Loading…
Tenderkart now works inside Claude and ChatGPT: search and analyse tenders right from your chat
Loading…
Tender ID
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹9.8 LAccepted-AOC BASUDEBPUR BELKHALI HOWRAH PIN 711 322 | HOWRAH | HOWRAH | WEST BENGAL | 711322 | L1 | Accepted-AOC Agency Stood L1 in the Tendering Process. | |
| 2 | L2₹10.6 L+₹76,010 (7.76%)Rejected-Finance 63 PILKHANA ROAD BERHAMPORE MURSHIDABAD 742101 | BERHAMPORE | MURSHIDABAD | WEST BENGAL | 742101 | L2 | Rejected-Finance Agency Stood L2 in the Tendering Process | |
| 3 | L3₹12.5 L+₹2.7 L (27.6%)Rejected-Finance | L3 | Rejected-Finance Agency Stood L3 in the Tendering Process |
Tender Value
Refer Docs
EMD Value
₹22,620
Closing Date
19 Jul 2022, 2:00 pmClosed
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
EXECUTIVE ENGG (P.W.D), D/DINAJPUR ELEC DIVN
O/O EXECUTIVE ENGG (P.W.D), D/DINAJPUR ELEC DIVN
SITC OF INTELLIGENT FIRE DETECTORS AT COMPOSITE EDUCATION COMPLEX KARNAOJORA UTTAR DINAJPUR
2022_WBPWD_384810_1
WBPWD/EE/DDED/e-NIQ-03/2022-23
Open Tender
ELECTRICAL WORKS ORG
Item Rate
30 days
Raiganj
Please refer tender documents
6 documents required · 6 mandatory
₹22,620
O/O EXECUTIVE ENGG (P.W.D), D/DINAJPUR ELEC DIVN
19 Sept 2022
17 Jun 2022
21 Jul 2022
17 Jun 2022
19 Jul 2022
22 Jun 2022
20 Jun 2022
120 days
Amount
FIRE CONTROL PANEL
Supply, Installation, Testing & Commisioning of Microprocessor based Intelligent, addressable expandable and fully networkable Fire Alarm Control Panel (VDS / UL / ERTL, LPCB & FM approved) suitable for the devices as stated in the previous items of this BOQ along with 20% spare capacity with each loop loading not exceeding 80% of the full capacity of detectors and devices taken together, conplying to IS 2189:2008 or its latest amendments, and with minimum 600 character alpha - numeric liquid crystal display.The panel shall be soft addressable type and shall be able to give pin point location of all fire/ fault conditions. Further, the panel must be able to automatically switch off respective control switches whenever any alarm is triggered.The Panel should be able to store sufficient numbers of log events in its Memory as per recommended standards.
The panel shall have in built rectifier, provision for external & internal printer ( if required ), Loop cards, LCD unit to indicate Fire/Fault Signal with address and analog output, complete in all respects, in built Surge protection facility, integral SMF lead acid batteries with sealed cells of 24 V capable of running for 24 hours normal working and then be capable of operating the system for 30 minutes during Emergency condition, with integral battery charger complete in all respect as required.
The FACP shall be capable of being networked (future expansion) with other similar FACP located at different part of the premises through single RS 485 bus.The FACP shall have provision for interfacing with the public address system, remote computer and BMS interface.The system must be preloaded with licenced software. (Approved Make: Esser/Cerberus Pro/ Bosch/ Johnson Controls/ Notifer / Edward /Secutron/ Securiton/ Apollo / Morley / Eaton/GST / GFE)
NOTE : 1. The Fire Alarm system shall comply with latest requirements of -- 2. National Fire Protection Association (NFPA) Standards IS:2189. 3. NFPA 70 National Electric Code. 4. NFPA 72 National Fire Alarm & Signaling Code. 5. Local Statutory Regulations. 6. Manufacturer Recommendation.
TESTS: 1.The system shall be tested and commissioned by a qualified competent,trained engineer or technician authorized by the manufacturer of the fire alarm equipment to technically supervise and participate during all of the adjustments and tests for the system. 2. Before energizing the cables and wires, check for correct connections and test for short circuits, ground faults, continuity, and insulation and other tests as per above standards must be done. 3. The Commissioning Manuals, Tools, Dongles, USb Token, Software, or whatever is required for the Commissioning of the FACP, in whatever name it called must be handed over to the EIC, along with the passwords of the panel.
DETECTOR, INDICATOR, HOOTER & CALL POINT
Supply, Installation,Testing & Commisioning of Analog Addressable Intelligent multisensor detector (VDS / UL / FM / ULC approved) with inbuilt optical smoke sensors as well as additional heat detector sensor with decentralise intelligence, soft addressable Photothermal type with inbuilt fault isolator as per NFPA style 7 wiring complete with base having IP as per recommended standard. (Note : Detectors without built-in fault isolator is also acceptable but in such case one independent fault isolator module for every group of addressable devices has to be provided (Numbers of addressable devices in a group will be as per latest recommended standards) without any additional cost). (Approved Make: Esser/Cerberus Pro/ Bosch/ Johnson Controls/ Notifer / Edward /Secutron/ Securiton/ Apollo / Morley / Eaton/GST/ GFE).
Supply, Installation,Testing & Commisioning of Addressable Manual Call Point (VDS / UL / FM / ULC approved) soft addressable type with in built fault isolator as per NFPA style 7 wiring complete as required. (Approved Make: Esser/Cerberus Pro/ Bosch/ Johnson Controls/ Notifer / Edward /Secutron/ Securiton/ Apollo / Morley / Eaton/GST/ GFE).
Supply, Installation, Testing & Commissioning of Addressable Loop Powered Hooter (sound output of minimum 90 db) cum strobe (strength of light 10 cd)complete with inbuilt isolator & IP65 base and (VDS / UL / FM / ULC approved) approved. (Approved Make: Esser / Cerberus Pro / Bosch / Johnson Controls / Notifer / Edward / Secutron / Securiton / Apollo / Morley / Eaton / GST / GFE).
INTERCONNECTION
Supply & Laying of 2 Core 1.5 sq.mm FRLS shielded copper Cable (For Loop) (Make. Finolex/RR Kable/Polycab) with 20 mm NB PVC rigid conduit pipe (Make: Precision /AKG / ATUL / VIP / Universal /BEC / Polycab) on the surface of the wall. [1500 mtrs for Signage wiring, 1500 mtrs for loop wiring and 2000 mtrs for 24V power supply]
TERMS & CONDITIONS
The Agency must procure the materials from the Manufacturer / OEM or from their authorised sales channel so that the standard warranty / support of the Manufacturer / OEM becomes applicable to the products to be delivered and installed by them.
Documents that authenticates such procurement from the Manufacturer / OEM or from their authorized sales channel and standard warranty / support should be sent from the e-mail of the Manufacturer / OEM / authorized sales channel to the e-mail of Engineer-in-Charge and hard copy of it to be submitted during execution, of work/submission of bill.
If any refurbished material is supplied and installed, penal action will be taken as per existing rules.
NOTE:- THE RATES TO BE QUOTED BY ALL THE BIDDERS SHOULD BE INCLUSIVE OF AL L TAXES INCLUDING GST AND OTHERS.
MITRA ELECTRONICS
Debtech Electronics
technical_752365.pdf
PDF • 0.13 MB
techsummary_752365.pdf
PDF • 0.05 MB
finance_752365.pdf
PDF • 0.09 MB
BOQ Comparative Chart
xlsx • 0.01 MB
finsummary_752365.pdf
PDF • 0.16 MB
finalwc.pdf
PDF • 0.13 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .