REPAIRS/MAINT OF LT PANELS, SWITCHGEARS, ACBs AND ASSOCIATED WORKS IN TECH AREA AT AF STATION MAHARAJPUR
2020_MES_357115_1
8900/1249/GWL/E8
Open Tender
Electrical and Maintenance Works
Item Rate
180 days
GE AF TA GWALIOR
As per tender documents
7 documents required · 7 mandatory
₹500
GE AF TA GWALIOR
₹50,000
Yes
29 Aug 2020
1 Jul 2020
11 Aug 2020
1 Jul 2020
7 Aug 2020
16 Jul 2020
Amount
Dismantling of air circuit breaker of capacity from 630A to 1250 Amps of any pole/make/model from the panel, checking, servicing, cleaning of breaker with CRC-226, removal of old grease and re-greasing with recommended grease, checking the condition of moving and fixed contacts, checking the tripping mechanism, tripping of ACB manually through voltmetric release, adjust freeness of DN and volt metric release trip rod, checking the proper tightening of hardware, checking presence of all circlips, alignment of jaw contact with cradle terminals, checking the condition of ACB wiring, adjusting the gap between hylam sheet and side plate, checking the condition of arc chutes, under voltage relay, shunt release, auxillary contact, checking the release by secondary injection for O/L, S/C, E/F, setting of release as per the load, Checking the healthy ness of the CTs, complete all as specified and directed. Note :- Spares shall be measured and fwd separately under appropriate item in schedule as supply only.
M&L for rewiring of ACB with suitable copper wire as per existing including testing complete all as specified and directed.
Supply only following items suitable for ACB of any make and model of capacity 630 to 1250 Amp complete all as specified and directed.:- (a) Single phase polyester resin cast CTs of capacity 630/0.2A to 1250/2 Amp
(b) Compact UVT Coil upto 630-4000A for ACB of any make
(c) Shunt trip coil of any capacity for ACB of any make
(d) Door interlock for ACB of any make
(e) OCR (Fault) Alarm Switch suitable for ACB of existing make/capacity
(f) Trip indication switch (For manual tripping only)for ACB of any make
(g) 'Spring charged' indication switch for ACB of any make /capacity
(h) Position indicator switch for ACB of existing make/Capacity
(j) Main isolating contacts (Jaw contacts) of ACB draw out type of existing make/Model/capacity
(k) Drawout mould base (Cradle side) for ACB of existing make/capacity
(l) Main fixed contacts (Upper terminals) for ACB of existing make/model/capacity
(m) Lower terminals with fitting plates for ACB of existing make/capacity
(n) Circuit terminals/drawout terminals for ACB of existing make/capacity
(o) Main moving contact assembly for ACB of existing make/capacity
(p) Arc chutes for ACB of existing make/capacity
(q) Single pole unit for drawout type ACB of existing make/capacity
Supply, Installed, Testing and Commissioning CPRI approved cubical type LT Panel floor mounted out door type for 415V, 3 phase 4 wire system 50 Hz AC supply with Copper bus bar duly colour coded, for neutral supported with DMC/SMC insulators colour coded with heat shrinkable sleeve having short circuit current with stand minimum 21 KA for one second complete connection from bus bar to breakers with suitable copper cable , factory made fabricated with CRCA sheet totally enclosed, dust weather and vermin proof for outer sehell and 2 mm thick for inner shell having TPN cpper bus bar rating 1.5 times that of controlling MCCB supported on SMC insulator with short circuit withstand capacity 35 MVA for 1 second, bottom base channel MS section not less than 100mm x 50mm x 5 mm thick, entire panel shall have a common copper earth bar of size 25mm x 5mm at the rear with 2 Nos earth stud, solid connection from main bus bar to switchgears with required size of copper wiring with minimum 1.5 Sqmm PVC insulated copper conductor cable , cable alleys, cable gland plates in two half inculding tamper proof digital energy meter to measure volatge current PF, KWH,KVAH,KVAR (amke secure/L&T/HL/Schneider) and general construction confirming to IS-8623/93 and mounted on suitable PCC foundation for the complete panel base with follwoing detailed specification & control :- complete with suitable fixing accessories.
OUTER SHELL :- The outer shell shall be made of 3. mm thick CRCA body & MS angle section 50x50x6 mm frame with front & back openable, single door system lockable/ openable by keys from both sides having flush pattern fancy locks with louvers & air vent gasket for natural flow of air. The bottom of the outer shell contains a detachable plate ahing provision for entry of armoured cable of adequite size of glands. The dimension of the outer shell should be adequite to accododate inner shell described below figing 50 mm space all around and shall be fabricated in such a way that the comple inner shell alongiwth its control gears and accessories should be taken outside without disturbing outer sheel. The outer shell shall be mounted on a zinc metal coated stand. Provision of threaded earthing studs at bottom and lifting lugs of suitable size at top to lift the feeder pillar box safely shall be made. Computer cut self adhesive vinly danger notice plate having conventional symbol of bone and skull shall be providid. The degree of protection of outer shell shall be IP-54.
INNER SHELL :- Inner shell made of 2.0 mm thick CRCA body compartmentalized for each control gear, front openable single door system lockable/openable by keys from both sides having chromium plated fancy locks (2 Nos in each compartment) having louvers and air vents gasket for natural flow of air "U' type gasket shall be used to make the inner shell completely vermin proof and to accomodate incomer/outgoing MCCB's and TPN copper bus bar and extension links of rating not less than the 1.5 times rated capacity of the respective MCCB's. The TPN bus bar and extension links shall be insulated with colour coaded heat, shrikable sleeve and shall be mmounted on suitable size 'F' class through out the length of the TPN bus bar. Computer cut slef adhesive vinyl danger notice plate having conventional symbol of bone and skull shall be providid on bus bar chamber. All control wires shall be with not less than 1.5 Sqmm multistranded copper conductor and shall be properly bunched. tied, ferruled for proper identification and crimped with adequite size of lugs. The cubical shall have a bottom channel of size 75x50mm duly coated with zinc metal coating. A detachable predrilled gland plate of thickness 3.15 mm zinc metal coated should be used at the bottom, indicating lamps LED type, 230 Volt, AC at the incomer of the unit to show three phase availablity at the incomer. An inspection lamp with 11 Watt CFL shall be fitted on top side of inner shell. The degree of protection for inner shell shall be IP-42 and carrly the floowing control :-
(A) Incoming :-
(a) ACB 4P,800A, 65KA -01 No to be fixed from the existing panel after proper dismantling. (c) Indicating lamps for three phases - Qty 1 set of 3 Nos (e) Power lamp inside the panel alongwith connection from incoming power supply .
(B) Out going :-
(a) MCCB 4P, 630A, 50KA -02No (Adjustable magnetic type) Make - Legrand. (b) MCCB 4P, 200A, 25KA -01No (Adjustable magnetic type) Make - Legrand. (c) MCCB 4P, 100A, 16KA -01No (Adjustable magnetic type) Make - Legrand. . Note :- The rate includes the earth work and PCC for grouting the panel ablove 60 cm from the ground level.
Supply, Installed, Testing and Commissioning CPRI approved cubical type LT Panel floor mounted out door type for 415V, 3 phase 4 wire system 50 Hz AC supply with Copper bus bar duly colour coded, for neutral supported with DMC/SMC insulators colour coded with heat shrinkable sleeve having short circuit current with stand minimum 21 KA for one second complete connection from bus bar to breakers with suitable copper cable , factory made fabricated with CRCA sheet totally enclosed, dust weather and vermin proof for outer sehell and 2 mm thick for inner shell having TPN cpper bus bar rating 1.5 times that of controlling MCCB supported on SMC insulator with short circuit withstand capacity 35 MVA for 1 second, bottom base channel MS section not less than 100mm x 50mm x 5 mm thick, entire panel shall have a common copper earth bar of size 25mm x 5mm at the rear with 2 Nos earth stud, solid connection from main bus bar to switchgears with required size of copper wiring with minimum 1.5 Sqmm PVC insulated copper conductor cable , cable alleys, cable gland plates in two half inculding tamper proof digital energy meter to measure volatge current PF, KWH,KVAH,KVAR (amke secure/L&T/HL/Schneider) and general construction confirming to IS-8623/93 and mounted on suitable PCC foundation for the complete panel base with follwoing detailed specification & control :- complete with suitable fixing accessories.
OUTER SHELL :- The outer shell shall be made of 3. mm thick CRCA body & MS angle section 50x50x6 mm frame with front & back openable, single door system lockable/ openable by keys from both sides having flush pattern fancy locks with louvers & air vent gasket for natural flow of air. The bottom of the outer shell contains a detachable plate ahing provision for entry of armoured cable of adequite size of glands. The dimension of the outer shell should be adequite to accododate inner shell described below figing 50 mm space all around and shall be fabricated in such a way that the comple inner shell alongiwth its control gears and accessories should be taken outside without disturbing outer sheel. The outer shell shall be mounted on a zinc metal coated stand. Provision of threaded earthing studs at bottom and lifting lugs of suitable size at top to lift the feeder pillar box safely shall be made. Computer cut self adhesive vinly danger notice plate having conventional symbol of bone and skull shall be providid. The degree of protection of outer shell shall be IP-54.
INNER SHELL :- Inner shell made of 2.0 mm thick CRCA body compartmentalized for each control gear, front openable single door system lockable/openable by keys from both sides having chromium plated fancy locks (2 Nos in each compartment) having louvers and air vents gasket for natural flow of air "U' type gasket shall be used to make the inner shell completely vermin proof and to accomodate incomer/outgoing MCCB's and TPN copper bus bar and extension links of rating not less than the 1.5 times rated capacity of the respective MCCB's. The TPN bus bar and extension links shall be insulated with colour coaded heat, shrikable sleeve and shall be mmounted on suitable size 'F' class through out the length of the TPN bus bar. Computer cut slef adhesive vinyl danger notice plate having conventional symbol of bone and skull shall be providid on bus bar chamber. All control wires shall be with not less than 1.5 Sqmm multistranded copper conductor and shall be properly bunched. tied, ferruled for proper identification and crimped with adequite size of lugs. The cubical shall have a bottom channel of size 75x50mm duly coated with zinc metal coating. A detachable predrilled gland plate of thickness 3.15 mm zinc metal coated should be used at the bottom, indicating lamps LED type, 230 Volt, AC at the incomer of the unit to show three phase availablity at the incomer. An inspection lamp with 11 Watt CFL shall be fitted on top side of inner shell. The degree of protection for inner shell shall be IP-42 and carrly the floowing control :-
(A) Incoming :-
(a) ACB 4P,800A, 65KA -01 No to be fixed from the existing panel after proper dismantling. (c) Indicating lamps for three phases - Qty 1 set of 3 Nos (e) Power lamp inside the panel alongwith connection from incoming power supply .
(B) Out going :-
(a) MCCB 4P, 630A, 50KA -03No (Adjustable magnetic r type) Make - Legrand. (b) MCCB 4P, 250A, 36KA -01No (Adjustable magnetic type) Make - Legrand. Note :- The rate includes the earth work and PCC for grouting the panel ablove 60 cm from the ground level.
Supply, Installed, Testing and Commissioning CPRI approved cubical type LT Panel floor mounted out door type for 415V, 3 phase 4 wire system 50 Hz AC supply with Copper bus bar duly colour coded, for neutral supported with DMC/SMC insulators colour coded with heat shrinkable sleeve having short circuit current with stand minimum 21 KA for one second complete connection from bus bar to breakers with suitable copper cable , factory made fabricated with CRCA sheet totally enclosed, dust weather and vermin proof for outer sehell and 2 mm thick for inner shell having TPN cpper bus bar rating 1.5 times that of controlling MCCB supported on SMC insulator with short circuit withstand capacity 35 MVA for 1 second, bottom base channel MS section not less than 100mm x 50mm x 5 mm thick, entire panel shall have a common copper earth bar of size 25mm x 5mm at the rear with 2 Nos earth stud, solid connection from main bus bar to switchgears with required size of copper wiring with minimum 1.5 Sqmm PVC insulated copper conductor cable , cable alleys, cable gland plates in two half inculding tamper proof digital energy meter to measure volatge current PF, KWH,KVAH,KVAR (amke secure/L&T/HL/Schneider) and general construction confirming to IS-8623/93 and mounted on suitable PCC foundation for the complete panel base with follwoing detailed specification & control :- complete with suitable fixing accessories.
OUTER SHELL :- The outer shell shall be made of 3. mm thick CRCA body & MS angle section 50x50x6 mm frame with front & back openable, single door system lockable/ openable by keys from both sides having flush pattern fancy locks with louvers & air vent gasket for natural flow of air. The bottom of the outer shell contains a detachable plate ahing provision for entry of armoured cable of adequite size of glands. The dimension of the outer shell should be adequite to accododate inner shell described below figing 50 mm space all around and shall be fabricated in such a way that the comple inner shell alongiwth its control gears and accessories should be taken outside without disturbing outer sheel. The outer shell shall be mounted on a zinc metal coated stand. Provision of threaded earthing studs at bottom and lifting lugs of suitable size at top to lift the feeder pillar box safely shall be made. Computer cut self adhesive vinly danger notice plate having conventional symbol of bone and skull shall be providid. The degree of protection of outer shell shall be IP-54.
INNER SHELL :- Inner shell made of 2.0 mm thick CRCA body compartmentalized for each control gear, front openable single door system lockable/openable by keys from both sides having chromium plated fancy locks (2 Nos in each compartment) having louvers and air vents gasket for natural flow of air "U' type gasket shall be used to make the inner shell completely vermin proof and to accomodate incomer/outgoing MCCB's and TPN copper bus bar and extension links of rating not less than the 1.5 times rated capacity of the respective MCCB's. The TPN bus bar and extension links shall be insulated with colour coaded heat, shrikable sleeve and shall be mmounted on suitable size 'F' class through out the length of the TPN bus bar. Computer cut slef adhesive vinyl danger notice plate having conventional symbol of bone and skull shall be providid on bus bar chamber. All control wires shall be with not less than 1.5 Sqmm multistranded copper conductor and shall be properly bunched. tied, ferruled for proper identification and crimped with adequite size of lugs. The cubical shall have a bottom channel of size 75x50mm duly coated with zinc metal coating. A detachable predrilled gland plate of thickness 3.15 mm zinc metal coated should be used at the bottom, indicating lamps LED type, 230 Volt, AC at the incomer of the unit to show three phase availablity at the incomer. An inspection lamp with 11 Watt CFL shall be fitted on top side of inner shell. The degree of protection for inner shell shall be IP-42 and carrly the floowing control :-
(A) Incoming :-
(a) MCCB, 4P,315A, 36KA -01 (Adjustable magnetic type) Make - Legrand. (c) Indicating lamps for three phases - Qty 1 set of 3 Nos (e) Power lamp inside the panel alongwith connection from incoming power supply .
(B) Out going :-
(a) MCCB 4P, 160A, 16KA -4 No (Adjustable magnetic type) Make - Legrand. (b) MCCB 4P, 63A, 16KA -03 No (Adjustable magnetic type) Make - Legrand. (c) MCCB 4P, 40A, 16KA -02 No (Adjustable magnetic type) Make - Legrand. Note :- The rate includes the earth work and PCC for grouting the panel ablove 60 cm from the ground level.
Supply, Installed, Testing and Commissioning CPRI approved cubical type LT Panel floor mounted out door type for 415V, 3 phase 4 wire system 50 Hz AC supply with Copper bus bar duly colour coded, for neutral supported with DMC/SMC insulators colour coded with heat shrinkable sleeve having short circuit current with stand minimum 21 KA for one second complete connection from bus bar to breakers with suitable copper cable , factory made fabricated with CRCA sheet totally enclosed, dust weather and vermin proof for outer sehell and 2 mm thick for inner shell having TPN cpper bus bar rating 1.5 times that of controlling MCCB supported on SMC insulator with short circuit withstand capacity 35 MVA for 1 second, bottom base channel MS section not less than 100mm x 50mm x 5 mm thick, entire panel shall have a common copper earth bar of size 25mm x 5mm at the rear with 2 Nos earth stud, solid connection from main bus bar to switchgears with required size of copper wiring with minimum 1.5 Sqmm PVC insulated copper conductor cable , cable alleys, cable gland plates in two half inculding tamper proof digital energy meter to measure volatge current PF, KWH,KVAH,KVAR (amke secure/L&T/HL/Schneider) and general construction confirming to IS-8623/93 and mounted on suitable PCC foundation for the complete panel base with follwoing detailed specification & control :- complete with suitable fixing accessories.
OUTER SHELL :- The outer shell shall be made of 3. mm thick CRCA body & MS angle section 50x50x6 mm frame with front & back openable, single door system lockable/ openable by keys from both sides having flush pattern fancy locks with louvers & air vent gasket for natural flow of air. The bottom of the outer shell contains a detachable plate ahing provision for entry of armoured cable of adequite size of glands. The dimension of the outer shell should be adequite to accododate inner shell described below figing 50 mm space all around and shall be fabricated in such a way that the comple inner shell alongiwth its control gears and accessories should be taken outside without disturbing outer sheel. The outer shell shall be mounted on a zinc metal coated stand. Provision of threaded earthing studs at bottom and lifting lugs of suitable size at top to lift the feeder pillar box safely shall be made. Computer cut self adhesive vinly danger notice plate having conventional symbol of bone and skull shall be providid. The degree of protection of outer shell shall be IP-54.
INNER SHELL :- Inner shell made of 2.0 mm thick CRCA body compartmentalized for each control gear, front openable single door system lockable/openable by keys from both sides having chromium plated fancy locks (2 Nos in each compartment) having louvers and air vents gasket for natural flow of air "U' type gasket shall be used to make the inner shell completely vermin proof and to accomodate incomer/outgoing MCCB's and TPN copper bus bar and extension links of rating not less than the 1.5 times rated capacity of the respective MCCB's. The TPN bus bar and extension links shall be insulated with colour coaded heat, shrikable sleeve and shall be mmounted on suitable size 'F' class through out the length of the TPN bus bar. Computer cut slef adhesive vinyl danger notice plate having conventional symbol of bone and skull shall be providid on bus bar chamber. All control wires shall be with not less than 1.5 Sqmm multistranded copper conductor and shall be properly bunched. tied, ferruled for proper identification and crimped with adequite size of lugs. The cubical shall have a bottom channel of size 75x50mm duly coated with zinc metal coating. A detachable predrilled gland plate of thickness 3.15 mm zinc metal coated should be used at the bottom, indicating lamps LED type, 230 Volt, AC at the incomer of the unit to show three phase availablity at the incomer. An inspection lamp with 11 Watt CFL shall be fitted on top side of inner shell. The degree of protection for inner shell shall be IP-42 and carrly the floowing control :-
(A) Incoming :-
(a) MCCB, 4P,400A, 36KA -01 (Electronic/Microprocesssor type) Make - Legrand. (c) Indicating lamps for three phases - Qty 1 set of 3 Nos (e) Power lamp inside the panel alongwith connection from incoming power supply .
(B) Out going :-
(a) MCCB 4P, 250A, 36KA -1No (Adjustable magnetic type) Make - Legrand. (b) MCCB 4P, 200A, 36KA -01No (Adjustable magnetic type) Make - Legrand. (c) MCCB 4P, 100A, 16KA -02No (Adjustable magnetic type) Make - Legrand. Note :- The rate includes the earth work and PCC for grouting the panel ablove 60 cm from the ground level.
Supply, Installed, Testing and Commissioning CPRI approved cubical type LT Panel floor mounted out door type for 415V, 3 phase 4 wire system 50 Hz AC supply with Copper bus bar duly colour coded, for neutral supported with DMC/SMC insulators colour coded with heat shrinkable sleeve having short circuit current with stand minimum 21 KA for one second complete connection from bus bar to breakers with suitable copper cable , factory made fabricated with CRCA sheet totally enclosed, dust weather and vermin proof for outer sehell and 2 mm thick for inner shell having TPN cpper bus bar rating 1.5 times that of controlling MCCB supported on SMC insulator with short circuit withstand capacity 35 MVA for 1 second, bottom base channel MS section not less than 100mm x 50mm x 5 mm thick, entire panel shall have a common copper earth bar of size 25mm x 5mm at the rear with 2 Nos earth stud, solid connection from main bus bar to switchgears with required size of copper wiring with minimum 1.5 Sqmm PVC insulated copper conductor cable , cable alleys, cable gland plates in two half inculding tamper proof digital energy meter to measure volatge current PF, KWH,KVAH,KVAR (amke secure/L&T/HL/Schneider) and general construction confirming to IS-8623/93 and mounted on suitable PCC foundation for the complete panel base with follwoing detailed specification & control :- complete with suitable fixing accessories.
OUTER SHELL :- The outer shell shall be made of 3. mm thick CRCA body & MS angle section 50x50x6 mm frame with front & back openable, single door system lockable/ openable by keys from both sides having flush pattern fancy locks with louvers & air vent gasket for natural flow of air. The bottom of the outer shell contains a detachable plate ahing provision for entry of armoured cable of adequite size of glands. The dimension of the outer shell should be adequite to accododate inner shell described below figing 50 mm space all around and shall be fabricated in such a way that the comple inner shell alongiwth its control gears and accessories should be taken outside without disturbing outer sheel. The outer shell shall be mounted on a zinc metal coated stand. Provision of threaded earthing studs at bottom and lifting lugs of suitable size at top to lift the feeder pillar box safely shall be made. Computer cut self adhesive vinly danger notice plate having conventional symbol of bone and skull shall be providid. The degree of protection of outer shell shall be IP-54.
INNER SHELL :- Inner shell made of 2.0 mm thick CRCA body compartmentalized for each control gear, front openable single door system lockable/openable by keys from both sides having chromium plated fancy locks (2 Nos in each compartment) having louvers and air vents gasket for natural flow of air "U' type gasket shall be used to make the inner shell completely vermin proof and to accomodate incomer/outgoing MCCB's and TPN copper bus bar and extension links of rating not less than the 1.5 times rated capacity of the respective MCCB's. The TPN bus bar and extension links shall be insulated with colour coaded heat, shrikable sleeve and shall be mmounted on suitable size 'F' class through out the length of the TPN bus bar. Computer cut slef adhesive vinyl danger notice plate having conventional symbol of bone and skull shall be providid on bus bar chamber. All control wires shall be with not less than 1.5 Sqmm multistranded copper conductor and shall be properly bunched. tied, ferruled for proper identification and crimped with adequite size of lugs. The cubical shall have a bottom channel of size 75x50mm duly coated with zinc metal coating. A detachable predrilled gland plate of thickness 3.15 mm zinc metal coated should be used at the bottom, indicating lamps LED type, 230 Volt, AC at the incomer of the unit to show three phase availablity at the incomer. An inspection lamp with 11 Watt CFL shall be fitted on top side of inner shell. The degree of protection for inner shell shall be IP-42 and carrly the floowing control :-
(A) Incoming :-
(a) MCCB, 4P,315A, 36KA -01 (Adjustable magnetic type) Make - Legrand. (c) Indicating lamps for three phases - Qty 1 set of 3 Nos (Adjustable magnetic type) Make - Legrand. (e) Power lamp inside the panel alongwith connection from incoming power supply .
(B) Out going :-
(a) MCCB 4P, 100A, 16KA -3No (Adjustable magnetic type) Make - Legrand. (b) MCCB 4P, 63A, 16KA -03No (Adjustable magnetic type) Make - Legrand. (c) MCCB 4P, 40A, 16KA -01No (Adjustable magnetic type) Make - Legrand. Note :- The rate includes the earth work and PCC for grouting the panel ablove 60 cm from the ground level.
Supplying ,Laying, jointing and testing XLPE insulated, armoured, heavy duty, aluminum conductor cable 1100 volts grade ,laid in trenches/ducts, floors, fixed to walls etc. complete all as specified and directed for the following sizes :-. Make :- Havells/Plaza/Poly cab/Finolex (a) 16 Sqmm 4 core
(b) 35 Sqmm, 3.5 Core
(c) 70 Sqmm, 3.5 Core
(d) 120 Sqmm 3.5 Core
Checking, Supplying, fixing, jointing and testing for provision of straight through joints Heat shrinkable type, suitable for XLPE, LT Cable, 1100 Volts grade, for the following sizes of cables all as specified and directed.
(a) 16 Sqmm to 16 Sqmm any core
(b) 35 Sqmm to 35 Sqmm 3.5 core
(c) 70 - 95Sqmm 3.5 core
(d) 120 -185 Sqmm 3.5 core
Supplying, laying & jointing GI tubing, 80 mm bore, light grade as in sleeving etc laid in trenches / ducts / horizontal bore hole complete all as specified and directed.
Excavation in trenches n exc 1.5 mtr wide and n exc 1.5 mtr depth for foundation and laying of cable and getting out in any type soil etc complete all as specified and directed.
Returning, filling in, including spreading, levelling watering and well ramming in layers n.exc 25cm in soft/loose soil etc complete as specified and directed
Removing excavated material to a distance n.exc 50 mtr and depositing where directed at a level n.exc 1.5 mtr above the starting point.
M&L for dry river sand in trenches for cable cushioning & protection including spreading, ramming all as specified and directed.
Supply & Laying precast PCC cable concrete cable cover LV low voltage type -I flat size 250 mm x 150 mm x 40 mm complete all as specified and directed by Engr-in-charge.
M&L for earthing complete with galvanised steel earth plate electrode 60cm x 60 cm x 6.3 mm thick buried directly in ground (earth pit not less than 2.25m below ground level) with top edge of the plate not less than 1.5m below ground level connected to and including galvanised iron strip 32x6 mm as earthing lead by means of GI bolts nuts check nuts and washers of galvanised iron or steel all as shown in electric plate No 5 SSR Part-I, connected to earthing etc all as specified including testing on completion with all necessary excavation in any kind of strata, earth work, PCC earth Pit in 1:3:6 CI RCC cover, CI funnel, GI watering Pipe 20 mm complete.
Note :- (i) The length of the GI strip beyond 7.5m will be measured and paid seperately. (ii) Test result of earthing to be submitted by the contractor for all earthing . (iii) The rate quoted by the contractor shall also be deemed to be including :- (a) Testing submission of earth result as desired. (b) Excavation upto 3 mtrs depth and returning filling in any type of soil
M&L for earth continuity conductor or main earthing lead fixed to wall on batten or recess or chases or buried in ground or drawn in conduit/pipe or fixed to poles or any other indicated situation for loop earthing etc, as required of size 32 x 6mm galvanised iron strip complete all as specified and directed.
S&F in repairs aluminum conductor steel reinforced ACSR of sizes on electric poles by proper jumpring and binding all as directed proper including dismantling of old u/s ACSR
S&F in repairs for insulator pin type porcelain vitreous white / brown / green including one galvanised mild steel spindle two galvanised iron washers and one galvanised iron nut 100mm height 65mm dia suitable for working pressure 1100 volts grade
S&F in repairs for shackle type insulator porcelain , vitreous 100mm high and 115 mm dia complete including glavanised mild steel straps, washer, insulator bolts and nuts suitable for 1100 volts grade.
S&F in repairs for stay wire galvanised strand size 7/3.15mm complete all as specified and directed.
S&F in repairs stay assembly complete with 16mm dia stay rod accessories shown in electric plate No 1. Note :- (Loop insulator, stay clamp excavation and concrete measured and paid separately)
S&F in reapirs for loop type insulator vitreous porcelain white/brown green small size with overall dimension 65x90mm, clearance of hole 16mm for fixing on stay wire .
S&F in repairs for earth wire, cradles, hexagonal/ rectangular, fabricated with galvanized steel earth wire 4 mm dia for LT OH line all as directed.
S&F in repairs cross arms bracings supports clamps & back plates anti climbing device spoke type fabricated from structural steel sections including nuts, bolts washers welding bending cold or hot drilling holes for bolts in any shape or size as indicated or directed & inclusive of one primer coat, one under coat & one finishing coat of paint all as directed.
M&L for PCC (1:4:8) (using 40mm graded aggregate) type D2 for foundation of poles struts & stay assembly etc all as specified & directed.
M&L for PCC (1:3:6) type C1 in coping of poles etc (using 20mm graded coarse aggregate) including fair finishing the exposed surface even and smooth without using extra cement and necessary form work all as specified and directed.
Supply and fixing of MS Junction boxes of size 600mm X 400mm X 200mm depth, fabricated with 3.15mm thick MS sheets duly painted with two coats of synethic enamelled paint over a coat of red oxide primer fixed plinth with nut, bolt, washers including 4 No aluminium bus bars 100Amps on insulators and locking arrangement with steel sliding bolts including connecting cables with suitable lugs complete all as specified and directed.
Shiva Traders
M/s Anupam Construction Co.
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .