Line Intractive UPS with AVR Line Intractive UPS With AVR ( 11 ) Technical Specifications Specification Specification Name Values Allowed Values GENERIC Rating in KVA/min VAH capacity of battery (KVA/VAH) 1.0/400 1.0/400 Technology IGBT-PWM IGBT-PWM Type of battery SMF-VRLA confirming to JISC-8702 Pt 1
2 &3 SMF-VRLA confirming to JISC-8702 Pt 1
2 &3 Rated Output (Volt) Single phase sinewave 230v AC
50Hz Single phase sinewave 230v AC
50Hz
Single Phase Quasi-Sin-wave 230 V AC
50 Hz Degree of protection IP-21 IP-21
IP 20 Inverter Efficiency (%) >/= 60% >/= 60%
>/= 70% Warranty for the battery from the date of delivery 1 year 1 year
3 Years Warranty for Line Interactive UPS 1 Year 1 Year Installation and commissioning instructions Yes - CONSTRUCTIONAL Type of enclosure ABS - AC out put for printer (not through Yes Yes
No 1/4 inverter) Inverter out put socket AC out put for printer (not through inverter) 3 Three pin 2 Three pin
3 Three pin
Hard wiring
Not applicable FUNCTIONAL Total harmonic distorsion (%) </= 40% - Input (Volt) Single phase sinewave(160-280v) - Switching over time (Mili sec) Maximum 10 milli seconds - Overload Time (Minutes) >/= 10 minutes - Load power factor >/= 0.6 - Variation in AVR output in AC mode (%) AVR (Voltage regulation) output voltage in AC Mode 230 Volts +/-9%
50 +/-3 Hz - Overload (%) >/=10% - Variation in output voltage in battery mode (%) (UPS output voltage in battery mode) 230 Volts +/- 10% - Variation on output frequency in battery mode (Hz) </=0.5 - PROTECTION Protection against (over discharge) discharge per 12v battery (Volt) 10.5 - Protection for outside input voltage range: If Input voltage goes outside the range 160 to 280 Volts
the system shall switch over to battery mode Yes - Protection against short circuit of UPS Yes - Protection for over voltage and over load Yes - REPORTS AND CERTIFICATIONS Damp heat Test at 45 degree
RH -95% for 2-cycle as per IS:9000 pt-5/sec-1 Yes - Dry heat Test at 45 degree for 16 Hrs as Yes - 2/4 per IS:9000 pt-3/sec-5 Cold Test as per IS:9000 pt-2/sec-4 Yes - Availability of the type test report from central Govt./NABL/ILAC Accredited Lab Yes - Type Test certificate no. and date - - Name Of Lab - - Address of Lab - - As per Meity (Government of India) guidelines UPS shall have valid BIS CRS certifications as applicable Yes - * Bold specifications are the golden parameters. Consignees and Quantity S.No. Consignee Address Quantity Delivery Days 1 Shatrughan shatrughan.singh 482001