/ Double arm bracket (as per requirement) of length one mtr, top cap etc. 1/6 of the pole to be burried in ground , concretting the foundation of size 1mx1mx1.2m in the ratio 1:3:6(Cement:Stone cheap:Sand) and construction of muffing of size 1.5 ftx 1.5 ftx 1.5 ft. with 6" slope on the top above cement finishing( the rate shall be inclusive of all materials ) & painting of pole if required (Pole will be supplied by Rly.). | Numbers | 20.00 | 3,020.67 | 60,413.4 |
| 47 | Supply,Installation and commissioning 7 meter GI Octagonal Pole with 100 W 6 nos LED flood Lights arranged in a ring to complete job, including all fixing accessories(Junction box,Astronomical timer panel,smart pack, insulated cable connector etc). Supply of all the materials required for civil foundation of pole. Transport cost is also included in the price. The price also includes the complete civil work with electrical work - Commissioning of R.C.C. foundation for High Mast/Pole (considering land bearing capacity of soil including design of foundation) supplying of all civil materials. All Civil works will be as per High Mast/pole manufacturer design.Pole description-As per Manufaucturer design. Make Pole: Utkarsh/Bajaj/Nezone/National Pole/BPP/any IS standard Indian make Make LED: Bajaj /Havells/Crompton/ Syska / Surya/any IS standard Indian m a k e The design drawing for RCC foundation and pole should be supplied this office and shall be approved by Sr.DEE(G)/KGP before the supply of all materials. | Numbers | 2.00 | 99,990 | 1,99,980 |
| 48 | Fabrication,Supply,Installation and commissioning of extra single arm heavy duty GI pipes arrangements on existing octagonal pole with all acessories to complete job. | Numbers | 40.00 | 1,234 | 49,360 |
| 49 | Supply,fixing and commissioning of decorative 5W or higher wattage Warm White or coloured (as per requirement) LED Outdoor UP Down Wall Light with in- built LED and all acessories to complete job. Warranty=2 years | Numbers | 50.00 | 999 | 49,950 |
| 50 | Supply,fixing and commissioning of PVC Occupancy sensor (PIR human sensor) with wiring and all acessories to complete job. Warranty=2 years | Numbers | 50.00 | 2,180.77 | 1,09,038.5 |
| 51 | Supply,fixing and commissioning of ceiling mounted hanging decorative glass/metal pendent LED luminaire as per consignee requirement. Warranty=1 year | Numbers | 15.00 | 5,006 | 75,090 |
| 52 | Supply of 12W (4000-6500k) LED Recess mounted downlighter with pressure die- cast aluminium heat sink & clear PC as a cover in white powder coated finish with Independent electronic LED driver..Warranty for free replacement :2 Years or above,Operating Voltage and frequency range :140V to 280 V at 50 Hz AC,Color Rendering Index(CRI) :>/=80,LED chip Efficacy :>/=120 Lm/Watt. | Numbers | 60.00 | 1,463.4 | 87,804 |
| 53 | Fixing and commissioning of 12W (4000- 6500k) LED Recess mounted downlighter with all other accessories to complete job. | Numbers | 60.00 | 146.34 | 8,780.4 |
| 54 | Supply of 9W (4000-6500k) LED Recess mounted downlightr with pressure die- cast aluminium heat sink & clear PC as a cover in white powder coated finish with Independent electronic LED driver..Warranty for free replacement :2 Years or above,Operating Voltage and frequency range :140V to 280 V at 50 Hz AC,Color Rendering Index(CRI) :>/=80,LED chip Efficacy :>/=120 Lm/Watt. Make- Bajaj/Havells/Crompton/Surya/IS standard Indian make . | Numbers | 65.00 | 1,092.6 | 71,019 |
| 55 | Fixing and commissioning of 9W (4000- 6500k) LED Recess mounted downlighte with pressure die-cast aluminium heat sink & clear PC as a cover in white powder coated finish with Independent electronic LED driver and all other accessories to complete job. | Numbers | 65.00 | 109.26 | 7,101.9 |
| 56 | Supply of DP 40 Amps, 10kA 2PP type-B MCB with sheet steel powder painted enclosure suitable for Double Pole MCB as per IS/IEC 60898-1, 2002 & IS/ERC 60947- 1- 2002 having charateristics of C/B, with front Sheet Steel cover, having cut out for installation of Circuit Breaker. The enclosure shall be powder coated with minimum 2 earth points and adequate din Rail for mounting the Circuit Breaker as per IS:11039-1983 Top Hat Section Rail TH: 35/7.5 with Stainless steel fasteners. The enclosure must have provision of knockout punches on top and bottom for conductor entry and exit and shall be as per IEC 61439-3 with IP- 65 protection. | Numbers | 70.00 | 1,018 | 71,260 |
| 57 | Fixing and commissioning of DP 40 Amps, 10kA 2PP all type MCB with sheet steel powder painted enclosure suitable for Double Pole MCB ,with front Sheet Steel cover, having cut out for installation of Circuit Breaker, with Stainless steel fasteners, wiring ,cable and necessary item as per site requirement to complete job. | Numbers | 70.00 | 74.39 | 5,207.3 |
| 58 | Dismantling of wiring fitting / C. fan/ M e t e r / DB board etc and return to Railway store. | Job | 2000.00 | 416.31 | 8,32,620 |
| 59 | Supply of 200A (ON-Load) manual Changeover Switch (4 Pole) I-O-II, (Conforms to IS/IEC:60947-3) with SS Enclosure and SS fastener and accessories. | Numbers | 1.00 | 22,939.2 | 22,939.2 |
| 60 | Fixing & Commissioning of 200A (ON- Load) manual Changeover Switch (4 Pole) I-O-II,(Conforms to IS/IEC:60947-3) with SS Enclosure and SS fastener and accessories with complete wiring to complete the job. | Numbers | 1.00 | 114.7 | 114.7 |
| 61 | Supply of 100A (ON-Load) manual Changeover Switch (4 Pole) I-O-II, (Conforms to IS/IEC:60947-3) with SS Enclosure and SS fastener and accessories. | Numbers | 1.00 | 12,466.7 | 12,466.7 |
| 62 | Fixing & Commissioning of 100A (ON- Load) manual Changeover Switch (4 Pole) I-O-II,(Conforms to IS/IEC:60947-3) with SS Enclosure and SS fastener and accessories with complete wiring to complete the job. | Numbers | 1.00 | 62.33 | 62.33 |
| 63 | Supply of 63A (ON-Load) manual Changeover Switch (4 Pole) I-O-II, (Conforms to IS/IEC:60947-3) with SS Enclosure and SS fastener and accessories. | Numbers | 2.00 | 9,894.3 | 19,788.6 |
| 64 | Fixing & Commissioning of 63A (ON-Load) manual Changeover Switch (4 Pole) I-O-II, (Conforms to IS/IEC:60947-3) with SS Enclosure and SS fastener and accessories with complete wiring to complete the job. | Numbers | 2.00 | 49.47 | 98.94 |
| 65 | Supply of FP 100A 36kA MCCB with Galvanised Iron Sheet Enclosure and spreader link .Thickness of enclosure Material (mm) 1.0 mm or higher.MCCB as per Description No. SER/ELEC/GS/DESCRIPTION/LT PANEL/1/REV-0/MAR 2024, dtd. 24/04/24 | Numbers | 1.00 | 21,869.62 | 21,869.62 |
| 66 | Fixing and commissioning of FP 100A MCCB with Galvanised Iron Sheet Enclosure and spreader link with proper wiring and all accessories to complete job. | Numbers | 1.00 | 693.59 | 693.59 |
| 67 | Supply of FP 250A 36kA MCCB with SS Enclosure and spreader link .Thickness of enclosure Material (mm) 1.0 mm or higher.MCCB as per Description No. SER/ELEC/GS/DESCRIPTION/LT PANEL/1/REV-0/MAR 2024, dtd. 24/04/24 | Numbers | 1.00 | 29,784 | 29,784 |
| 68 | Fixing and commissioning of FP 250A MCCB with Galvanised Iron Sheet Enclosure and spreader link with proper wiring and all accessories to complete job. | Numbers | 1.00 | 693.59 | 693.59 |
| 69 | Supply of FP 400A 3 6 k A MCCB with Galvanised Iron Sheet Enclosure and spreader link .Thickness of enclosure Material (mm) 1.0 mm or higher.MCCB as per Description No. SER/ELEC/GS/DESCRIPTION/LT PANEL/1/REV-0/MAR 2024, dtd. 24/04/24 Make: L&T/Havells/HPL/INDO ASIAN/ C&S/Hager/any Indian make IS standard | Numbers | 1.00 | 46,879.94 | 46,879.94 |
| 70 | Fixing and commissioning of FP 400A MCCB with Galvanised Iron Sheet Enclosure and spreader link with proper wiring and all accessories to complete job. | Numbers | 1.00 | 693.59 | 693.59 |
| 71 | Supply and Installation of Lightening Protection System Class A type, detail as follows- (1) Lightening arrester technology: Advance Early Steamer Emission. Material: High current discharge stainless steel. International standards: NFC 17- 102. (2) Mast material: FRP pipe and high-grade aluminium. Dimension: 50mm. length: 2 metres FRP pipe and 2 metres high grade aluminium mast. (3) Down conduct cable: PVC insulated copper cable. Dimension: 50 Sq. mm, length: 75mtrs (per set) Lightning strike counter number of counts: 6 digits. Current sensitivity: 1KA to 200 KA, 8/20 & 10/350 micro/Sec. induction Shunt: 0.5 micro. (4) Two (02) No. of maintenance Free Earth with all required consisting as per Specification No. RDSO/SPN/197/2016 Ver 1.0 or latest with all required copper cables and strips. | Set | 2.00 | 1,41,191.72 | 2,82,383.44 |
| 72 | Supply of Wall Mounted Fan with Brushless DC (BLDC) Motor, sweep size 400 mm with feature of Oscillaton & Vertcal Adjustable Tilt Mechanismn Minimum Air Delivery 65 cubic meter/min, Rated Voltage: 230 V, 50Hz, Single phase AC, Motor Winding Material: Copper, No. of Blades-3, Provided with Pull cord or string based speed control mechanism with minimum 3 speed stepsn Colour: White, Minimum Service Value 1.43 as per BEE 5 star rating (BEE's Schedule- 32, Table & Wall- Mounted Fan), Conforming to IS 555:1979 (Reaffirmed Year: 2020) with all amendments.as per latest specification as issued from HQ/GRC time to time. | Numbers | 40.00 | 6,537.2 | 2,61,488 |
| 73 | Fixing and commissioning of 400 millimeter Wall Fan with supply of all accessories and wiring as per consignee requirement. | Numbers | 40.00 | 149.9 | 5,996 |
| 74 | Supply of Propeller type AC Ventilating Fan (Exhaust Fan) of size 300mm, Capacitor type, Rated Voltage-240V, Frequency 50±2 Hz, Insulation material Class B, Motor Enclosure-Totally Enclosed Type, along with Guard and other Accessories such as Frame, Legs Set, Rubber Clamps & Other Hardware etc, Conforming to IS 2312- 1967 with all amendments (Reaffirmed 2020) and ISI mark .Cost includes Suitable size of Stainless steel fastener, screw, nuts, bolts ,washer,along with Guard and other Accessories such as Frame, Legs Set, Rubber Clamps & Other Hardware etc as per site requirement. Fan as per Description No. CEE/S/185/519/Genl., Dtd. 30/05/2022 or latest. | Numbers | 40.00 | 2,312 | 92,480 |
| 75 | Fixing and commissioning of Heavy Duty Exhaust Fans with Stainless steel fastener, screw, nuts, bolts, washer etc. as per site requirement. | Numbers | 40.00 | 155.14 | 6,205.6 |
| 76 | Supply of LED 45 watt or higher wattage street light with Colour Rendering Index (CRI) >=70, confirming IP66 as per specifications mentioned in explanatory note | Numbers | 50.00 | 2,348.27 | 1,17,413.5 |
| 77 | Fixing and commissioning of LED 45 watt or higher wattage street light including wiring of light from loop box. | Numbers | 50.00 | 229.92 | 11,496 |
| 78 | Supply of 150 watt LED flood light as per description No. SER/ELEC/GS/DESCRIPTION/LED Flood Light/ REV-0/OCT 2024 dtd. 28/10/24 or latest including Warranty for free replacement for 03 years with reports & certificates as per attachment. | Numbers | 10.00 | 16,350 | 1,63,500 |
| 79 | Fixing and commissioning of 60W or Higher Watt LED Flood light energy efficient enviornment friendly including wiring of light with lug/socket as per site requirement . | Numbers | 10.00 | 325.72 | 3,257.2 |
| 80 | Supply of 10 HP FULLY AUTOMATIC STAR DELTA OIL IMMERSED SUBMERSIBLE Control Panel for siren in Sheet-Steel Enclosure(of size 6MM or as per site requirement) with single phase preventer relay and in-built auto Star-Delta Timer , Voltmeter & ammeter with rotary switch for 3 Ph. 415V Motor, Timer for auto operation.as per IS standard. | Set | 2.00 | 14,375 | 28,750 |
| 81 | Fixing ,commissioning of 10 HP FULLY AUTOMATIC STAR DELTA OIL IMMERSED SUBMERSIBLE Control Panel for siren in Sheet-Steel Enclosure(of size 6MM or as per site requirement) with single phase preventer relay and in-built auto Star- Delta Timer , Voltmeter & ammeter with rotary switch for 3 Ph. 415V Motor, Timer for auto operation.as per IS standard. | Set | 2.00 | 143.75 | 287.5 |
| 82 | Supply of 4 Pole Power Contactor rating 60A for 3 Ph. 415V,50HZ ,Main Pole Configuration 2NO, 2NC as per IS standard with stainless steel fastener , complete accessories and wiring to complete the job | Set | 2.00 | 13,170 | 26,340 |
| 83 | Fixing ,commissioning of 4 Pole Power Contactor rating 60A for 3 Ph. 415V,50HZ ,Main Pole Configuration 2NO, 2NC as per IS standard with stainless steel fastener , complete accessories and wiring to complete the job | Set | 2.00 | 131.7 | 263.4 |
| 84 | Supply of painted outdoor pillar box made of 2mm thickness sheet steel,rust protected, powder coated single door & locking arrangement as per IP-54, consisting with FP 250Amps 36kA MCCB one no as incoming and FP 125Amps 36kA MCCB-06no as outgoing with suitable Cu. busbar(4nos), ammeter and Voltmeter,selector switches,fuse and indicator etc.including spreader link for MCCB a n d lock -key system and proper socket for proper connection of cable and stainless steel fastener, Pin Type Terminal End Lugs as per specification etc., appropriate spreader link for MCCB and with necessary item for seal the cable entry and outgoing point The pillar box should be mounted on cemented plinth of appropriate size as per the direction of consignee.MCCB as per Description No. SER/ELEC/GS/DESCRIPTION/LT PANEL/1/REV-0/MAR 2024, Dtd. 24/04/24 or latest and MCB as per Description no. SER/ELEC/GS/DESCRIPTION/MCB/REV- 0/NOV 2024, dtd. 18/11/24 or latest. | Set | 2.00 | 2,44,184 | 4,88,368 |
| 85 | Fixing and Commissioning of painted outdoor pillar box made of 2mm thickness sheet steel,rust protected, powder coated single door & locking arrangement as per IP-54, consisting with FP 250Amps 36kA MCCB one no as incoming and FP 125Amps 36kA MCCB- 06no as outgoing with suitable Cu. busbar(4nos), ammeter and Voltmeter,selector switches,fuse and indicator etc.including spreader link for MCCB a n d lock -key system and proper socket for proper connection of cable and stainless steel fastener, Pin Type Terminal End Lugs as per specification etc., appropriate spreader link for MCCB and with necessary item for seal the cable entry and outgoing point The pillar box should be mounted on cemented plinth of appropriate size as per the direction of consignee | Set | 2.00 | 3,178.55 | 6,357.1 |
| 86 | Dismantling,re-fixing,shifting and commissioning of pillar box (Indoor/Outdoor) with cable at other location as per consignee requirement including MCCB/MCB/Time switch / Cable/wiring and all other accessories. The pillar box should be mounted on cemented plinth of appropriate size as per direction of consignee with supply of stainless steel fastener, Lug in Wire termination and all other accessories to complete the job as per SER latest specification. | Job | 4.00 | 4,800 | 19,200 |
| 87 | Dismantling,re-fixing,shifting and commissioning of LT panel (Indoor type , of large capacity switch gears 630A- 1250A capacity) with cable at other location as per consignee requirement including MCCB/MCB/Time switch / Cable/wiring and all other accessories. The panel should be mounted on cemented plinth of appropriate size or wall as per direction of consignee with supply of stainless steel fastener, Lug in Wire termination and all other accessories to complete the job as per SER latest specification. | Job | 2.00 | 33,000 | 66,000 |
| 88 | Dismantling,re-fixing,shifting and commissioning of LT panel (Indoor type , of medium capacity switch gears 150A- 600A capacity) with cable at other location as per consignee requirement including MCCB/MCB/Time switch / Cable/wiring and all other accessories. The panel should be mounted on cemented plinth of appropriate size or wall as per direction of consignee with supply of stainless steel fastener, Lug in Wire termination and all other accessories to complete the job as per SER latest specification. | Job | 2.00 | 12,800 | 25,600 |
| 89 | Fixing and commissioning Cable Junction Boxes of size (Box Dimensions LXBXH in mm) 450x375x200 mm or higher IP 65 with metric knockouts for cable entry with 3-Phase in- coming and out going connection consists of 3-Phase and neutral terminal and 15 Amps K-fuse as per relevant ISS, with suitable bridge arrange- ment with 4nos copper bus bar of 63A capacity and all necessary accessories. Fixing shall be made with necessary arrangements as per site requirement, cables are to be terminated with proper socketing arrangement to complete job. | Numbers | 5.00 | 74.09 | 370.45 |
| 90 | Supply, laying, fixing and commissioning of 25 x 5mm GI strip as and where required extra for earth connection, at 0.5 Mtr below ground between earth electrode and main switch/ DB/ Electric pole etc. as per site supervisor's instruction, including connection & terminating with stainless steel nut, bolt, spring, washer etc, as required. (joining shall be done by overlapping and with 2 sets of stainless steel nut bolt & spring kit complete as per IS, IE rules and site requirement. | Metre | 200.00 | 112.17 | 22,434 |
| 91 | Supply of Earthing arrangement with supply of Hot Dip Galvanized (HDG) earth cone and all other requisite materials as per CEE/GRC's Drg. No.CEE/G/A3/P-150, Alt.1 including sump box with salt and charcoal, metalic cover etc. as per site supervisor's instruction. Cost includes supply of all materials mentioned in the Drawing including 02 mtrs 25x5mm GI strip for connection from earth electrod pipe to light pole /Rail pole etc. | Each | 25.00 | 4,119.67 | 1,02,991.75 |
| 92 | Erection of Earthing arrangement with erection of Hot Dip Galvanized (HDG) earth cone and all other requisite materials as per CEE/GRC's Drg. No.CEE/G/A3/P-150, Alt.1 including sump box with salt and charcoal, metalic cover etc. as per site supervisor's instruction. Cost includes erection of all materials mentioned in the Drawing including 02 mtrs 25x5mm GI strip for connection from earth electrod pipe to light pole /Rail pole etc. | Each | 25.00 | 993.86 | 24,846.5 |
| 93 | Supply of LED Garden Light 12W, Bollard type Pole with LED .Material of Garden Lighting pole :Aluminium casting . LED Lamp/System effi cacy in each lantern /luminaire (in lumen / watt)>=105 and < 120 , Colour Rendering Index (CRI) - Minimum 70, Description may be change as per site requirement.As per IS standard or latest if any, | Numbers | 50.00 | 9,950 | 4,97,500 |
| 94 | Fixing and commissioning of LED Garden Light 12W, Bollard type Pole with LED with all civil work to complete the job. | Numbers | 50.00 | 149.25 | 7,462.5 |
| 95 | Supply of Decorative GLOBE wall light fixture made up of Polycarbonate with suitable 9 W LED lamp. | Numbers | 6.00 | 705.2 | 4,231.2 |
| 96 | Fixing and commissioning of of Decorative GLOBE wall light fixture made up of Polycarbonate with suitable 9 W LED lamp with GI clamp, nut, bolt and and all other accessories to complete job. | Numbers | 6.00 | 141.04 | 846.24 |
| 97 | Point wiring for light, fan, plug points etc. by 1.5 sq. mm, Single Core, Copper wire each for phase & neutral with 1.5 Sq. mm, Single Core, Copper wire for Earthing through PVC Conduit Pipe of Nominal Size 25mm including supply and fixing of all required materials like ceiling rose, modular switch and socket suitable flush metal boxes, front plate etc. as per specifications mentioned in explanatory note | Each | 500.00 | 714.55 | 3,57,275 |
| 98 | Circuit/ Sub Circuit wiring by 2.5 sq. mm, Single Core, Copper wire each for phase & neutral with 2.5 Sq. mm, Single Core, Copper wire for Earthing through PVC Conduit Pipe of Nominal Size 25mm including supply and fixing of all required materials like ceiling rose, suitable flush metal boxes, front plate etc. as per specifications mentioned in explanatory note. | Metre | 500.00 | 152.5 | 76,250 |
| 99 | Circuit/ Sub Circuit wiring by 4 sq. mm, Single Core, Copper wire each for phase & neutral with 4 Sq. mm, Single Core, Copper wire for Earthing through PVC Conduit Pipe of Nominal Size 25mm including supply and fixing of all required materials like ceiling rose, suitable flush metal boxes, front plate etc. as per specifications mentioned in explanatory note. | Metre | 400.00 | 111.64 | 44,656 |
| 100 | Circuit/ Sub Circuit wiring by 6 sq. mm, Single Core, Copper wire each for phase & neutral with 6 Sq. mm, Single Core, Copper wire for Earthing through PVC Conduit Pipe of Nominal Size 25mm including supply and fixing of all required materials like ceiling rose, suitable flush metal boxes, front plate etc. as per specifications mentioned in explanatory note. | Metre | 200.00 | 322 | 64,400 |
| 101 | Supply of Three Phase 5 HP Electric Siren, Range (Km) 8,Speed, Rpm 2880,Operating voltage 440 Volt,Motor Rating- HP 5,Sound level 122 decibel,Frequency 50 Hertz ,Warranty 12 month, Mounting Double Ended,Body material-Alluminium Casting | Numbers | 1.00 | 1,13,850 | 1,13,850 |
| 102 | Supply of 24W (4000-6500k) LED Recess mounted downlighte with pressure die- cast aluminium heat sink & clear PC as a cover in white powder coated finish with Independent electronic LED driver..Warranty for free replacement :2 Years or above,Operating Voltage and frequency range :140V to 280 V at 50 Hz AC,Color Rendering Index(CRI) :>/=80,LED chip Efficacy :>/=120 Lm/Watt. | Numbers | 50.00 | 2,190.6 | 1,09,530 |
| 103 | Fixing and commissioning of 18W (4000- 6500k) or higher wattage LED Recess mounted downlighte with pressure die- cast aluminium heat sink & clear PC as a cover in white powder coated finish with Independent electronic LED driver and all other accessories to complete job. | Numbers | 50.00 | 219.06 | 10,953 |
| 104 | Installation And Commissioning of 2Ton Split AC (including connection of copper cable, PVC drain pipe, refrigerent, outdoor mounting stand, Stainless Steel nut- bolt, Refrigerant Copper pipe of all size and all other accessories as per site and consignee requirement) no extra cost will be paid by Railway. Cost included for supply of drain pipe, refrigerent, outdoor mounting stand, Stainless Steel nut- bolt etc. | Numbers | 3.00 | 2,000 | 6,000 |
| 105 | Supply of Flush Mouting AC Metal Distribution Box with SP 20A, 10kA MCB, Type-C- 01 No. & 3 Pin Socket with plug top for Split AC. | Numbers | 4.00 | 727.35 | 2,909.4 |
| 106 | Fixing and commissioning of Flush Mouting AC Metal Distribution Box with SP 20A, 10kA MCB, Type-C- 01 No. & 3 Pin Socket with plug top for Split AC duly concealed in wall with all others accessories and proper wiring to complete job. | Numbers | 3.00 | 72.74 | 218.22 |
| 107 | Supply of starter for split AC for 1.5ton or 2ton of 20-25A capacity or as per site requirement. | Numbers | 4.00 | 453.99 | 1,815.96 |
| 108 | Fixing and commissioning of starter for split AC for 1.5ton or 2ton of 20-25A capacity or as per site requirement duly concealed in wall with all others accessories and proper wiring to complete job. | Numbers | 3.00 | 45.4 | 136.2 |
| 109 | Supply of flexible rubber hose pipe for water cooler of length 1000 mm/piece. size inner diameter (in mm). 50 or as per field requirement. | Numbers | 8.00 | 211.45 | 1,691.6 |
| 110 | Supply of 4 stroke grass cutter with circular saw (Branded or similar) diesel operated as per explanatory note (Warranty Period : Upto 24 months from the date of delivery.) | Numbers | 2.00 | 60,775 | 1,21,550 |
| 111 | Supply of 5 star rated FRIDGE OF 185 LITRES CAPACITY | Numbers | 6.00 | 17,700 | 1,06,200 |
| 112 | FABRICATION,SUPPLY, INSTALLATION, TESTING AND COMMISSIONING OF 200 KVAR APFC PANEL (Automatic Power Factor Correction panel) with cubical modular construction floor mounting dust and vermin proof made of 14/16SWG CRCA sheet as per latest approved specification IS standard and harmonic block reactor with Capacitors 25 KVAR - 04 Banks, Capacitors 20 KVAR- 02 Banks, Capacitors 15 KVAR -02 Bonks, Capacitors 10 KVAR -02 Bank, Capacitors 5 KVAR - O1 Bank, Capacitors 3 KVAR -01 Bank, Capacitors 2 KVAR -01 Bank or any other combination as per site requirement, COMPRISING OF HOUSING, CAPACITORS BANKS. APFC RELAYS, MCCB / MCB PROTECTION ETC., WITH ALL ACCESSORIES INCLUDING MOUNTING ARRANGEMENTS SUITABLE TO WORK ON 3 PHASE 440 VOLTS, 50 HZ AC SUPPLY.Features: automatically switch ON and switch OFF relevant capacitor steps to ensure Consistent power factor, continuously sense and monitor the load conditions by the use of the external CT (whose output is fed to the control relay), Double side earthing connection, Advance C-MOS technology based micro processor relay for intelligent power factor control, Provision of top and bottom cable entry, ensure easy user interface for enabling reliable understanding of system operation, such as display of real time power factor, number of switching operations caried out etc (Warranty Period : Upto 30 months from the date of delivery.) | Numbers | 2.00 | 2,03,062.66 | 4,06,125.32 |
| 113 | FABRICATION,SUPPLY, INSTALLATION, TESTING AND COMMISSIONING of 100 KVAR APFC panel, with CRCA sheet of thickness 2.00 mm with 7 Tank process powder coated, IP-54 consisting of the followings:- (1) Main MCCB 250 Amp 3 Pole 35/36KA - 01 No., (2) Main copper bus bar TPN 400A capacity -01 Set, (3) APFC Relay 8 stage - 01 No. (4) LED indicator R/Y/B -03 Nos, (5) MCCB 100 A 3-Pole 10 KA -02 Nos. (6) MCB 40 A 3-Pole 10 KA -02 Nos.(7) MCB 32 A 3 Pole 10 KA- 01 No. , (8) MCB 20 A 3-Pole 10 KA - 01 No., (9) MCB 10 A 3 Pole 10 KA - 01 No. (10) MCB 6 A 3-Pole 10 KA - 01 No. (11) Contactor Capacity duty type:- MOC 25 for 25 KVAR - 02 No. (12) MOC 15 for 15 KVAR- 02 No(13) MOC 10 for 10 KVAR -01 No. (14) MOC 05 for 05 KVAR -01 No.(15) MOC 03 for 03 KVAR -01 No.(16) MOC 02 for 02 KVAR- 01 No .(17) Heavy Duty capacitor :- 25 KVAR - 02 No, 15 KVAR- 02 No., 10KVAR-01 No. 05 KVAR - 01 No., 3KVAR- 01 No., 2KVAR - 01 No. (18) Auto manual selector switch -08 Nos. (19) LED indicator ON OFF- 16 Nos. (20) Control and Power cable FRLS copper , ( 21) CT- As per requirement or any other combination as per site requirement Including all accessories for commissioning complete in all respect as per direction of Engineer in-charge.. Transportation of complete set from Electrical store to installation site and dismantling and new arrangement as per site requirement is under the scope of firm. NABL/Govt. Lab test report along with 3rd party inspection report to be submitted at the time of supply of material at consignee end. As per IEC 61921/ IS 8623/ IS 16636/ IEC 61439 (Warranty Period : Upto 30 months from the date of delivery.) | Numbers | 2.00 | 1,19,793.35 | 2,39,586.7 |
| 114 | Supply, fixing and fitting of automatic wall mounted hand dryer machine (Warranty Period : Upto 12 months from the date of delivery.) | Numbers | 10.00 | 12,500 | 1,25,000 |
| 115 | Supply of Live Working Non Composite Gloves, Class 4 for maximum use voltage 36000V AC, 54000V DC, Governing Specification As per IS 13774 or latest. | Pair | 12.00 | 4,690 | 56,280 |
| 116 | Supply of 1.5 L 1.0 KW Stainless steel Electric Kettle. | Numbers | 8.00 | 1,047.12 | 8,376.96 |
| 117 | Supply of Microwave Oven Capacity / Volume (Litres) 28 or as per site requirement, Conformity to Indian Standard IS 11676 (Latest),Finish of heating chamber Stainless steel, Warranty 1 year Make- LG/Bajaj/Havells/Philips/ similar IS approved Indian Make. | Numbers | 4.00 | 19,320.18 | 77,280.72 |
| 118 | Supply of 120 W LED Highbay down light new generation energy saving and environmental frindly long life Pressure die cast aluminium alloy housing IP66 with high power LED, Luminaire System Efficacy - Lumen output - (Lumen/watt)>= 120, Color Temperature (CCT) +/- 500 K (in Kelvin) 6000 K, Colour Rendering Index (CRI) (in % age)>= 70, Power factor at full load>=0.95 ,THD < 10%,efficiency >85% (Minimum ).Cover to be fixed to the housing by mean of stainless steel screws. *Warranty for free replacement for 05 years. | Numbers | 30.00 | 13,999.21 | 4,19,976.3 |
| 119 | Fixing and commissioning of 120W Highbay LED new generation energy saving and environmental frindly including wiring of light . | Numbers | 30.00 | 355.04 | 10,651.2 |
| 120 | Supply of 10 Module Hydraulic Cable Cubby Popup Box with HDMI, VGA Connector, Audio Connector, LAN, Power & USB Port or as per site requirement. | Numbers | 30.00 | 2,299 | 68,970 |
| 121 | Erection and commissioning of of 10 Module Hydraulic Cable Cubby Popup Box with HDMI, VGA Connector, Audio Connector, LAN, Power & USB Port or as per site requirement. | Numbers | 30.00 | 114.95 | 3,448.5 |
| 122 | Supply, Installation, Testing and Commissioning of high quality long throw multi color Wash light, Protection Rating: IP66, Power & DMX loop-in / loop-out cables for easy connections. Additional wall mount yoke arrangements for fixing the lights. Power: 100W, CCT: RGBW, Beam Angle 25°/45°, Body: Pressure Die Cast Aluminum / Extruded Aluminum. Body Color: Telegrey. Power Input: DC 24V (without DC Driver) | Numbers | 38.00 | 38,734.68 | 14,71,917.84 |
| 123 | Supply, Installation, Testing and Commissioning of high quality long throw multi color Wash light, Protection Rating: IP66, Power & DMX loop-in / loop-out cables for easy connections. Additional wall mount yoke arrangements for fixing the lights. Power: 50W, CCT: RGBW, Beam Angle 25°/45°, Body: Pressure Die Cast Aluminum / Extruded Aluminum. Body Color: Telegrey. Power Input: DC 24V (without DC Driver) | Numbers | 12.00 | 27,403.14 | 3,28,837.68 |
| 124 | Supply, Installation, Testing and Commissioning of high quality Linear Profile light, Protection Rating: IP65, Power: 15W, Size: 23mm, CCT: RGBW. Beam Angle 120°. Body: Extruded Aluminum With front diffuser. Body Color:Silver, Power Input: DC 24V (without DC Driver) | Numbers | 30.00 | 5,682.88 | 1,70,486.4 |
| 125 | Supply, Installation, Testing and Commissioning of DC power driver for the above Lights, Power : 200W, Input : AC 110-240V AC, 50Hz, Output : DC 12/24V, Protection rating, IP67, Surge protection : LL 4KV, LE 6KV | Numbers | 35.00 | 7,661.74 | 2,68,160.9 |
| 126 | Supply, Installation, Testing and Commissioning of high quality DMX decoder, Power Input : DC 24V | Numbers | 3.00 | 16,699.36 | 50,098.08 |
| 127 | Supply, Installation, Testing and Commissioning of IP65 ""I"" power connectors having 3/4 pole cable connector, chuck type strain relief, Current rating 20A rms continuous, Easy and extremely precise locking system ""Quick Lock"" High impact materials - long-lasting and reliable. | Numbers | 50.00 | 2,376.52 | 1,18,826 |
| 128 | Supply, Installation, Testing and Commissioning of IP65 ""I"" DMX connectors having 3/5 pole cable connector, Male/ Female connector with improved latch, cage type contacts, ""solder stop"" for easy soldering, and additional ground contact for best contact integrity between chassis and cable connector. More durable housing for maximum reliability. | Numbers | 50.00 | 2,630.22 | 1,31,511 |
| 129 | Supply, Installation, Testing and Commissioning of 5 pin XLR Male connectors having 5 pole cable connector, Male/ Female connector with improved latch, cage type contacts, ""solder stop"" for easy soldering, and additional ground contact for best contact integrity between chassis and cable connector. More durable housing for maximum reliability. | Numbers | 8.00 | 969.96 | 7,759.68 |
| 130 | Supply, Installation, Testing and Commissioning of 5 pin XLR Female connectors having 5 pole cable connector, Male/ Female connector with improved latch, cage type contacts, ""solder stop"" for easy soldering, and additional ground contact for best contact integrity between chassis and cable connector. More durable housing for maximum reliability. | Numbers | 2.00 | 969.96 | 1,939.92 |
| 131 | Supply, Installation, Testing and Commissioning of Power Distribution Board made up of CRCA Sheet Steel fabricated housing black powder coated and ivery connectors for the internal terminations and external outgoing connecting points, brass glands of suitable size fitted MCB control for outgoing circuits. - 9 Nos of 6/10A SP Outgoing MCB's. - 1No of 16A TPN Incoming MCB. | Numbers | 1.00 | 39,155.94 | 39,155.94 |
| 132 | Supply, Installation, Testing and Commissioning of IP driver box made up of PVC / UPVC for the internal terminations and external outgoing connecting points, with required PVC / brass glands, Optional suitable size MCB fitted for control outgoing circuits. | Numbers | 9.00 | 6,822.76 | 61,404.84 |
| 133 | Supply, Installation, Testing and Commissioning of DMX isolator or splitter provides Isolated optical DMX splitter provides 8 outputs from a 1 input and Input voltage: AC 110 to 220 V, 50 Hz, Product features: Group 1 & group 8 DMX signal change. | Numbers | 1.00 | 44,567.42 | 44,567.42 |
| 134 | Supply, Installation, Testing and Commissioning of Din Rail Mount DMX controller can be used to control a wide variety of different DMX systems- from RGB/RGBW to more advanced moving and color mixing luminaires, 512 DmX channels in live mode (computer), stand alone mode with 1 area and 20 scenes, Mac OSx 0.6/10.7/10.8 - Windows XP/VISTA/SEVEN/8 32/64 bits and USB 2.0, XLR3, mini USB, Power From 5V to 5.5V DC (AC/DC) adapter in option. | Numbers | 1.00 | 1,79,341.12 | 1,79,341.12 |
| 135 | Facade Lighting arrangement Programming charges. | Job | 1.00 | 60,099.76 | 60,099.76 |
| 136 | Installation, Testing and Commissioning of facade lighting arrangement with supply of required additional accessories for installing the lights as per the final drawing /site condition consisting of clamps, brackets, angles, conduits, joints, hardware's like stainless steel fasteners, nut & bolts etc., (Cost for each station) | Job | 1.00 | 1,22,603.18 | 1,22,603.18 |
| 137 | Design, manufacture, display of wall /hanging / floor mounting type LED illuminated sign / direction boards in half elliptical shape as per explanatory note | Square Foot | 200.00 | 2,988.95 | 5,97,790 |
| 138 | Erection and installation of wall / hanging / floor mounting type LED illuminated sign / direction boards in half elliptical shape. The display sheet shall be of unbreakable 040 translucent polycarbonate sheet of 2 mm thickness. The text / graphics matter visibility shall not be less than 160 deg. The approved colour text and graphics shall be printed / router cut on monomeric calendered vinyl of 70 um thickness and shall be firmly pasted on display sheets. The mounting arrangement shall be hanging, wall mounting, ceiling mounting, pole mounting or floor mounting and as per site requirement. The signage shall have the integral mounting arrangements with sturdy structural frame and ACP cladding on the back side of the signage to avoid rusting and entry of dust. The LED board shall have uniform illumination with 4-8 W / sq. ft and with brightness more than ambient light. Suitable size end cap of 1.5 mm thick SS 304 should be provided | Square Foot | 200.00 | 298.89 | 59,778 |
| 139 | Supply of Flying Insect Control Traps having 2 Chambers with 2 Nos. 20 W or higher wattage UV lamp and other accessories to complete job. | Numbers | 20.00 | 3,770 | 75,400 |
| 140 | Supply of Square Single Element Induction Heater | Numbers | 6.00 | 3,937.3 | 23,623.8 |
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
HTML
nit.pdf
NIT
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .