Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | 1₹13.3 LAccepted-AOC | ₹13.3 L Quoted ₹13.8 L | 1 | Accepted-AOC Lowest tender |
| 2 | 2₹14.0 L+₹20,808 (1.51%)Rejected-AOC 110059 NEW DELHI NATIONAL CAPITAL TERRITORY OF DELHI 110059 | WEST DELHI | DELHI | 110059 | ₹14.0 L+₹20,808 (1.51%) | 2 | Rejected-AOC 2nd |
| 3 | Not Admitted-Fee/PreQual/Technical NA | NA | NA | 121004 | - | - | Not Admitted-Fee/PreQual/Technical Not Complied with technical specification |
Tender Value
₹17.5 L
EMD Value
₹35,000
Closing Date
21 Nov 2019, 6:00 pmClosed
GE AF TUGHLAKABAD
GE AF TUGHLAKABAD SANGAM VIHAR PO NEW DELHI 110080
Maint/Repair/Replacement of street lights, LT panels, LT underground cables and misc E/M works at Electric and Water supply installations at DGQA Complex Badarpur under GE (AF) Tughlakabad
2019_MES_282713_2
GE/TKD/EM/TOKEN-31/2019-20
Open Tender
Civil Works
Item Rate
330 days
GE AF TUGHLAKABAD
MES contractor enlisted as Class E category bi having deposited Standing Security of Rs. 50000 with dept. Contractors not enlisted in MES should meet the MES enlistment criteria corresponding to appropriate class and category
8 documents required · 8 mandatory
₹500
Yes
GE AF TUGHLAKABAD
₹35,000
Yes
3 Jun 2020
13 Nov 2019
23 Nov 2019
13 Nov 2019
21 Nov 2019
13 Nov 2019
Amount
M&L for lifting of submersible pump and motor using chain pully arrangement of suitable size and disconnecting the electric and water pipe connection for lifting and taking out the column pipe of dia 50 mm / 40 mm dia pipe from the bore well up to depth of 90 metre including submersible cable, submersible pump set of any capacity complete all as specified.
S&F in replacement of rusted GI column pipe Med Grade of size 50 mm dia (10 feet long) including flanged nut bolts, washer, gasket and welding works complete all as specified and directed by Engr-in-Charge.
S&F in replacement of Submersible cable PVC insulated copper conductor flat 3 core 4 Sqmm 1100 volt.
Lowering of the submersible pumping set with motor by using the chain pulley arrangement with fixing of column pipe of size 50 mm dia including nut, bolts, washers, and rubber gasket in replacement and tightening of submersible cable with pipe and connected submersible cable from existing panel board complete all as specified and directed by Engr-in-charge.
S&F in replacement of Gun metal gate valve of size 50 mm dia with iron wheel complete all as specified and directed by Engr-in-charge.
S&F in replacement of Gun metal gate valve of size 40 mm dia with iron wheel complete all as specified and directed by Engr-in-charge.
S&F in replacement of Gun metal gate valve of size 25 mm dia with iron wheel complete all as specified and directed by Engr-in-charge.
S&F in replacement of Gun metal gate valve of size 20 mm dia with iron wheel complete all as specified and directed by Engr-in-charge.
S&F in replacement of cast Iron sluice valve, class PN 1.6 with iron hand wheel, 80 mm bore size (IS:14846 marked), long body, both end flanged and drilled, including provisioning rubber gasket joint at both ends of the valve with necessary nuts, bolts and washers complete all as directed by the Engineer-in-charge.
S&F in replacement of cast Iron sluice valve, class PN 1.6 with iron hand wheel, 100 mm bore size(IS:14846 marked), long body, both end flanged and drilled, including provisioning rubber gasket joint at both ends of the valve with necessary nuts, bolts and washers complete all as directed by the Engineer-in-charge.
S&F in replacement of cast Iron sluice valve, class PN 1.6with iron hand wheel, 150 mm bore size (IS:14846 marked), long body, both end flanged and drilled, including provisioning rubber gasket joint at both ends of the valve with necessary nuts, bolts and washers complete all as directed by the Engr-in-charge.
M&L for supply, installation and testing for Maintenance free Grounding (Earthing) system complete buried directly in ground vertically (Earth pit not less than 10 feet below ground level) by making bore hole of 100 mm dia for inserting 01 No - 17MM dia Molecular copper bonded high tensile low carbon steel circular earth electrode of 3 mtr length with average copper thickness of 100 microns alongwith Environmental friendly grounding enhancing compound and heavy duty (HDPE) PVC pipe cap all in below the ground level and connected to copper earth wire of 2 mm dia by means of same metal bolts, nuts and washers etc including protection pipe of GI 15 mmm bore medium grade upto 7.5 metre length and connection of earth lead to main distribution/LT panel board with copper lugs complete all as specified and directed by Engr-in-charge. Note- (i) Necessary earth work, PVC pipe and required materials are deemed to be included in the above quoted rate. (ii) 01 x 25 Kg grounding enhancing compound with NABL certification along with conductivity testing is deemed to be included in the quoted rates. (iii) Necessary earth pit cover as per SSR Part-I is also deemed to be included in the quoted rates.
Taking down of existing pipe and S&F GI pipe of medium grade 80 mm with all necessary GI accessories and fittings laid under trenches/walls complete all as specified.
Taking down of existing pipe and S&F GI pipe of medium grade 50 mm with all necessary GI accessories and fittings laid under trenches/walls complete all as specified and as directed by Engr-in-Charge.
Taking down of existing pipe and S&F GI pipe of medium grade 25 mm with all necessary GI accessories and fittings laid under trenches/walls complete all as specified and as directed by Engr-in-Charge.
Taking down of existing pipe and S&F GI pipe of medium grade 20 mm with all necessary GI accessories and fittings laid under trenches/walls complete all as specified and as directed by Engr-in-Charge.
M&L for opening of submersible pump set upto 35 stage of capacity 5 HP,100mm dia (three phase) pump type 4 C/50 and replacement of the following unserviceable parts and re-fixing the same duly testing, commissioning complete all as specified and directed by Engr-in-charge. 1. Allon bolts - 4 Nos 2. Bearing bush in suction housing - 1 No 3. Bearing sleeves - 1 No 4. Bearing bush in stage casing - 4 Nos 5. Cable guards - 1 No 6. D.O.L - 1 No 7. D.O.L. Sleeves - 1 No 8. Distance sleeves in suction Housing - 1 No 9. D.O.L bush - 1 No 10. Impeller Noryl - 35 Nos 11. inlet - 1 No 12. Joining kit - 1 No 13. J Clamp/Jacket - 1 No 14. NRV Body - 1 No 15. NRV Cone - 1 No 16. Oil Seal - 2 Nos 17. Pump Coupling- 1 No 18. Pump shaft - 1 No 19. Inter mediate - 3 Nos 20. Intermediate bush - 3 Nos 21. Shaft sleeve - 2 Nos 22. Diffuser - 35 Nos 23. Suction housing - 1 No 24. Sand Guard- 1 No 25. Screw for cable Guard - 2 Nos 26. Square NW - 4 Nos 27. Strainer- 1 No 28. Drain plug - 2 Nos
M&L for rewinding of burnt submersible motor of 5 HP, 3 phase, 415 volt, 50 Hz of any make with water proof insulated copper conductor of same specification as per old one after dismantling /cutting out burnt windings from stator assembly, cleaning slots properly complete with insulating slots packing, sleeves, papers & re-assembling stator and rotor after replacement of the worn out spares/matching works including painting with two coats of synthetic enamel paint over a coat of red oxide primer duly preparation of external surfaces and water proof jointing for submersible cable of 3 core with replacement of oil seal sand guard, bolts and nuts, gasket and cable packing ring, bearing, bush etc complete all as specified and directed by Engr-in-charge.
M&L for dismantling of centrifugal pump of capacity 5 HP from the foundation and MS channel including disconnection of all electric connections and disconnection of suction and delivery pipe lines complete and repair to the pump at authorised work shop as required like rep/replacement of spares like seal kit, Outlet parts, male/female connections, couplings, gaskets, complete for making the pump fully serviceable complete all as directed by Engr-in-charge.
M&L for rewinding of burnt centrifugal motor of 5 HP capacity of any type and make of 3 phase and 415 volts, 50 Hz, AC type complete with rewinding with same gauge of super enamelled copper wire including all insulating materials, sleeves and insulation sheet and replacement of spare parts like ball bearing, bush and any other parts required to be fixed in the motor for fully serviceable complete all as directed by Engr-in-charge.
Dewatering the existing 20,000 ltr capacity, semi underground water supply sump by pumping and manual labour with necessary T&P and cleaning the same by way of taking out all scaling/silt/dirt deposition there in completely from bottom and side walls surfaces and from mouth of circulating pipes of UG sump, necessary brooming and brushing and marking the date of cleaning the sump periodically at the interval of 3 months including disinfectant using the bleaching powder complete all as specified and directed by Engr-in-charge.
M&L for Testing of drinking water by sample taken from any of the RO water delivering point of DGQA complex, badarpur from authorised testing laboratory registered with the NABL Deptt complete all as specified and directed by Engr-In-Charge.
M&L for servicing of RO system complete by checking all the parts of the plant including cleaning of RO membrane of 1000 LPH capacity and RO plant capacity 6000 LPH with the help of injecting RO membrane cleaning chemical of technical grade and of approved quality and cleaning should be performed to remove biological or organic foulants and membrane cleaning will be done individually complete making the system trouble free and entire satisfaction to the Engr-in-charge. Note: RO membrane cleaning chemicals as per NABL approved for removal of collodial deposits on RO membrane of qty 20 litres per servicing is deemed to be included in the above quoted rate. Make of existing RO system: Ion Exchange RO Plant
Supply of consumable anti scalene chemical for preventing scaling of membrane of RO plant.
Replacement of 30 Micron filter suitable for size 4 inch dia X 20 inch length with filter capacity upto 1 micron.
Supply of consumable PH booster chemical for RO plant (Human consumption grade superior quality).
Supply of consumable water treatment chemical Calcium Hypochlorite of granular type of all free chlorine chemical, (superior quality) complete all as specified.
Replacement of mechanical seal for 10 HP 3 Phase, 415 volt in high pressure pump installed at RO plant of capacity 6000 LPH complete all as specified.
Replacement of power contactor, 3 Phase, 415 Volt type ML-2 complete all as specified.
Replacement of RO membrane module size 8040 suitable for 6000 ltr per hour central RO Plant complete including taking out the old unserviceable membrane from the housing including testing and commissioning of the RO plant complete all as specified and directed by Engr-in-charge.
S&F MCB SPN 6-32 Amp, 10 KA, single phase 220 V, complete all as specified and directed by Engr-in-charge.
S&F MCB SP 6-32 Amp, 10 KA, single phase 220 V, complete all as specified and directed by Engr-in-charge.
Supply only the CP connection of PVC for inlet and outlet geyser with washers complete all as specified.
M&L for heating element delta type (triangle type) copper upto 25L, complete all as per directed by Engr-in-Charge
M&L for thermostat for geysers of capacity upto 25 L complete all as specified and directed by Engr-in-Charge
Dehydration and filtration of the existing transformer/servo voltage stabilizer oil by Dehydration plant to achieve di-electric strength of 40 KV at the gap of 4mm complete all as specified and directed by Engineer-in-charge. (Dehydration plant shall be brought at site by the Contractor) and shall also include the following provisions :- a) Testing of transformer /servo voltage stabilizer oil before & after dehydration shall be carried out as directed. b) The Unit of Payment under this item shall be paid per litre of oil meant for all processes to the entire completion of jobs.
Supply and filling transformer oil for topping up or replacement in different existing transformers outdoor/indoors type of any capacity located and installed at different places and different height complete all as specified. Note : - Transformer Oil :- The entire quantity of transformer oil shall be procured in one lot. The complete material shall be brought at site and then as per requirement oil should be shifted to site. The Purchase Vouchers of transformer oil will be verified by AGE personally and certificate for the supply of genuine transformer oil shall be kept on record. Cost of this aspect deemed to be included in the quoted rate.
Supply and replacement of dehydrating agents (Silica gel) in transformers of capacity upto 1000 KVA outdoor /indoor type complete all as specified and as directed by the Engineer-In-Charge.
Supply and replacement of HT bushing (Brass stud and bolts with porcelain insulator) suitable size to fix the transformer capacity range 500 KVA including replacement of gasket, cable glands, etc to make the transformer leak proof complete all as specified and as directed by Engr-in-charge.
Supply and replacement of LT bushing (Brass stud and bolts with porcelain insulator) suitable size to fix the transformer capacity range 500 KVA including replacement of gasket, cable glands, etc to make the transformer leak proof complete all as specified and as directed by Engr-in-charge.
S&F in replacement of cable end jointing kit and testing and commissioning for 11 KV (Earthed) grade cable for indoor termination heat shrink type joint complete with jointing material and accessories suitable for 3 core XLPE cable armoured aluminium conductor cable of size 120 Sqmm to 185 Sqmm.
M&L for cable jointing kit for 11 KV (Earthed) grade cable for straight through heat shrinkable type joint complete with jointing material and accessories suitable for 3 core XLPE armoured aluminium conductor cable of size 120 Sqmm to 185 Sqmm including earth work complete
S&F testing and commissioning in replacement heat shrinkable end termination straight through Jointing Kit suitable for LT Cable of size 25 Sq mm to 50 Sq mm, 3.5 core complete.
S&F testing and commissioning in replacement heat shrinkable end termination straight through Jointing Kit suitable for LT Cable of size 70 sq mm to 150 Sqmm, 3.5 core complete.
M&L for servicing /cleaning the DG set of capacity 125KVA Kirloskar make installed at main Receiving sub station complete, comprising of the following works duly Testing and commissioning after service complete all as specified and directed by Engg-in -charge. Note: Spare parts shall be measured and paid separately under relevant items. Make: Kirloskar
Supply of Fuel Filter Suitable for DG set of capacity 125KVA. Make: Kirloskar
Supply of oil Filter suitable for DG set of capacity 125KVA. Make: Kirloskar
Supply of Assembly of air cleaner suitable for 125 KVA DG Set.
Supply of hose for air cleaner suitable for 125 KVA DG Set.
Supply of stop solenoid Assembly energies to run 12 V two coil suitable for 125 KVA DG.
Supply of AVR Suitable for DG set of capacity 125KVA. Make: Kirloskar
Supply of air pipe (CAC To Air Inlet Manifold) suitable for DG set of capacity 125KVA. Make: Kirloskar
Supply of water pump assembly with pulley Suitable for DG set of capacity 125KVA. Make: Kirloskar
Supply of Injector assembly Suitable for DG set of capacity 125KVA. Make: Kirloskar
Supply of air inlet manifold (CI) suitable for 125 KVA DG Set.
Dismantling the unserviceable radiator and inter cooler of DG set of 125 KVA by unscrewing nut, bolts and cleaning the internal surface by wet cloth and depositing the same in MES store at Badarpur for safe custody all as directed by Engineer-In-Charge.
M&L for detect & brazing of leakage radiator tubing suitable for 125 KVA DG Set complete all as directed at site.
Re-fixing of the inter cooler with radiator assembly complete all as directed suitable for 125 KVA DG Set complete.
S&F of hose of water pipe in replacement all as directed at site suitable for 125 KVA DG Set complete. Make: Kirloskar
M&L for spray painting one coat for DG set capacity 125KVA including canopy and writing of SM/MES No installed at main Receiving sub station complete with colour all as specified and directed by Engg-in-charge.
Labour only for servicing of the diesel engine of 20/25 KVA at DGQA Badarpur and repair/replacement of the following components including testing all as specified and directed. Note: Spare parts required shall be measured and paid separately under relevant items. Make of existing DG Set: Kirloskar
Replacement of Element fuel filter pre
Replacement of Element fuel filter Micro
Replacement of Element LO filter 1.1 ltr
Replacement of O ring.
Replacement of Air cleaner assembly dry
Replacement of Flexible pipe engine to cooler
Replacement of Flexible pipe cooler to filter
Replacement of Radiator fan
Replacement of V Belt B-53
Replacement of Hose pipe thermostat to radiator
Replacement of Hose
Replacement of Fuel pipe
Replacement of L. O. supply pipe
Removing the old engine oil from the diesel engine sump of 20 KVA DG sets, cleaning the oil sump thoroughly, supply and fill new engine oil complete all as specified and directed by Engineer -in -Charge.
Taking out unserviceable Dynamo cap of 12 Volt from DG set and servicing of dynamo including replacement of slip-ring & carbon brushers and reassembling after repair and re-fixing the DG set complete all as specified and directed.
Disconnecting of complete radiator assembly cleaning of 20/25 KVA DG Set and de-scaling of chocked water tubes of radiator by pull through nylon brush and reassembling the same duly cleaning the fins of the radiator with acid including brazing of worn out copper tube and replacement of the worn out minor spares such as plain washer, spring washer, screw nut bolt joint rubber complete all as specified and directed by Engr-in-charge.
Supply and filling the water coolant (diluted) in radiator valve line or equivalent in golden crusher including removal of old water/coolant, all as directed by Engineer-in-Charge.
Charging of the battery of 12 Volt 180 AH by 1250 specific gravity Electrolyte by filling in each cell of battery with charging the battery for 12 hrs and testing complete all as specified and directed by Engr-in-charge.
Replacement of unserviceable AVR card of 20/25 KVA DG Set alternator complete all as specified. Make: Kirloskar
Replacement of electrically operated fuel shut down valve assembly suitable for 20/25 KVA DG Set testing and commissioning including dismantling and removal of old Unserviceable valves of any capacity DG set complete all as specified and directed by Engr.in-charge.
Dismantling the PT/FI pump assembly of 20/25 KVA DG set and repair/ overhauling/ calibrating in authorised lab including replacing the worn out rings, plunger, damper plate gasket etc. including, refixing, reconnecting, testing & commissioning complete all as specified and directed by Engr-in-charge.
Repair/overhauling of self starter including replacement of worn out clutch assembly, bush, spring, plunger assembly, solenoid switch, carbon brushes, brush spring etc for the 20/25 KVA DG Set complete all as specified and directed by Engr-in-charge.
S&F in replacement for commissioning of maintenance free battery 12V, 180 AH, for DG set 125 KVA, 25 KVA, 20 KVA, and solar light with copper battery terminals for wire connection complete all as specified and directed by Engr-in-Charge.
Taking down old unserviceable security light fittings from pole upto 11 mtr height and S&F new LED street light fitting of capacity 60 watt 5700K made up of pressure die cast housing with toughned glass and individual high power LEDs, IP66 protection and impact resistance of IK07 with all electrical accessories and complete all as specified. Make- Havells Cat part No- LHETBXU7PA6J060/ C&S Cat part No LTESS160WLED/Bajaj Cat No-BRTFG60WLEDV3
M&L for scrubbing old paint surface by removing old dirt etc from LT pole 9 mtr long and applying one coat of synthetic enamel paint upto 1.2 m height and there on one coat of synthetic enamel paint of silver colour on steel surfaces such as cross arms including writing of the pole number complete all as specified and directed by Engr-in-Charge.
M&L for replacement of MCCB capacity 400 Amps of 3 pole 415V, breaking capacity 35 KA complete all as specified and as directed by Engr-in-Charge. Make: Havells Cat No-IHL CNT0400/LEGRAND Cat No-422002/L&T Cat No-DH400SL978840000
M&L in replacement MCCB capacity 250 Amps of 4 pole 415V, breaking capacity 36 KA complete all as specified and as directed by Engr-in-Charge. Make : Havells Cat No-IHLCNF0250/LEGRAND Cat No-420249/L&T Cat No- DH250SL978830000
M&L in replacement MCCB capacity 200 Amps of 4 pole 415V, breaking capacity 36 KA complete all as specified and as directed by Engr-in-Charge. Make: Havells Cat No-IHLCNF0200/Legrand Cat No 420248/L&T Cat No DU200CM981110000
M&L in repalcement of MCCB capacity 160 Amps of 4 pole 415V, breaking capacity 36 KA complete all as specified and as directed by Engr-in-Charge.
Taking down the existing cable and Supply and lay LT underground cable of PVC insulated, armoured, heavy duty electric cable with aluminium conductor, 1100 volts grade, cross sectional area 25x4 sqmm complete all as directed by Engr-in-charge.
Taking down of existing cable and Supply and lay LT underground Cable PVC insulated, armoured heavy duty electric cable with aluminium conductor, 1100 volts grade, cross sectional area 35x4 sqmm complete all as directed by Engr-in-charge.
Taking down of existing cable and Supply and lay LT underground Cable PVC insulated, armoured heavy duty electric cable with aluminium conductor, 1100 volts grade, cross sectional area 95x3.5 sqmm complete all as directed by Engr-in-charge.
Excavation in trenches soft/loose soil not exceeding 1.5mtr wide in not exceeding 1.5mtr in depth for foundation etc or for shaft well, cesspits, manholes, fire hole etc not exceeding 10sqmm on plan and not exceeding 1.5mtr in depth and getting out complete all as specified and as directed by the Engr-In-Charge
Returning filling in including spreading, leveling, watering and well ramming in layers not exceeding 25cm complete all as specified and as directed by the Engineer-In-Charge
Removing excavated material not exceeding 50mtr and depositing where directed at a level not exceeding 1.5mtr above the starting point complete all as specified and as directed by the Engineer-In-Charge
M&L for sand cushioning in trenches as lauers for protection of LT underground cable including watering and consolidation all as mentioned in SSR Part-I complete all as specified. Note: Punned thickness only shall be measured for payment purpose.
Supply and laying well burnt sub class ‘B’ bricks, locally available in trenches for protection of underground cable complete all as specified.
S&F in replacement KWH metre with Polycarbonate box single phase type, current rating 5-60 amps, LCD display, class1.0, voltage range 230/240 volts, AC complete all as specified.
S&F Voltage stabiliser for auto operation, servo controlled single phase, naturally cooled, indoor type and designed for input variation between 170V to 230V with output voltage stabilized at 230 V with accuracy within +/- 2.5% and speed of correction 8V per section capacity 4 KVA.
M&L for Servicing of VCB of rating 400/630 Amps and 11 KV grade by authorized and verified company as approved by Engr-in-charge complete all as directed by Engr-in-charge. Make of existing VCB: ALSTOM (Type-VMX)
M&L for Servicing of ACB of rating 600 amps and 415 volts by authorized and verified company as approved by Engr-in-charge complete all as directed by Engr-in-charge. Make of existing ACB: ABB
S&F in replacement wall mounted fan 400/450 mm sweep, single phase, AC, 50 HZ supply, high speed, three blade type, copper motor type having auto thermal overload protection and designed for Indian weather conditions, jerk free and uniform oscillation with powder coated guards and suitable size pull cord for speed regulation and oscillation control of white in colour complete all as specified. Make: Model Swanky of Havells / Model -Snow Fall 16WB01 of Orient / Model- HELIX Pro High Speed Wall Fan of Usha
Taking out old unserviceable fitting and S&F wall mounted LED batten 20 watt, extruded aluminium heat sink provided for efficient heat dissipation & integrated electronic driver 230 Volt, including all accessories prewired and making necessary electrical connection with 3 core copper conductor and testing complete all as directed by Engr-in-charge. Make:Bajaj Cat Part No 830254, CCT22W/Havells Cat Part No LHEXBYPNINIW020/C&S Cat Part No -LTTB4F20WLED/W
S&F in replacement wall mounted LED batten 10 watt, extruded aluminium heat sink provided for efficient heat dissipation & integrated electronic driver, 230 Volt, including all accessories prewired and making necessary electrical connection with 3 core copper conductor and testing complete all as directed by Engr-in-charge. Make: Cat No- LHEWEBP6PL1W012 of Havells / Bajaj Cat Part No BCLSB10WH/C&S Cat Part No -LTTB2F10WLED/W
S&F in replacement of MCB Four pole higher rating MCB of 63 Amps capacity, 10 KA, 415 Volts complete including taking out old Unserviceable from existing DB all as specified and directed by Engr-in-charge.
S&F in replacement of MCB Four pole higher rating MCB of 100 Amps capacity, 10 KA, 415 Volts complete including taking out old Unserviceable from existing DB all as specified and directed by Engr-in-charge.
Taking out old Unserviceable street light timer switches and M&L, testing and commissioning for NATURE Switch for outdoor lighting automation using space grade sensors and an advances micro controller suitable for outdoor use having features Automatic Switching ON at Sunset, Automatic Switching OFF at dawn, No clock setting and time settings wide operating voltage range, High voltage trip and auto reset having specification 415 Volts, 50 Hz complete with all connected accessories of rating 12 KW 3 phase, current range 40 Amps all as specified. Make- Universal Switch Gear & Control System or equivalent in Havells/Kaktiya Energy System: Model No -SWADEEP66-12KW3P
M&L for Excavation by Trench less Boaring Technology for holes under the road, pavement, hard standing using Ultra sound technique and engaging necessary Machine including HDPE pipe of dia 50 MM suitable for 0.4 MPA working pressure complete all as specified and directed by Engr-in-charge. Note - HDPE pipe and making good the disturbed surface is deemed to be included in the rate quoted by the Contractor.
M&L in replacement of Digital panel mounted Voltmeter with bar graph made out of ABS plastic with dimensions 50x72x72 mm (LWH) and suitable for 415 Volts, 3 phase, 50 HZ AC supply complete all as specified and directed by Engr-in-charge. Note - Any alteration required at site to fix the voltmeter with existing LT panel is deemed to be included in the rate quoted by the contractor.
M&L in replacement of Digital panel mounted of Ammeter range 0-100 amps with bar graph made out of ABS plastic with dimensions 50x72x72 mm (LWH) and suitable for 415 Volts, 3 phase, 50 HZ AC supply complete all as specified and directed by Engr-in-charge. Note - Any alteration required at site to fix the voltmeter with existing LT panel is deemed to be included in rate quoted by the contractor.
M&L for repairing of solar light fitting complete by replacement of electronic control unit, solar control panel 12V, suitable for 15 watts capacity solar light, charge control unit, replacement of solar modules, including testing, commissioning complete all as specified and directed by Engr-in-charge. Note: Accessories like solar modules and solar control panels is deemed to be included in the rate quoted by the contractor. Battery and solar light shall be measured and paid Separately
S&F in replacement of maintenance free battery suitable for solar light fitting of 12 Volt and 50 AH complete all as specified.
M&L for repalcement of 15 watts LED solar street light water proof type from the existing solar pole of height 4/5 metre height complete all as specified. Make- Bajaj / Wipro / Havells
Taking down the old unserviceable MCCB DBs and M&L for distribution boards in sheet metal enclosure triple pole and neutral vertical Loadline 415 Volts 8 way, IP 43 of metal door type with 100 Amps MCCB, Double door type complete. Make for Distribution board: Cat Part NoDHDLVSRWG0G008 of Havells / Cat Part No DBVTL0088DD of L&T / Cat Part No 5077528W of Legrand Make of MCCB: L&T Cat No -DH100SL972090000/Legrand Cat No DRX100027008/Havells Cat No IHLGHT0100
Taking out the old unserviceable submain wiring of any size and type and M&L for sub main wiring with multistranded FRLS copper conductor cable PVC sheathed in and duly concealed with suitable PVC conduit and conduit accessories with two runs of 6.0 Sqmm and one run of 6.0 Sqmm FRLS copper conductor as earth wire and connected to earth dolly all as specified and as directed by Engr-in-Charge.
Taking out old unserviceable sub main wiring of any size and type and M&L for sub main wiring with multistranded FRLS copper conductor cable PVC sheathed in and including concealed suitable PVC conduit with two runs of 10.0 Sqmm and 1 run of 10.0 Sqmm FRLS copper conductor as earth wire and connected to earth dolly, the work includes cutting of Chasis and making good the disturbed surfaces and rate deemed to be included in quoted rate complete all as specified and as directed by Engr-in-Charge. Notes for sch items 104 & 105 (i) The work includes cutting of Chasis and making good the disturbed surfaces to match with surroundings complete. (ii) 2 runs of cable, 1 run of earth wire and 1 run of PVC conduit with accessories shall be measured as one unit of RM.
S&F LED lamp of 7 watt suitable for B22 base complete all as directed by Engr-in-charge.
S&F in replacement LED Flood light fitting 50 Watts fabricated with die-cast aluminium IP-65 flood light with high power LED as light source complete with all connected accessories and all as directed by the Engineer-in-Charge. Make: Cat Part No JETA COMPACT OF L50W LED 757LTG of Havells / Cat Part No LFBX11-50-CDL of Crompton Greaves / Cat Part No BJLF50WLEDI of Bajaj
M&L for providing cable indoor terminations suitable for HT cable 3 core of size 120-180 Sqmm terminated at HT VCB of 630 Amps complete after disconnections all the existing connections and removal of burnt/unserviceable cable terminations complete including taking of the VCB panel complete all as specified and directed by Engr-in-charge.
Notes: The amount of Rs 45,274.00 against schedule of credit given on Tender Serial Page No 50 shall be deducted from the total amount quoted by the contractor against BOQ while deriving the contract sum for acceptance.
V r traders
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .