Tender ID
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
| # | Company | Status |
|---|---|---|
| 1 | Admitted-Fee/PreQual/Technical 315 INDUSTRIAL AREA II PANCHKULA 134113 | PANCHKULA | HARYANA | 134113 | Admitted-Fee/PreQual/Technical |
| 2 | Admitted-Fee/PreQual/Technical CHANDIGARH | Admitted-Fee/PreQual/Technical |
Tender Value
₹3.0 L
EMD Value
₹5,910
Closing Date
29 Dec 2025, 12:00 pmClosed
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
Er. Gurpreet Singh Bhains
Office of the Executive Engineer, Electrical Division No. 1, Sector-9,Chandigarh.
CONSTRUCTION OF EXPANSION OF EMERGENCY BLOCK (TRIAGE ROOM), GMSH, SECTOR-16, CHANDIGARH (FIRE SENSING WORK) (IBM SCHEME NO. W1/2025/24545).
2025_CHD_89300_2
E1/TN-386
Open Tender
Electrical Works
Percentage
30 days
Chandigarh
Please refer Tender documents.
2 documents required · 2 mandatory
₹0
₹5,910
29 Dec 2025
23 Dec 2025
29 Dec 2025
23 Dec 2025
29 Dec 2025
23 Dec 2025
Supply, installations, testing and commissioning of intelligent multisensor detector with integrated fault isolator and isolator base. The intelligent multi criteria detector shall have integrated fault isolator/ fault isolator base as per NFPA style 7 to make ensure complete system working without losing any detector in case of cable fault. Be an addressable device that is designed to monitor, (As per Complete Item No. 1 of the DNIT).
DSR Item No. 28.2.14 Supplying, installation, testing & commissioning of addressable manual call point complete as required.
DSR Item No. 28.2.15 Supplying, installation, testing & commission of addressable horn cum strobe complete as required.
DSR Item No.28.5.1Supplying & laying of 2x1.5 sqmm fire survival armoured cable, 600/1000V rated with annealed copper conductor having glass mica fire barrier tape covered by an extruded layer of Cross Linkable Ethylene Propylene Rubber (EPR) insulation and LSZH inner bedding, steel wire armouring& LSZH outer sheath complete as required.
DSR Item No. 1.20 Supplying and fixing of following sizes of steel conduit along with accessories in surface/recess including painting in case of Surface conduit, or cutting the wall and making good the same in case of recessed conduit as required.
S/I/T/C of fire exit sign board illuminated made from etched sheet with LED illumination and all electrical accessories included battery and battery charge etc. on ceiling/ wall mounted with logo & exist arrow) Make:-Glowline/ HHE/ Ravel/ Honeywell.
Supply installation testing and commissioning of 2X12 watt wall mounted Industrial Double Beam emergency LED light with exit sign board. The fitting should have CRCA steel housing, 50000 burning hours, battery of suitable capacity for emergency backup of 4 to 5 hours.(As per Complete Item No. 7 of the DNIT).
tech_bid_open.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 0.71 MB
BOQ_109697.xls
BOQ • 0.28 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .