| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹16.7 LAccepted-Finance | L1 | Accepted-Finance Lowest Bidder | |
| 2 | L2₹16.9 L+₹23,800 (1.43%)Rejected-Finance | L2 | Rejected-Finance 2nd Lowest Bidder | |
| 3 | L3₹16.9 L+₹26,920 (1.62%)Rejected-Finance MAIRAKATA P O GARBETA DIST PASCHIM MEDINIPUR 721127 | GARBETA | PASCHIM MEDINIPUR | WEST BENGAL | 721127 | L3 | Rejected-Finance 3rd Lowest Bidder | |
| 4 | Rejected-Technical RAGHUNATHPUR P S JHARGRAM DIST JHARGRAM WEST BENGAL PIN 721507 | JHARGRAM | JHARGRAM | WEST BENGAL | 721507 | - | Rejected-Technical Technically Rejected due to insufficient Credential Certificate |
| Sl No | Description | Qty | Unit | M/S JOGMAYA ENTERPRISE L1 | DURGAPUR POWER L2 | R.K.ENTERPRISE L3 |
|---|---|---|---|---|---|---|
| 1.00Supply, Installation, Testing and Commissioning of metal clad, indoor type, single tier, fully compartmentalized, free-standing, floor-mounted, Floor roll type, consisting of 1 (One) No. panel, having Internal Arc Classification (IAC) suitable for 26.3 kA for 3 seconds, complete with horizontal draw-out type 11 kV, 800 A Vacuum Circuit Breaker (VCB). The panel shall be provided with 1 (One) No. power pack of adequate rating complete in all respects. [Make: ABB/SIEMENS/SCHNEIDER ] N.B. Vacuum Interrupter , Vacuum Circuit Breaker, and Protective Relays shall be same VCB panel manufacturer. | ||||||
| 1.01MOVING PORTION | ||||||
| 1.0212 kV, 800A, 26.3 kA for 3 sec, draw-out type Vacuum Circuit Breaker (VCB), complete with motorized spring charging mechanism suitable for 240V AC supply, and equipped with closing coil and tripping coil suitable for 110V DC control voltage – 01 Set. [Make: ABB/SIEMENS/SCHNEIDER] | ||||||
| 1.03PANEL, BUSBAR, CT AND PT DETAILS: | ||||||
| 1.04Fully compartmentalized, sheet steel, totally enclosed, floor-mounted HT switchgear panel complete with safety shutters, horizontal draw-out and horizontal isolation type arrangement, including insulated PVC sleeved electrolytic copper busbars suitable for 11 kV system voltage, rated for 800 A continuous current and 26.3 kA short-circuit withstand capacity for 3 seconds, along with foundation bolts and all associated accessories complete in all respects. | ||||||
| 1.05Epoxy cast dual core Current Transformers (CTs) having CT Ratio: 50–25/5–5 A with the following core specifications: Core–1: 10 VA, Class–0.5, Core–2: 10 VA, Class–5P10 ----03 Sets [Make-PLASTOFAB/BMC/POWER FOILS/ ECS/Pragati/Jyoti or as per the OEM Standard] - 03 sets | ||||||
| 1.06Epoxy cast, dual core Voltage Transformer, drawout type (VT/PT) suitable for 11 kV/√3 / 110 V/√3 – 110 V/√3 system voltage ratio, complete with built-in primary PT fuses, having the following core specifications: Core–1: 50 VA, Class–1, Core–2: 50 VA, Class–3P ----- 03 Sets and Fuse for PTs Secondary --- 06 Nos. [Make-PLASTOFAB/BMC/POWER FOILS/ ECS/Pragati/Jyoti or as per the OEM Standard] - 03 sets | ||||||
| 1.07BREAKER PANEL INDICATION LAMPS: | ||||||
| 1.08VCB cubicle mimic indication and annunciation lamps complete with LED type indication for ON, OFF, TRIP, Spring Charged (SP.CH), Trip Circuit Healthy (TCH), and R/Y/B phase healthy indications (STS type), complete in all respects — 8 Nos. | ||||||
| 1.09SWITCHES AND OTHER ACCESSORIES: | ||||||
Tender Value
Refer Docs
EMD Value
₹33,441
Closing Date
27 Jun 2026, 2:30 pmClosed
SENIOR SUPERINTENDING ENGINEER
OFFICE OF THE SENIOR SUPERINTENDING ENGINEER (P.W.Dte) South-Western Electrical Circle PWD Compound, Midnapore, Paschim Medinipur
SITC of HT Panel including allied EI Work at the Substation of Govt.ITI , Jhargram.
2026_WBPWD_5014132_2
WBPWD/SSE/SWEC/NIQ09/2026-27
Open Tender
ELECTRICAL WORKS ORG
Item Rate
30 days
JHARGRAM
Please refer Tender documents.
4 documents required · 4 mandatory
₹33,441
OFFICE OF THE SENIOR SUPERINTENDING ENGINEER
22 Jul 2026
11 Jun 2026
29 Jun 2026
11 Jun 2026
27 Jun 2026
15 Jun 2026
15 Jun 2026
| Sl No | Description | Qty | Unit | Est. Rate | Est. Amount |
|---|---|---|---|---|---|
| 1.01 | MOVING PORTION | - | - | - | - |
| 1.02 | 12 kV, 800A, 26.3 kA for 3 sec, draw-out type Vacuum Circuit Breaker (VCB), complete with motorized spring charging mechanism suitable for 240V AC supply, and equipped with closing coil and tripping coil suitable for 110V DC control voltage – 01 Set. [Make: ABB/SIEMENS/SCHNEIDER] | - | - | - | - |
| 1.03 | PANEL, BUSBAR, CT AND PT DETAILS: | - | - | - | - |
| 1.04 | Fully compartmentalized, sheet steel, totally enclosed, floor-mounted HT switchgear panel complete with safety shutters, horizontal draw-out and horizontal isolation type arrangement, including insulated PVC sleeved electrolytic copper busbars suitable for 11 kV system voltage, rated for 800 A continuous current and 26.3 kA short-circuit withstand capacity for 3 seconds, along with foundation bolts and all associated accessories complete in all respects. | - | - | - | - |
| 1.05 | Epoxy cast dual core Current Transformers (CTs) having CT Ratio: 50–25/5–5 A with the following core specifications: Core–1: 10 VA, Class–0.5, Core–2: 10 VA, Class–5P10 ----03 Sets
[Make-PLASTOFAB/BMC/POWER FOILS/ ECS/Pragati/Jyoti or as per the OEM Standard] - 03 sets | - | - | - | - |
| 1.06 | Epoxy cast, dual core Voltage Transformer, drawout type (VT/PT) suitable for 11 kV/√3 / 110 V/√3 – 110 V/√3 system voltage ratio, complete with built-in primary PT fuses, having the following core specifications: Core–1: 50 VA, Class–1, Core–2: 50 VA, Class–3P ----- 03 Sets and Fuse for PTs Secondary --- 06 Nos. [Make-PLASTOFAB/BMC/POWER FOILS/ ECS/Pragati/Jyoti or as per the OEM Standard] - 03 sets | - | - | - | - |
| 1.07 | BREAKER PANEL INDICATION LAMPS: | - | - | - | - |
| 1.08 | VCB cubicle mimic indication and annunciation lamps complete with LED type indication for ON, OFF, TRIP, Spring Charged (SP.CH), Trip Circuit Healthy (TCH), and R/Y/B phase healthy indications (STS type), complete in all respects — 8 Nos. | - | - | - | - |
| 1.09 | SWITCHES AND OTHER ACCESSORIES: | - | - | - | - |
| 1.1 | PANEL SPACE HEATER WITH THERMOSTAT [Make: APT Control or as per OEM Standard ] - 01 Set | - | - | - | - |
stage.html
html • 0.04 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 0.52 MB
Tendernotice_2.pdf
PDF • 1.75 MB
2911.pdf
Tender Documents • 0.51 MB
NIQ09re.pdf
Tender Documents • 1.74 MB
BOQ_5084173.xls
BOQ • 0.45 MB
niqcorri.pdf
PDF • 0.48 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .