| 1.00COMPREHENSIVE MAINTENANCE OF GAS BASED FIRE SUPPRESSION SYSTEM FOR DATA CENTRE & SERVER ROOM AT DRDO BHAWAN, NEW DELHI | ||||||
| 1.01 | Maintenance of 80 ltrs capacity seamless gas cylinder of OESI/CCOE approved suitable for storing HFC 227 ea (FM-200) agent at 25 bar pressure system, complete with valve safety burst disc & safety cap etc. complete as required. (03 Nos) | 12 | Month | 3,000 ₹36,000 | 5,280 ₹63,360 | 15,000 ₹1.8 L |
| 1.02 | Maintenance of master kit comprising of Electric control head (Solenoid valve actuator, Manual valve actuator etc) 24 volt DC to operate the system on receipt of signal from agent releasing control panel to dischrge gas automatically or to operate system manually in case of power failure & gas inhibit push button unit to shift system from auto to manual (reset tool) with all accessories as high pressure discharge & actuation flexible hose metal jacketed, pressure guage, tee, elbow etc. complete as required (01 No) | 12 | Month | 1,450 ₹17,400 | 2,040 ₹24,480 | 1,000 ₹12,000 |
| 1.03 | Maintenance of slave kit comprising of pressure operator control head (Pneumatic actuator) mounted on top of the cylinder to actuate the slave cylinder complete with high pressure discharge & actuation flexible hose metal jacketed, master cylinder adapter kit, pressure guage, male branch tee, elbow etc complete as required (02 Nos) | 12 | Month | 3,500 ₹42,000 | 4,680 ₹56,160 | 500 ₹6,000 |
| 1.04 | Maintenance of HFC 227ea/ (FM-200) Discharge Nozzles (02 Nos) | 12 | Month | 600 ₹7,200 | 960 ₹11,520 | 500 ₹6,000 |
| 1.05 | Maintenance of conventional optical smoke detectorwith built in LED, mounting base (08 No) | 12 | Month | 250 ₹3,000 | 480 ₹5,760 | 500 ₹6,000 |
| 1.06 | Maintenance of fire alarm electronic hooter cum strobe (01 No) | 12 | Month | 200 ₹2,400 | 300 ₹3,600 | 500 ₹6,000 |
| 1.07 | Maintenance of response indicators (04 Nos) | 12 | Month | 200 ₹2,400 | 300 ₹3,600 | 500 ₹6,000 |
| 1.08 | Maintenance of temprature sensors (06 Nos) | 12 | Month | 200 ₹2,400 | 300 ₹3,600 | 500 ₹6,000 |
| 1.09 | Maintenance of 2 zone micro controller based fire alarm cum gas release panel with built in LCD display, real time clock, event logging & on site system configration (01 No) | 12 | Month | 600 ₹7,200 | 960 ₹11,520 | 1,000 ₹12,000 |
Updated dates
Tender Value
₹1.8 L
EMD Value
₹3,672
Closing Date
14 Mar 2026, 11:00 amClosed
Sh B K Panda, Jt Dir (Works)
O/o EMU RND DRDO BHAWAN
CAMC OF GAS BASED FIRE SUPPRESSION SYSTEM INSTALLED AT DATA CENTRE AND SERVER ROOM AT DRDO BHAWAN NEW DELHI
2026_DRDO_892666_3
EMU RND/DRDOBWN/GBFSS/2025/NIT-4
Limited
Miscellaneous Works
EMU RND DRDO BHAWAN
please refer NIT and Enquiry Document
5 documents required · 5 mandatory
₹0
₹3,672
14 May 2026
19 Feb 2026
16 Mar 2026
19 Feb 2026
14 Mar 2026
19 Feb 2026
COMPREHENSIVE MAINTENANCE OF GAS BASED FIRE SUPPRESSION SYSTEM FOR DATA CENTRE & SERVER ROOM AT DRDO BHAWAN, NEW DELHI
Maintenance of 80 ltrs capacity seamless gas cylinder of OESI/CCOE approved suitable for storing HFC 227 ea (FM-200) agent at 25 bar pressure system, complete with valve safety burst disc & safety cap etc. complete as required. (03 Nos)
Maintenance of master kit comprising of Electric control head (Solenoid valve actuator, Manual valve actuator etc) 24 volt DC to operate the system on receipt of signal from agent releasing control panel to dischrge gas automatically or to operate system manually in case of power failure & gas inhibit push button unit to shift system from auto to manual (reset tool) with all accessories as high pressure discharge & actuation flexible hose metal jacketed, pressure guage, tee, elbow etc. complete as required (01 No)
Maintenance of slave kit comprising of pressure operator control head (Pneumatic actuator) mounted on top of the cylinder to actuate the slave cylinder complete with high pressure discharge & actuation flexible hose metal jacketed, master cylinder adapter kit, pressure guage, male branch tee, elbow etc complete as required (02 Nos)
Maintenance of HFC 227ea/ (FM-200) Discharge Nozzles (02 Nos)
Maintenance of conventional optical smoke detectorwith built in LED, mounting base (08 No)
Maintenance of fire alarm electronic hooter cum strobe (01 No)
Maintenance of response indicators (04 Nos)
Maintenance of temprature sensors (06 Nos)
Maintenance of 2 zone micro controller based fire alarm cum gas release panel with built in LCD display, real time clock, event logging & on site system configration (01 No)
Please Enable Macros to View BoQ information
stage.html
html • 0.04 MB
tech_eval.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 0.84 MB
NIT.pdf
Tender Documents • 0.82 MB
ENQGB.pdf
Tender Documents • 1.42 MB
BOQ_945353.xls
BOQ • 0.22 MB
Download all tender documents and submit your bid