Executive Engineer ED III
Office of Executive Engineer ED III
Replacement of damaged CT/PT unit at FTR HQ BSF Camp Paloura, Jammu on 11KV MU-06 feeder I the jurisdiction of sub division Janipur on turnkey basis
2026_PDD_323371_1
ED-III/Jammu/46 of 2026-27
Open Tender
Electrical Works
Item Rate
30 days
jurisdiction of SD Janipur
Please refer Tender documents.
7 documents required · 7 mandatory
₹500
Executive Engineer ED III
₹8,100
3 Sept 2026
3 Sept 2026
26 Sept 2026
3 Sept 2026
25 Sept 2026
3 Sept 2026
| Sl No | Description | Qty | Unit | Est. Rate | Est. Amount |
|---|---|---|---|---|---|
| 1Supply, Installation, Testing & Commissioning of 11KV CT/PT unit with Trivector Meter at FTR HQ BSF Camp Paloura Jammu. | |||||
| 1.01 | 11kV Pilfer resistant metering cubicle for 3phase 4 wire metering system made of MS Sheet steel thickness not less than 2mm duly power coat painted suitable for indoor as well as outdoor as per the site requirement. The cubicle shall be painted through 7-tank process. The External dimensions should be adequate. Panel having two compartments upper Meter compartment and lower CT/PT compartment. Provided with synthetic or semi synthetic gasket firmly glued to the sufrace, Dust, weather and Vermin proof and shall comply degree of protection IP 65 both the chambers having one sided hinged door arrangments. The metering panel shall be provided with two No MS channels of size 100 x 50 mm on the front and rear sides duly welded and 4 No of lifting hooks. It should be possible to take meter reading manually, through CMRI and computer without opening the LV chamber door. | 2 | No | 100 | ₹200 |
| 1.02 | Single Phase, Single core, single ratio, Epoxy resin Cast Current Transformers suitable for 11kV, copper wound primary type with rated burden 5VA and accuracy class 0.5 or better and conforming to IS2705 (part-I & II) amended upto date. ISF shall be upto 5
The CT ratio shall be as under:
50/5 for 630kVA DT | 6 | No | 100 | ₹600 |
| 1.03 | 11kV/ 110 V, Three phase epoxy resin cast PT with rated burden 15VA per phase and accuracy class 0.5 or better and conforming to IS:3156 (part-I&II) amended upto date with proper colour coded identification. PTs shall be of uniform insulating and withstand separate source 23kV pf for one minute. | 2 | Set | 100 | ₹200 |
| 1.04 | Bus Bar details:
CTs bus bar:- 40x6 mm copper strip or adequate size
PTs bus bar: Copper wire 8 SWG or 30x0.6mm copper flat strip to connect PT terminal or adequate size
duly insulated by the monoplast tape | 2 | Lot | 100 | ₹200 |
| 1.05 | PVC Copper wire flexible multi-strand of required size for secondary connections for CT wiring the minimum wire size shall be 4 mm2 (RYB) and for PT wiring minimum wire size shall be 2.5 mm2 (RYB). | 2 | Lot | 100 | ₹200 |
| 1.06 | Copper Lugs preferably ring type duly crimped for termination of wires and tapes | 2 | Lot | 100 | ₹200 |
| 1.07 | Grounding bus of minimum 40mm copper, 25cm long fixed to the unit in HV chamber. The CTs, PT meter and 11kV Cable sheath shall be grounded to the bus through grounding wire (green) of min size 10mm2 | 2 | Lot | 100 | ₹200 |
| 1.08 | 3Ph3 Wire HT CT/PT operated Fully static Smart Tri-Vector Energymeters DLMS Compliant Category 'C' with RS232 port for modem compatibility. 11kV/110V, Ph-Ph (3P,3W) meters for measurement of different electrical parameters including Active Energy (kWh/ MWh), Reactive Energy (kVArh/MVArh), Apparent Energy (kVAh/ MVAh) etc. (make L&T, Secure, ABB) | 2 | No | 100 | ₹200 |
| 1.09 | Independent flexible PVC pipes for CT wiring and PT wiring of appropriate size from HT compartment to meter compartment | 2 | Lot | 100 | ₹200 |
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Tendernotice_1.pdf
PDF • 3.21 MB
Tendernotice_2.pdf
PDF • 1.82 MB
BOQ_1088124.xls
BOQ • 0.29 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .