| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹18.1 LAccepted-AOC 303 GHS 888 SECTOR 20 PANCHKULA 134116 HARYANA | PANCHKULA | PANCHKULA | HARYANA | 134116 | L1 | Accepted-AOC Being lowest | |
| 2 | L2₹21.8 L+₹2.5 L (12.7%)Rejected-Finance MANDIR ROAD NEW ABADI AKALGARH AIR FORCE STATION HALWARA TEH RAIKOT DISTT LUDHIANA PB 141106 | LUDHIANA | LUDHIANA | PUNJAB | 141106 | L2 | Rejected-Finance Other than lowest | |
| 3 | L3₹21.9 L+₹2.6 L (13.2%)Rejected-Finance | L3 | Rejected-Finance Other than lowest | |
| 4 | L4₹23.0 L+₹3.7 L (18.9%)Rejected-Finance 45 PIR BABA TARUSHAW ROAD HALWARA AD LUDHIANA 141106 | HALWARA | LUDHIANA | PUNJAB | 141106 | L4 | Rejected-Finance Other than lowest | |
| 5 | L5₹26.4 L+₹7.1 L (36.5%)Rejected-Finance | L5 | Rejected-Finance Other than lowest |
Tender Value
Refer Docs
EMD Value
₹60,000
Closing Date
19 Mar 2024, 6:00 pmClosed
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
GE (AF) Halwara
GE (AF) Halwara
REPAIR/MAINT OF LT INFRASTRUCTURE IN DOMESTIC AND TECHNICAL AREA AT BARNALA UNDER GE (AF) HALWARA
2024_MES_643119_1
GE/HAL-70/2023-24
Open Tender
Electrical and Maintenance Works
Item Rate
270 days
Barnala
MES ENLISTED CONTRACTORS CLASS D CATEGORY b(i)
8 documents required · 8 mandatory
₹500
GE (AF) Halwara
₹60,000
Yes
6 Apr 2024
19 Feb 2024
21 Mar 2024
19 Feb 2024
19 Mar 2024
5 Mar 2024
Amount
Excavation in trenches not exc 1.5m wide and not exc 1.5m depth for laying of cables etc getting out including forming bottom surface to required level and gradient in soft / loose soil, complete all as specified and directed.
Returning and filling in excavated soil including spreading leveling, watering, well ramming in layers not exc 25 Cm thick, complete all as specified and directed.
Removing of excavated materials not exceeding 50 Mtrs and depositing where directed at a level not exceeding 1.5 Mtrs above the starting point, complete all as specified and directed..
Material and labour sand cushioning using dry clean sand for protection of underground cable, consolidated and compacted, complete all as specified and as directed.
Material and labour well burnt old size sub Class ‘B’ bricks, laid flat, in trenches for cable protection, complete all as specified and as directed.
Taking out following defective cable XLPE/PVC sheathed 1100 volt grade heavy duty armoured with aluminium conductor of any Cross sectional area from trenches, from wall/poles/under floor etc, shifting serviceable cable for relaying and removing the unserviceable cable, complete all as specified and directed. Note : (i) Excavation and earth work shall be measured and paid for separately. (ii) Unit rate of this item is also includes the removal of brick/tile as cable protection, GI pipe and cable joint etc. and nothing extra shall be admissible on this account. (iii) After taking out the cables from the trench, serviceability of cable shall be checked by the contractor in presence of the Engr-in-Charge and nothing extra shall be paid on this account.
Supply and laying, jointing,testing XLPE insulated, armoured, heavy duty, 1100 Volts grade aluminium conductor cable Cross sectional area 6 Sqmm, 4 core in trenches or fixed to wall / passing through pipe / pole and testing, compete all as specified and directed Note : (i) Excavation & earth work, brick protection and sand cushining shall be measured and paid separately in respective items of BOQ.
All as per item No. 7.00 here-in-before but Cross sectional area 10 sqmm, 2 core.
All as per item No. 7.00 here-in-before but Cross sectional area 10 sqmm, 4 core.
All as per item No. 7.00 here-in-before but Cross sectional area 16 sqmm, 4 core.
All as per item No. 7.00 here-in-before but Cross sectional area 25 sqmm, 4 core.
All as per item No.7.00 here-in-before but Cross sectional area 35 sqmm, 4 core.
All as per item No.7.00 here-in-before but Cross sectional area 50 sqmm, 4 core.
All as per item No.7.00 here-in-before but Cross sectional area 70 sqmm, 4 core.
All as per item No.7.00 here-in-before but Cross sectional area 95 sqmm, 4 core.
All as per item No.7.00 here-in-before but Cross sectional area 185 sqmm, 3.5 core.
Supply and fixing in replacment of street light timer with prefabricated box company made, three phase for 8-12 KW light load, 32 Amp per phase comprising of nature switch, suitable capacity contactor and MCB housed in a enclosure and mounted on 40 x 40x 6mm angle iron frame work PCC 1:2:4 (Type-B-1) work on ground as in foundation including excavation and earthwork, complete all as specified and directed.
Material and labour for isolating, disconnecting and transporting the Servo voltage stabilizer of any capacity to workshop for repair maint, strip opening of stabilizer for inspection and ascertaining the defects for repair & replacement of unserviceable spare parts, cleaning, servicing all serviceable accessories including reassembling after repair, preparation for painting with two coats of synthetic enamel paint of approved colour and marking SM/MES No., transporting back to site, reinstallation and testing on load, complete all as specified and directed. Note:- Spare parts will be measured and paid seperately as 'Supply only'.
Supply only PCB controller / plate for automatic voltage correction suitable for servo stabilizer of capacity 150 KVA as per existing type and make, complete all as specified and directed.
Supply only control supply transformer suitable for 150 KVA servo voltage stabilizer as per existing type and make, complete all as specified and directed.
Supply only copper dimmer gear set for automatic voltage correction capacity 150KVA servo stabilizer with as per site requirement for type and make, complete all as specified and directed.
Supply only micro limit switch with cam lever complete for servo stabilizer of capacity 150 KVA as per site requirement for type and make, complete all as specified and directed.
Supply only servo motor synchronous type for automatic voltage correction suitable for servo stabilizer of capacity 150 KVA as per site requirement for type and make, complete all as specified and directed.
Supply only Control Transformer heavy duty sutiable for servo stablizer of 150 KVA capacity as per existing make, complete all as specified and directed.
Taking down old burnt out copper winding and replacement of same for stabilizer oil immersed type of capacity 150KVA by using suitable gauge super enamelled copper conductor as per existing winding, complete all as specified and directed.
Supply only of insulation transformer oil toping up into voltage stabilizer of different capacity complete with superior quality insulating oil BDV not less than 50 KV, complete all as specified and directed.
Material and labour boring of road crossing of size 80 mm dia at suitable depth not lss than 1.00 metre by using machinery / equipments complete without damaging the surface for passing pipes / cables etc. including removing excavated soil to a distance not exc 50m, complete all as specified and as directed. Note : (i) Location of boring holes shall be decided by the Engr-in-Charge as per requirement, nothing extra shall be payable on account of variation in length of crossing of road etc. (ii) During boring soil strata may be changed, hence nothing extra shall be paid to the contractor for boring of holes through different strata/different type of soil. Tenderer is hereby advised to keep in mind this aspect while quoting his rates.
Material and labour in replacment for GI pipe light grade for road crossing / on wall / with pole for cable protection of including cutting chasing of plinth protection or wall for inserting of cable and making good disturbed surface with P:C:C 1:2:4, complete all as specified and directed for following size:-
15 mm dia
40 mm dia
80 mm dia
Material and labour for earthing complete with GI earth plate electrode 600 mm x 600 mm x 6 mm thick, burried directly and preferably vertically in ground, earth pit not less than 2.25 Mtr deep below ground level with top edge of the plate not less than 1.50 Mtr below ground level. The earth plate to be connetced with GI earthing strip of size 32mmx6mm thick by means of brazing between GI strip and earth plate min 45 cm in vertical length and GI strip also to be joined by brazing only. The GI earthing strip to be protected by galvanised iron pipe 40 mm bore (medium grade) up to ground level. Earthing shall be include with providing funnel with 20mm bore galvanised iron pipe (light grade), wire mesh, charcoal or coke and common salt in alternate layer of 15cm (compacted thickness) up to 90 cm all around earth plate further filled with 60 cm thick Tibba sand and 2nd layer with 30 cm of Magnesium sulphate powder (compact thickness ) , 3rd layer with tibba sand up to the ground level. Earthing shall also be include for providing concrete earth pit in PCC (1:3:6) type B-1 (with 20mm graded stone aggregate), 50mm thick precast RCC (1:2:4) cover slab (reinforced with 8mm dia TMT bar @ 15 cm C/C bothways and suitable handle made of 10mm dia) including necessary earth work and testing, complete all as specified and directed. Note :- GI Strip upto 7.5 metre is included in this rate, the length beyond 7.5 metre shall be measured and paid seperately under respective items.
Supply and fix in repairs GI strip 32mm x 6mm in ground / laid in floor / fixed to wall etc, complete all as specified and diredcted. Note :- Excavation and earth work shall be measured and paid separately.
Dismantling and taking out the old stay assembly complete incl demolition of plain cement concrete, complete all as specified and directed. Note :- (i) Unit rate of this item includes to loose/ disconnection the all accessories which are connected to stay assembly including neccessary excavation as directed.
Material and labour for stay assembly complete with accssories as shown in electrical plate No1 including GI adjustable stay rod of 16 mm dia, GI stay wire of size 7/4 mm including stay clamps, loop type insulators etc, complete all as specified and directed. Note :- Earth work and PCC work shall be measured and paid separately.
Supply and replacement of silica gel complete contains in the breather assembly, complete all as specified and directed.
Material and labour for danger notice plate of 1.6mm thick mild steel sheet, vitreous enamelled white, with letters, figures and conventional skull and bones in signal red colour and fixed with M.S. clamps, bolts and nuts of approved size, for LT, 20x15cm size, complete all as specified and directed.
All as per item no 34 above but for HT, 25 x 20 cm size.
Material and labour for PCC 1:4:8 type D-2 using 40 mm graded stone aggregate as in foundation for poles, filling of mass concrete, complete all as specified and as directed.
Material and labour for PCC 1:2:4 type B-1 using 20 mm graded stone aggregate as in coping for old and new poles including form work, complete all as specified and as directed.
Material and labour for cleaning and preparation of steel surfaces of existing dull painting of transformer outdoor type including radiators, cooling ducts, vent pipes, condensor etc and applying two coats of synthetic enameled paint by spray machine including writing MES /SM No(letter size shall be 50 mm size) in capital letters on body for capacity upto 100 KVA transformer outdoor/indoor, complete all as specified and directed.
All as per item No: 38 here-in-before but capacity above 160 KVA and upto 630 KVA.
Material and labour for painting of steel tubular pole 9.0 m long/Swan neck pole, by applying two coat of alluminum paint after scraping/brushing and cleaning the rust on pole and cross arms. Aluminium painting will be done on pole above 1.5 m height from ground level and balance 1.5 m from ground level will be painted by alternate layer of red and white synthetic enammelled paint ( 30 cms each) pole No will be written on pole by black paint in yellow circle of 150 mm dia, complete all as specified and directed.
Material and labour for painting with two coats of synthetic enamel paint on RCC pole upto 1.5 mtr above the GL painted by synthetic enamel paint in alternatively black and white strap of 30 cm after scraping /removing the existing paint and the preparation on the surface of RCC LT pole. Pole No will be written on pole by black paint in white circle of 150 mm dia, complete all as specified and directed.
Material and labour for cleaning and preparation of steel surfaces of any existing E/M equipment / LT Panel and applying one coats of synthetic enameled paint, complete all as specified and directed.
Material and labour for trimming of tree branches on both sides of HT /LT aluminium conductor overhead, complete all as specified and directed. Note : (i) Cutting branches shall be dumped outside the Air Force premises. (ii) Contractor shall be provide the ladder of required height including T&P to his worker and nothing extra shall be paid on this account.
Supply and fixing in replacment of onload change over switch 630 Amps, 4 pole, 415 Volts in sheet metal enclosure, complete all as specified and directed.
Supply and fixing in replacment of Bus bar assembly 400 Amp, 415 Volts,TPN type, IP 42 protection in sheet metal enclosure, complete all as specified and directed.
Taking down / removing existing damage and bent PCC/Steel poles from site including connections, complete all as specified and directed.
Supply and fixing steel tubular swaged poles type 410 SP-31 (9 meter long) complete with CI base plate and finial taper plug, bolts, nuts and screws as specified type including, two coats of synthetic enamel paint over a coat of red oxide primer, complete all as specified and as directed.
Supplying and fixing in replacment of MCCB of 800 Amps, 4 Pole 415 Volt breaking capacity 50 KA , FIXED TM type complete connection with proper size of thimbles, nut bolts etc, complete all as specified and directed.
Material and labour for repair of existing AMF DG set panel complete checking of circuit wiring and replacment of burnt/US spare parts and replacment of burnt circuit wiring and testing at site for smooth functioning of entire system complete all as specified and directed. Note:- Spare parts will be measured and paid seperatly as 'Supply only'.
Supply only contactor MCX-23 cat part No. CS97018 of L&T or equivalent as approved, complete all as specified and directed.
Supply only contactor MCX-22 cat part No. CS97017 of L&T or equivalent as approved, complete all as specified and directed.
Supply only power contactor of cat part No.TC1D8011 C&S make with auxiliary contractor or equivalent as approved, complete all as specified and directed.
Supply only power contactor 115A ofcat part No. LC1FDP115A of C&S make with auxiliary contactor or equivalent as approved, complete all as specified and directed.
Supply only onload change over switch 100 Amps, 4 pole, 415 V, complete all as specified and directed.
Supply only onload change over switch 160 Amps,4 pole ,415 V, complete all as specified and directed.
Material and labour for cleaning of entire cable duct by removing HT/LT cables from the duct, PCC/ iron duct covers removing waste materials including sand , and clean the entire duct and relaying of cables then fillup new sand and cover with existing PCC/Iron duct covers, complete all as specified and directed.
Material and labour for cleaning and preparation of steel surfaces of existing painting of rolling shutter and applying two coats of synthetic enameled paint by spray machine, complete all as specified and directed
Taking out rusted/ damaged M.S sheet as in /PCC/RCC duct covers and Supply & fixing Fe 410-W (Gde-E- 250) quality- A, Plates (plain or chequered) channels, square cut or notched (ordinary and counter sunk) forming holes, without anyattachment, complete all as specified and directed.
Material and labour in repair MS works, cross arms, bracing, support clamps and back plate fabricated out of structural steel sections including nuts, bolts and washers, welding, bending hot or cold, cutting, drilling holes for bolts in any shape or size and including 02 coats of aluminium paint over a coat of red oxide primer, completet all as specified and directed.
Tracing out fault in 11KV U/G cable with the help of fault tracing machine and rectifying the same with joints as specified and directed to restore the supply, complete all as specified and directed. Note: (i) Jointing kit to be measured and paid separately. (ii) Earth work to be measured and paid separately under respective items of BOQ. (III) All other necessary arrangements suitable for locating the faults is deemed to be included in the quoted rate. (iv) T & P required for the entire job shall be provided by the contractor at his own end and quoted rates is deemed to be included and nothing extra shall be admissible on this account.
Material and labour in repair cable jointing kit for 11 KV (Earthed) grade cable for straight through heat shrink type joint complete with jointing material and accessories suitable for 3 core XLPE armoured aluminium conductor cable of size 95 sqmm 3 core, complete all as specified and directed.
All as per item Sl No 61 here-in-before but Cross sectional area 120 sqmm, 3 core.
Supply, jointing and testing in repair 11 KV, 3 core cable end termination joint (heat shrinkable) suitable for 3 core ,11 KV /UG 3 core XLPE armoured aluminium conductor cable of size 95 sqmm 3 core, complete all as specified and directed.
Supply, jointing and testing in repair 11 KV, 3 core cable end termination joint (heat shrinkable) suitable for 3 core ,11 KV /UG 3 core XLPE armoured aluminium conductor cable of size 120 to 185 sqmm 3 core, complete all as specified and directed.
Dismantling of existing ACSR conductor of any size/type from PCC/Steel poles from overhead line, complete all as specified and directed.
Supply, stringing and fixing ACSR conductor of any type/size on existing poles including fixing to insulators with binding wire or aluminium taps, complete all as specified and directed.
Supply and fixing in replacement by removing melted or brunt terminals / connections of MCCB, 4 pole, 415 Volts, with in existing electric panel and connecting with new connections of following capacities:-
MCCB, 50 KA, 4 pole, 630 Amps
MCCB, 25 KA, 4 pole, 400 Amp
MCCB, 25 KA, 4 pole, 200 Amp
MCCB, 25 KA, 4 pole, 160 Amp
MCCB, 25 KA, 3 pole, 250 Amp
MCCB, 25 KA, 3 pole, 200 Amp
MCCB, 25 KA, 3 pole, 100 Amp
MCCB, 16 KA, 3 pole, 63 Amp
Supply only self adhesive PVC electrical Insulation Tape roll of size 1.80 cm X 0.125 mm of length 6.5 metre, complete all as specified and directed.
Supply, install, testing and commissioning in replacement LT Panel, Outdoor type, dust and vermin proof, totally enclosed, platform mounted, factory made having front openable shutter with locking arrangement made out of CRCA steel sheet 3.15 mm thick CPRI approvedwith MS angle iron frame work of size 40 mm x 40 mm x 6 mm thick, duly painted including necessary foundation bolts, PCC (1:2:4), type B-1 platform of suitable size for mounting the panel, suitable for 415 Volts, 50 Hz, three phase, 4 wire system with suitable insulated aluminium busbar of capacity not less than 400 Amps and shall be complete with internal wiring with suitable size of FRLS wire of copper conductor and including the following accessories (for alternate site), complete all specified and directed:- (A) Main Incoming (i) MCCB conforming to IS:13947 (Part-II), IEC-947, 4 pole, 250 Amps, 415 volts, 50 Hz, rupturing capacity 36 KA, with adjustable thermal and adjustable magnetic setting - 01 No. (iii) LED Multifucntional Panel meter to measure voltage, current, frequency, power factor, kWH, etc with all connected CTs. (iv) LED indicating lamps with colour Red, Yellow, Blue, Main ON - 01 Set (B) Main Outgoing (i) MCCB conforming to IS:13947 (Part-II), IEC-947, 4 pole, 63 Amps, 415 volts, 50 Hz, rupturing capacity 36 KA, with adjustable thermal and fixed magnetic setting - 04 No. (ii) MCCB conforming to IS:13947 (Part-II), IEC-947, 4 pole, 160 Amps, 415 volts, 50 Hz, rupturing capacity 36 KA, with adjustable thermal and fixed magnetic setting - 01 No.
Kular and Company
SANGAM ENGINEERS
CHOUDHARY ENTERPRISES
S K BANSAL AND CO.
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .