Executive Engineer , Kalimpong Electrical Division
Office of the Executive Engineer, PWD Kalimpong Electrical Division Upper Cart Road, Near DM Bungalow Kalimpong-734301
Electrical Repairing and Renovation Work at Main Building and Hostels of Centre for Co Operative Management , Kalimpong.
2025_WBPWD_946558_1
WBPWD/EE/KED/e-NIQ- 07 of 2025-26
Open Tender
ELECTRICAL WORKS ORG
Item Rate
45 days
Kalimpong
Please refer Tender documents.
4 documents required · 4 mandatory
₹87,000
Yes
21 Jan 2026
12 Nov 2025
8 Dec 2025
12 Nov 2025
5 Dec 2025
12 Nov 2025
Supplying & Laying of Cable :-Supply of 2/4 Core XLPE Insulated & Sheathed Armoured stranded Aluminium Conductor cables for Working Voltage up to 1100 Volts of following sizes [Make Polycab / RR /KEI/ Havells/ Gloster as approved by E.I.C]
2 core 10 sq. mm.
4 core 25 sq. mm.
4 core 35 sq. mm.
Laying of cable upto 2 core 25 sqmm on wall/surface incl. S & F MS saddles with earthing attachment in 10 SWG GI (Hot Dip) Wire, making holes etc. as necy. mending good damages and painting
2 core 10 sq. mm.
Laying of one No. cable upto 35 sqmm in underground trench 460 mm wide x 760 mm average depth, with brick protection on the top of the cable with 8 (eight) Nos. bricks per metre, including filling the space between the brick & cable and also the trench with shifted soil, leveling up and restoring surface duly rammed (For 4 core 25 Sq. mm cable)
Supplying and fixing compression type gland complete with brass gland, brass ring & rubber ring for dust & moisture-proof entry of XLPE/PVC armoured cables as below :
2 core 10 sq. mm.
4 core 25 sq. mm.
4 core 35 sq. mm.
Finishing the end of following XLPE/PVC armoured cables by crimping method incl. supplying and fixing solderless socket (Dowels make), tapes, anticorrosive paste & jointing materials :
2 core 10 sq. mm.
4 core 25 sq. mm.
4 core 35 sq. mm.
GI Pipe Protection
S&F medium gauge 32mm dia GI Pipe (ISI-Medium) Protection with necessary fittings and jointing metarials as required as per GS. [PWD/GS Page: F-6 Item: 11]
S&F medium gauge 40mm dia GI Pipe (ISI-Medium) Protection with necessary fittings and jointing metarials as required as per GS. [PWD/GS Page: F-6 Item: 11]
Earthing Installation – with Pipe Electrode :
Earthing with 50 mm dia GI pipe 3.64 mm thick x 3.04 Mts. long and 1 x 4 SWG GI (Hot Dip) wire (4 Mts. long), 13 mm dia x 80 mm long GI bolts, double nuts, double washers incl. S & F 15 mm dia GI pipe protection (1 Mts. long) to be filled with bitumen partly under the ground level and partly above ground level driven to an average depth of 3.65 Mts. below the ground level as below: By ISI-Medium GI pipe
Excavation of soil for installation of Earth Electrode and filling & ramming. (For Morrum Soil)
Extra for providing masonery enclosure on the top of the earth electrode of overall size 86.36 cm x 86.36 cm x 46 cm deep (below Ground level) complete with cemented brick work(1:6) of 25 cm width duly plastered with cement morter (inside) CI hinged inspection cover of size 36.56 cm x 35.56 cm with locking arrangement, GI reducer including drilling of 46 nos. 12 mm dia holes on the GI pipe.
Extra treatment of soil by using salt & charcoal for pipe electrode as to G.S.
Supply & fixing earth busbar of galvanized (Hot dip) MS flat 65 mm x 8 mm on wall having clearence of 6 mm from wall incl. providing drilled holes on the busbar complete with GI bolts, nuts, washers, spacing insulators etc. as required.
Connecting the equipments body to earth busbar incl. S & F 50 mm x 6 mm Galvanized (Hot Dip) MS flat on wall/floor with GI saddle as required and connection to equipments with incl. drilling holes, bolts, nuts,washers etc.
Supplying and fixing 240/415 V MCB of Breaking capacity 10kA & C characteristics on din rail of existing DBs and necessary connectionas per GS [Make: Legrand / ABB /SIEMENS/Schneider/L&T]
63A FP MCB
63A TP MCB
32A DP MCB
6-32A SP MCB
Average run 8 mtr
Average run 10 mtr
On board 6 A
Polythene pipe and wires:-
Cutting Channel of size (40 mm x 40 mm) on masonry wall by Electric operated cutting machine incl. supplying & fixing heavy gauge 19 mm, 3 mm thick Polythene pipe by means of anchoring chemical (Hilti/Sika) and GI 'U' hooks of 8 SWG incl. supplying and drawing 18 SWG GI wire as Fish wire and mending good damages to original finish by using own tools and tackles (a) 19 mm dia 3 mm thick polythene pipe without earth continuity wire
Supplying and Drawing 1.1 KV single core stranded 'FR' PVC insulated & unsheathed single core stranded copper wire (Brand approved by EIC) of the following sizes in the 19mm/25mm prelaid polythene pipe/PVC rigid conduit as per GS. [Make- Finolex/Polycab/RR Kabel/KEI]
3 x 22/0.3 (1.5 sqmm) as ECC
2x36/0.3 (2.5 sqmm) + 1x22/0.3 (1.5 sqmm) as ECC
2x56/0.3 (4 sqmm) + 1x36/0.3 (2.5 sqmm) as ECC
2 x 84/0.3 (6 sqmm) + 1 x 56/0.3 (4 sqmm) ECC
4x126/0.4 (16 sqmm) + 2x80/0.4 (10 sqmm) as ECC
Finishing of the PVC insulated wire ends by socketting with pin/ ring type copper sockets and insulated tapes etc., including supplying sockets, tapes.
PLUGS & SOCKETS:-
Supply & Fixing 240 V, two nos. 6 A, 3 pin Modular type plug socket (Brand approved by EIC) with two nos. 6A Modular type switch, without plug top on 6 Module GI Modular type switch board with 6 Module top cover plate flushed in wall incl. S&F switch board and cover plate and making necy. connections with PVC Cu wire and earth continuity wire etc. [PWD/GS Page: E-18 Item: 9/a ]
Galvanised iron sheet eaves gutter fitted and fixed with necessary 50 mm X 6 mm M.S flat bar clamps bent to design, bolts, nuts, washers etc. complete. Eaves gutter made of 0.63 mm. sheets. (300mm End lapping)300 mm. wide gutter
S&F 240 V, 3 nos. 6 A, 3 pin Modular type plug socket with 3 nos. 6A Modular type switch (Brand approved by EIC) with 1 no. 16 A, 3 pin Modular type plug socket with 1 no. 16A Modular type switch, 20A Modular switch type SP MCB (C-Curve) and Indicator without plug top on 12 Module GI Modular type switch board with 12 Module top cover plate flushed in wall incl. S&F switch board and cover plate and making necy. connections with PVC Cu wire and earth continuity wire etc. [PWD/GS Page: E-17 & 19 Item: 1,3a,4a,3b,4b &19a]
Supply & Fixing of 220V, Single Phase, 50 Hz A.C heavy duty exhaust fan of following sizes having complete metal body. incl. making hole on wall with nuts & bolts of required with S&F of louver shutter. (Make- EPC/ USHA/Orient CROMTON) [BEE star rated]
(a) 230 mm (9"), 4 Blade, RPM ≤ 1370 , Wattage ≤ 40 Watt, Sound level ≤ 49 dB, Air Displacement (In CFM) ≥ 440
(b)300 mm (12"), 4 Blade, RPM ≤ 1420 , Wattage ≤ 82 Watt, Sound level ≤ 56 dB, Air Displacement (In CFM) ≥ 1120
SUPPLY AND FIXING OF LIGHT FITTINGS:-
Supply and Fixing of 4 feet Industrial box type single LED tube fitting incl.1 no. 240V, 20 W LED Tube (Polycarbonate with heat sink) with glare free light distribution with CCT (5000K-6500K) having minimum luminous efficiency of 100 Lm/ Watt or better & 50,000 LED burning hours or more. on wall/ceiling/HW round block and suitable size of MS fastener.[Make- Philips/ Crompton/ Wipro or manufacturer with own NABL accredited lab with valid test certificate] [LED lamps & accessories shall have BEE certification]
Supply and Fixing of 4 feet Industrial box type twin LED tube fitting inc 2 no. 240V, 20 W LED Tube (Polycarbonate with heat sink) with glare free light distribution with CCT (5000K-6500K) having minimum luminous efficiency of 105 Lm/ Watt or better & 50,000 LED burning hours or more.Extra for suspension exceeding 25 cm with S&F additional 2 no. 20 mm dia EI conduit (14 SWG) supports & necy. PVC insulated wire and painting etc. as required by 2x24/0.20 mm (1.5sqmm.) flexible copper wire of 1.10 mt. length. [Make- Philips/ Crompton/ Wipro or manufacturer with own NABL accredited lab with valid test certificate] [LED lamps & accessories shall have BEE certification]
Supply & Fixing 36 Watt 240 V recess mounted 2'x2' LED in white powder coated pressure die cast aluminium housing , with glare free uniform illumination, suitable for 2' x 2' grid ceiling with CCT (3000 K Warm White) having minimum luminous efficiency of 100 Lm/ Watt or better & 50,000 LED burning hours or more. [Make- Philips/ Crompton/ Wipro or manufacturer with own NABL accredited lab with valid test certificate] [LED lamps & accessories shall have BEE certification
Supply & Fixing 36 Watt 240 V recess mounted 2'x2' LED downlight in white powder coated pressure die cast aluminium housing , with glare free uniform illumination, suitable for 2' x 2' grid ceiling with CCT (5700K-6500K Cool White) having minimum luminous efficiency of 100 Lm/ Watt or better & 50,000 LED burning hours or more. [Make- Philips/ Crompton/ Wipro or manufacturer with own NABL accredited lab with valid test certificate] [LED lamps & accessories shall have BEE certification
Supply & Fixing 9 Wat 240V LED lamps B22/E27 Base with glare free light distribution having minimum luminous efficiency of 100 Lm/ Watt or better & 50,000 LED burnin
g hours or more. incl S & F angular batten holder (Anchor) on 75mm dia PVC round block / round bakelite on wall/ceiling.[Make- Philips/ Crompton/ Wipro or manufacturer with own NABL accredited lab with valid test certificate] [LED lamps & accessories shall have BEE certification]
Supply & Fixing 18 Watt 240V recess mounted 1'x1' LED downlight in white powder coated pressure die cast aluminium housing, with glare free uniform illumination, suitable for 1' x 1' grid ceiling with CCT (5700K-6500K) having minimum luminous efficiency of 100 Lm/ Watt or better & 50,000 LED burning hours or more. [Make- Philips/ Crompton/ Wipro or manufacturer with own NABL accredited lab with valid test certificate] [LED lamps & accessories shall have BEE certification]
Supply and fixing 220 V - 240 V AC 50 Hz 2900 Watt Oil Filled Heater with PTC Heater of cord storage, Adjustable Thermostat Tip over switch Thermal cutout (Auto & Manual) Rear Safety cover,easy mobility ( make- Havells OFR-13FIN, or equivalent of Philips, Bajaj)
500V, 200A electrolyte grade tinned copper BBC with vertical section of 25X5mm size for neutral & Phases. Bus-bar shall be fixed with FRP insulator chair & the entire bars are insulated with PVC heat Sinkable sleeve of suitable size & color as per direction of E.I.C [equal bar for each i.e. 4-bar] And interconnections for: 160 A FP MCCB is 20X5mm copper bar, for 100A FP MCCB is 35 sqmm copper wire, for 40 A FP MCCB is 10 sqmm Copper Wire
Erection of Single octagonal pole of length 9 mt with 4 nos. 24mm dia750 mm length "J" type Bolt projected 125 mm & Nut etc. in RCC foundation (Proportion and dimension indicated below), having 750x750x150 mm thick PCC (4:2:1) base block with black stone including mm depth 1650x500mm dia cylindrical type RCC (M20 grade muffing with 4 nos. 12mm dia tor rod and 8mm dia tor rod for caging with 190 mm centre to centre spacing) and 200mm above ground level including 3 mm thick neat cemented finish and for alkathene/polythene pipe entry, for street light wiring, without Loop Box with GI earth bolt after making drilled holes etc. on base plate & carriage of pole upto 1.6 Km from Store to work-site including filling up the excavated earth pit with shifted soil and ramming properly.
Supply & Fixing 70 Watt of 240V, LED street lights with optic lens and polycarbonate in white powder coated pressure die cast aluminium housing with IP 66 protection & incl. 10 kV SPD, with glare free uniform illumination with CCT (5700K-6500K) having minimum luminous efficiency of 110 Lm/ Watt or better & 50,000 LED burning hours or more. complete with all accessories to be fixed on existing pole. incl. S&F necy. length of 1.5 sqmm PVC insulated single core stranded annealed copper wire and making necessary connections as required [Make- Philips/ Crompton Cat Ref. No. CRP421-70-57-SL-LM-NSG/ Wipro]
Supply & fixing of single arm header assembly made with 100mm dia GI pipe Jacket of 30cm long with 1.5 mtr. long 40mm dia GI pipe bracket duly welded with top cap at an angle of 110 degree with the vertical incl. 12 mm dia full threaded through nuts-bolts and 3 nos. supporting nut-bolts etc. including necessary painting as per direction of EIC.
Supply & Fixing 70 Watt of 240V, LED street lights with optic lens and polycarbonate in white powder coated pressure die cast aluminium housing with IP 66 protection & incl. 10 kV SPD, with glare free uniform illumination with CCT (5700K-6500K) having minimum luminous efficiency of 110 Lm/ Watt or better & 50,000 LED burning hours or more. and making necessary connections as required [Make- Philips/ Crompton Cat Ref. No. CRP421-70-57-SL-LM-NSG/ Wipro]
Supplying & Fixing GI waterproof type looping cable box size 200x150x100 mm deep having 4 mm thick comprising of one 250 V 15 A kit-kat fuse unit, one NL on porcelain insulator, one compression type brass cable gland for upto 2- core 16 sqmm PVC/A cable and having lined with rubber gasketted GI top cover with brass machine screws etc., earthing terminal with lug, on steel tubular pole near base, including S&F 40x6 mm thick, MS clamps with bolts, nuts etc. including painting with anticorrosive paint
Earthing with 50 mm dia GI pipe 3.64 mm thick x 3.04 Mts. long and 1 x 4 SWG GI (Hot Dip) wire (4 Mts. long), 13 mm dia x 80 mm long GI bolts, double nuts, double washers incl. S & F 15 mm dia GI pipe protection (1 Mts. long) to be filled with bitumen partly under the ground level and partly above ground level driven to an average depth of 3.65 Mts. below the ground level as below: By ISI-Medium GI pipe
Excavation of soil for installation of Earth Electrode and filling & ramming. (For Morrum Soil)
Extra for providing masonery enclosure on the top of the earth electrode of overall size 86.36 cm x 86.36 cm x 46 cm deep (below Ground level) complete with cemented brick work(1:6) of 25 cm width duly plastered with cement morter (inside) CI hinged inspection cover of size 36.56 cm x 35.56 cm with locking arrangement, GI reducer including drilling of 46 nos. 12 mm dia holes on the GI pipe.
Extra treatment of soil by using salt & charcoal for pipe electrode as to G.S.
Supply & fixing earth busbar of galvanized (Hot dip) MS flat 65 mm x 8 mm on wall having clearence of 6 mm from wall incl. providing drilled holes on the busbar complete with GI bolts, nuts, washers, spacing insulators etc. as required.
Connecting the equipments body to earth busbar incl. S & F 50 mm x 6 mm Galvanized (Hot Dip) MS flat on wall/floor with GI saddle as required and connection to equipments with incl. drilling holes, bolts, nuts,washers etc.
Supply & Drawing 1.1 KV grade 3Core 22/0.3 (1.5 sqmm) XLPE insulated Un-armoured Cu Cable (Brand approved by EIC) for connection from loop box to fittings through the Pole including making connections as necessary.
1st coat of aluminium paint over one coat of RO priming.
S & F of Exhaust piping shall be held from silencer onwards to the terrace for discharging entire exhaust gas. The piping and silencer shall be insulated fiber glass white wool. The insulation shall be held in position with galvanized steel wire mesh and neatly finish with 26 SWG Al. cladding M.S. Pipe (65 mm dia) shall be class - B. S & F flanges , MS Clamps vertically
Supply & Laying a) 12 core 2.5 sq. mm. (As meter loop/ Incomer to the main panel) PVC inculated armoured Copper. cable.Make- Polycab/ Havells/ KEI (For Control Panel to DG Set) incl. Supplying and fixing compression type gland complete with brass gland, brass ring & rubber ring for dust & moisture-proof entry and Finishing the end by crimping method incl. supplying and fixing solderless socket (Dowels make), tapes, anticorrosive paste & jointing materials
Supply of 2/4 Core XLPE Insulated & Sheathed Armoured stranded Aluminium Conductor cables for Working Voltage up to 1100 Volts of following sizes [Make Polycab / RR /KEI/ Havells/ Gloster as approved by E.I.C] (a) 4 core 35 sq. mm.
Laying of one No. cable upto 35 sqmm in underground trench 460 mm wide x 760 mm average depth, with brick protection on the top of the cable with 8 (eight) Nos. bricks per metre, including filling the space between the brick & cable and also the trench with shifted soil, leveling up and restoring surface duly rammed (For 4 core 35 Sq. mm cable)
Supplying and fixing compression type gland complete with brass gland, brass ring & rubber ring for dust & moisture-proof entry of XLPE/PVC armoured cables as below : (For 4 core 35 Sq. mm cable)
Finishing the end of following XLPE/PVC armoured cables by crimping method incl. supplying and fixing solderless socket (Dowels make), tapes, anticorrosive paste & jointing materials : (For 4 core 35 Sq. mm cable)
Earthing with 50 mm dia GI pipe 3.64 mm thick x 3.04 Mts. long and 1 x 4 SWG GI (Hot Dip) wire (4 Mts. long), 13 mm dia x 80 mm long GI bolts, double nuts, double washers incl. S & F 15 mm dia GI pipe protection (1 Mts. long) to be filled with bitumen partly under the ground level and partly above ground level driven to an average depth of 3.65 Mts. below the ground level as below: By ISI-Medium GI pipe
Earthing with Copper plate (610x610x3mm size) having weight of 9.84 Kg and 1 No. 25x5mm Copper strip (3.20 mt long) & 1 no. 6 sqmm PVC insulated stranded Copper wire (4 Mt long) incl. S & F 15 mm dia GI pipe (ISI-Medium) protection (4 mt. long) to be fillied with bitumen, partly under the ground level & partly above ground level to an average depth of 3.65 Mts. below the ground level and restoring the surface duly rammed incl. providing 3.0 mt long, 25 mm dia GI pipe (ISI-Medium) for periodic treatment, incl. providing masonery enclosure on the top of the earth electrode of overall size 86.36x86.36x46cm deep (below Ground level) complete with cemented brick work (1:6) of 25 cm width, duly plastered with cement morter (inside) CI hinged inspection cover of size 36.56x35.56cm with locking arrangement, GI reducer and treatment of soil by using salt & charcoal or coke for plate electrode
Excavation of soil for installation of Earth Electrode and filling & ramming. (Soft Soil) (for Earthing & DG Foundation) [PWD/GS Page: G-1 Item:1]
Extra for providing masonery enclosure on the top of the earth electrode of overall size 86.36 cm x 86.36 cm x 46 cm deep (below Ground level) complete with cemented brick work(1:6) of 25 cm width duly plastered with cement morter (inside) CI hinged inspection cover of size 36.56 cm x 35.56 cm with locking arrangement, GI reducer including drilling of 46 nos. 12 mm dia holes on the GI pipe [PWD/GS Page: G-2 Item: 3/a]
Extra for treatment of soil by using salt & charcoal or coke for plate electrode [PWD/GS Page: G-2 Item: 3/b]
S&F earth busbar of 40X6mm galvanized (Hot Dip) MS flat on wall having clearance of 6 mm from wall including providing drilled holes on the busbar complete with GI bolts, nuts, washers, spacing insulators etc. as required [PWD/GS Page: G-2 Item: 4/a]
Connecting the equipments body to earth busbar including S&F 25X6mm galvanised (Hot Dip) MS flat on wall/floor with GI saddles as required and connection to equipments incl. drilling holes, with bolts, nuts, washers etc. [PWD/GS Page:G-3 Item: 5/d]
Cutting RCC floor by special tools and tackles very carefully without any damaging and removing the shifted rubbish & levelling up and restoring the surface for 8nos. earth pit as per direction of EIC.
Supply and pour of H.S. Diesel oil for necessary commissioning of new DG incl. transportation cost.
Supply & delivery PVC 200Ltr. Oil Barrel of thickness 6mm.
Removal of rubbish,earth etc. from the working site and disposal of the same beyond the compound, in conformity with the Municipal / Corporation Rules for such disposal, loading into truck and cleaning the site in all respect as per direction of Engineer in charge
Sq. mtr.
S&F 240 V, 16 A, 3 pin Modular type plug socket (Brand approved by EIC) with 16A Modular type switch, without plug top on 4 Module GI Modular type switch board with top cover plate flushed in wall incl. S&F switch board and cover plate and making necy. connections with PVC Cu wire and earth continuity wire etc. [PWD/GS Page: E-18 Item: 9/b ]
Supplying and laying Polythene Sheet (150gm / sq.m.) overdamp proof course or below flooring or roof terracing or infoundation or in foundation trenches.
Ordinary cement concrete (mix 1:2:4) with graded stone chips (20 mm nominal size) excluding shuttring and reinforcement, if any, in ground floor as per relevant IS codes.(a) Pakur Varity
Hire and labour charge for shuttering with centreing and necessary staging up to 4 m. using approved stout props and thick hard wood planks of approved thick ness with required bracing for concrete slabs, beams,columns, lintels curved or staight including fitting fixing and striking out after complection of works. (a) 25 mm. to 30 mm. thick wooden shuttering as per decision & direction of the Engineer-in-charge. .
Reinforcement for reinforced concrete work in all sorts of structures including distribution bars, stirrups, binders etc. initial straightening and removal of loose rust (if necessary), cutting to requisite length, hooking and bending to correct shape, placing in proper position and binding with 16 gauge black annealed wire at inter-section, complete as per drawing and direction.(a) For works in foundation, basement and up to roof of ground floor/up to 4m. Tor steel/Mild steel. other than SAIL/TATA RINL
Construction of DG Set Platform:-Surface Dressing of the ground in any kind of soil including removing vegetation inequalities not exceeding 15 cm depth and disposal of the rubbish within a lead upto 75 m as directed.
Brick work with 1st class bricks in cement mortar (1:4)(b) In superstructure, ground floor. In superstructure, ground floor
125 mm. thick brick work with 1st class bricks in cement mortar (1:4) in ground floor.
M.S. structural works in roof trusses with tubular sections conforming to IS: 806-1968 & IS: 1161- 1998 cnnected to one another with bracket, gusset cleats as per design, direction of Engineer-in-charge complete including cutting to requisite size, fabrication with necessary metal arc welding conforming to IS: 816-1969 & IS: 9595 using electrodes of approved make and brand conforming to IS:814- 2004, haulage, hoisting and erection all complete. The rate includes the cost of rolled steel section, consumables such as electrodes, gas and hire charge of all tools and plants and labour reqired for the work including all incidental chages such as electricity charges, labour insurance charges etc. Payment to be made on the basis of calculated weight of structural tubular memebrs as specified in relevent IS code in finished work. Payment for gusset, bracket, cleat may be made by adding the actual weight of such items with weight of finished structural members. The rates are considered for a height of erection 8 m. / 2nd floor level from the ground. Add 1.5 % extra over the rate for each additional floor or 4m. beyond the initial 8 m. or part thereof i) For trusses spanning up to 12.00 m
Galvanised or painted wind-tie made of M.S. flats, fitted and fixed complete including cost of necessary fittings. Made with 50 mm. X 6 mm. flats
Plaster (to wall, floor
, ceiling etc.) with sand and cement mortar including rounding off or chamfering conrners as directed and raking out joints including throating, nosing and drip course, scaffolding/ staging where necessary(ground floor)[Excluding cost of chipping over concrete surface](With 1:4 cement mortar.15 mm. thick plaster.
(ground floor)(i) with 1:6 cement mortar.20 mm. thick plaster.
Neat cement punning about 1.5mm thick in wall, dado, window sill, floor etc. NOTE:Cement 0.152 cu.m per 100 sq.m.
Painting with best quality synthetic enamel paint of approved make and brand including smoothening surface by sand parpering etc. in cluding using of approved putty etc. on the surface , if necessary. On steel or other metal surface:With super gloss (hi-gloss). Two coats (with any shade except white). Two coats (with any shade except white).
Supplying, fitting, fixing G.I chain link fencing 75 mm x 75 mm mesh 12 g wire to the R.C.C or wooden posts with galvanised hooks or staples etc. complete as per direction.
Priming one coat on steel or other metal surface with synthetic oil bound primer of approved quality including smoothening surfaces by sand papering etc.
Iron butt hinges of approved quality fitted and fixed with steel screws, with ISI mark. 100mm. X 50mm. X 1.25mm.
Hand operated Oil Pump
PVC pipe suitable for oil pumping to DG of length 10Mtr.
SITC of LED SIGN BOARD:-
SITC of Glowsign Board ( Router cutting) with liquid Acrlyic letters with adhesive on ACP Board of 3 mm Thick (Make – Aludecor / Alstone) of suitable size to accommodate all the matters / contains as approved by the authority to be made with 25 x 25 x 4 mm M.S angle Iron, 18 S.W. G square /Round Hollow bar, Base plate (10 mm Thickness) requires for fixing the necessary Nuts, Bolts, Washers, supporting angle Iron, Clamp etc. and ACP Sheet on Front sides & edges only & back side to be covered by GI Sheet (with proper ventilation arrangement), All side to be moulded uniformly, Side fabricated by Aluminium ‘L’Channel, upon which elevated or box type letter made from imported liquid acrylic will be fixed. The Thickness of Acrylic will be 5 mm (for small letters), 8 mm (for Big letters) and 10 mm (for very big letters). The Back Side of the letters is covered by 3 mm thick ACP (Make – Aludecor / Alstone). The inside of the letter of the letter Supplying and Fixing of best Quality LED Lighting arrangement of fully water proof 10 nos. LED light fittings of 20 watt (100 lumen / watt). The letters are sealed by exterior grade Silicon. The back side of the Board Covered by 22 S.W.G G.I sheet with Nuts & Bolts. (2 no Signage- 96 Sq Ft/ 12 Ft x 8 Ft each)
Intensity: Same & smooth uniform throughout without any dark patch.
Visibility: Up to 250 meters for normal eyes.
The complete sign board would be fixed on roof of the building with providing necessary CC muffing, 1 no CI water proof 200 x 150 x 100 mm loop Box, 50 x 50 x 6 mm MS angel for supporting the board of required length by nuts, bolts, washers etc. After drilling holes on the frame front facia. GSB would have 2 nos. hinge type doors in back side to have the inside access including mending goods the damages to origi
nal finish.
Painting of any steel / iron surface of the above Glow sign board with no. of coats of paints as given below with ready mixed paint / primer of approved make and brand incl. preparation of surface by sand paper / emery paper, cleaning etc. for receiving fresh coat of paint.
Supply and Delivery of Unidirectional Dynamic Multi Purpose Microphone.( make: ahuja, Model: AUD-101XLR)
SITC of 15 Litre capacity vertical/ horizontal type water geyser having following specification and accessories: Closed water geyser, Class- I, 230V, 50 Hz AC, BEE 5 Star Rating, Blue Diamond Glass Lined tank and Glass Coated Incoloy heating element, outer container should be made with mild steel and having water proof powder coating to protect from rust & corrosion with the facility of “Green” & “Red” indicator, Superior polymer coated tank, with the safety of Thermostat, Thermal cut out, Temperature controlled facility, Multi function valve & sacrificial anode & must be protected against galvanic corrosion, Manufactured in modern automated plant using European Technology. (Make- Venus/ Racold/ AO Smith/ Bajaj/ Crompton/Havells/ V-Guard/Orient)
Supply and Delivery of Mic Cable 6.35mm Jack Male To XLR 3PIN Female Cord Wire For Microphone Cable 3 Meter.
SITC of LT Panels:-Supply delivery installation testing & commissioning Indoor Cubical type L.T. Distribution panel board of appropriate size base mounted compartmentalized with maple arrangement having rigid & self supporting structure with cable allay fabricated from 02 mm thick CRCA sheet steel with 25X25X6mm MS angle frame and 75X40X40mmX4.4mm M.S. Channel for base support. And making masonary trench of 600mm depth and suitable length & wide in matching with Panel with 10" brick work, plastering & neet cementing as per direction of EIC. The Pannel should be made from CPRI certified or equivalent Panel making workshop. The panel board consisting of the following item-
Incomming: a. 415V 160 A FP MCCB ( Legrand Make 35 KA) 01 nos. b. 415V, 160 amp TPN on load front operated Changeover switch 01 no. Outgoing: a. 415 Volt 100A FP MCCB ( Legrand Make 35 KA) 03 Set. b. 415 Volt 40A FP MCCB ( Legrand Make 35 KA) 02 Set. Other equipments: 3-ph LED Volt Meter class-1 (L&T: WL132010OOOO) -- 01 no. 3-ph LED Ammeter 5A, class-1 ( L&T: WL131010OOOO) -- 01 no. 3-ph Frequency meter (AE: 21 LED, 45 - 55HZ blinking led type, resolution-0.5) -- 01 no. 200/5A CT (Kappa) -03 nos. LED R-Y-B indicator with 3 nos. Legrand 6A SP MCB -- 01 item Supply & Fixing 16"X12" Danger Board -- 01 no.
stage.html
html • 0.02 MB
cancelled_1.pdf
pdf • 2.07 MB
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Tendernotice_1.pdf
PDF • 1.22 MB
Tendernotice_2.pdf
PDF • 1.87 MB
BOQ_2251754.xls
BOQ • 0.36 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .