Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹76.1 LAccepted-AOC HOUSE NO 41 WARD NO 09 ARYA SAMAJ GALI UDHAMPUR 182101 J K | UDHAMPUR | UDHAMPUR | J K | 182101 | L1 | Accepted-AOC LOWEST QUOTED BIDDER | |
| 2 | L2₹77.8 L+₹1.5 L (1.94%)Rejected-Finance A 3 257 JANAKPURI NEW DELHI 110058 | WEST DELHI | DELHI | 110058 | L2 | Rejected-Finance NOT THE LOWEST QUOTED BIDDER | |
| 3 | L3₹87.4 L+₹11.2 L (14.6%)Rejected-Finance | L3 | Rejected-Finance NOT THE LOWEST QUOTED BIDDER | |
| 4 | L4₹88.9 L+₹12.6 L (16.5%)Rejected-Finance 33 CHANDASI HOUSE LANE NO 11 S K PURAM ARYA SAMAJ MANDIR ROAD RPS MORE BAILEY ROAD DANAPUR PATNA BIHAR 801503 | PATNA | PATNA | BIHAR | 801503 | L4 | Rejected-Finance NOT THE LOWEST QUOTED BIDDER | |
| 5 | L5₹92.9 L+₹16.6 L (21.8%)Rejected-Finance | L5 | Rejected-Finance NOT THE LOWEST QUOTED BIDDER |
| Sl No | Description | Qty | Unit | OM SAI POWER SYSTEMS L3 | M/S AMRIT DAS MAHAPATRA L6 | VBK ELECTRICALS AND AGENCIES PRIVATE LIMITED L8 | Haasith constructions L5 | Srinivasa Consructions L7 | Roy and Sons Infrastructures L4 | M/S ADHIKARI CONSTRUCTION CO. L2 | M/S N K POWER SYSTEMS AND PROJECTS L1 |
|---|---|---|---|---|---|---|---|---|---|---|---|
| 1.00 | Supply and install Transformer Step down Outdoor type complete with standard fittings HT, 11KV 3 Phase, LT 433V, 3 Phase, 4 wire copper wound Energy efficiency Level 2 with off load tap changer in 7 steps of 2.5% for range of +/- 7.5% step down outdoor type on HT side to very secondary voltage within limit all as per IS-1180 : 2014 (Amendment No 4 of Mar 2021) of capacity 63 KVA transformer shall be of oil immersed naturally cooled type (ONAN) complete Including disconnecting and takingout from position, transporting and diposited to AGE E/M Store yard consists following specifications complete all as specified and as directed :-
(a) Two earthing terminals for body earthing and two additional for neutral brought on bushing.
(b) Oil level gauge indicating oil level minimum and maximum.
(c) lifting lugs.
(d) Drain cum sampling valve.
(e) Thermometer pocket.
(f) Oil filling hole with cover.
(g) Dehydrating breathing device.
(h) Rating and terminal marking plates.
(j) Three nos of porcelain bushing HT 11 KV with bushing rods, nuts, bolts inside cable end box.
(k) One cable box LV side consists of 4 Nos of brass bushing rods with nuts, bolts with two nos of cable glands of suitable size.
(l) Explosion vents.
(m) Air relief valve plug.
(n) Intial filling to transformer oil. Location : Substation at 09 End and 27 End. | 2 | Each Job | 5,34,501 ₹10,69,002 | 5,40,000 ₹10,80,000 | 5,85,000 ₹11,70,000 | 4,10,000 ₹8,20,000 | 4,48,920 ₹8,97,840 | 5,00,000 ₹10,00,000 | 3,99,999 ₹7,99,998 | 3,66,666 ₹7,33,332 Lowest |
| 2.00 | All as per Item No 1 here in above but of transformer capacity of 100 KVA Loc: STP AFS | 1 | Each Job | 6,85,100 ₹6,85,100 | 6,90,300 ₹6,90,300 | 7,08,300 ₹7,08,300 | 5,00,000 ₹5,00,000 | 5,40,960 ₹5,40,960 | 6,00,000 ₹6,00,000 | 4,99,999 ₹4,99,999 | 4,77,777 ₹4,77,777 Lowest |
| 3.00 | All as per Item No 1 here in above but of transformer capacity of 160 KVA Location: AFNET | 1 | Each Job | 10,59,500 ₹10,59,500 | 10,60,300 ₹10,60,300 | 11,09,430 ₹11,09,430 | 9,00,000 ₹9,00,000 | 9,30,360 ₹9,30,360 | 7,00,000 ₹7,00,000 | 5,99,999 ₹5,99,999 Lowest | 6,11,111 ₹6,11,111 |
| 4.00 | All as per Item No 1 here in above but of transformer capacity of 200 KVA , Location : WT, 44R&SU | 2 | Each Job | 11,70,000 ₹23,40,000 | 11,80,000 ₹23,60,000 | 12,20,940 ₹24,41,880 | 10,75,000 ₹21,50,000 | 10,93,200 ₹21,86,400 | 7,50,000 ₹15,00,000 | 6,49,999 ₹12,99,998 Lowest | 8,44,444 ₹16,88,888 |
| 5.00 | Supply and install Transformer Step Up Outdoor type complete with standard fittings HT, 11KV 3 Phase, LT 433V, 3 Phase, 4 wire copper wound Energy efficiantLevel 2 all as per IS -1180 : 2014 (Amendment No 4 of Mar 2021) of capacity 100 KVA transformer shall be of oil immersed naturally cooled (ONAN) type complete Including disconnecting and takingout from position, transporting and diposited to AGE E/M Store yard consists following specifications complete all as specified and as directed :-
(a) Two earthing terminals for body earthing and two additional for neutral brought on bushing.
(b) Oil level gauge indicating oil level minimum and maximum.
(c) lifting lugs.
(d) Drain cum sampling valve.
(e) Thermometer pocket.
(f) Oil filling hole with cover.
(g) Dehydrating breathing device.
(h) Rating and terminal marking plates.
(i) Three nos of porcelain bushing HT 11 KV with bushing rods, nuts, bolts inside cable end box.
(j) One cable box LV side consists of 4 Nos of brass bushing rods with nuts, bolts with two nos of cable glands of suitable size.
(k) Explosion vents.
(l) Air relief valve plug.
(m) intial filling to transformer oil. Location : Substation ATC. | 1 | Each Job | 6,85,000 ₹6,85,000 | 6,95,430 ₹6,95,430 | 10,40,400 ₹10,40,400 | 6,50,000 ₹6,50,000 | 5,97,600 ₹5,97,600 | 6,00,000 ₹6,00,000 | 4,99,999 ₹4,99,999 | 4,77,777 ₹4,77,777 Lowest |
| 6.00 | Supply, installation, testing and commissioning in replacement of Servo controlled voltage stabilizer (Confirming to BIS 9815 (Part-1): 1994, reaffirmation 2019 latest version). Three phase, four wire (RYBN), 50HZ Naturally Oil cooled, indoor, unbalanced type, cooper wound, metallic body duly powder coated with lifting hooks two Nos, digital display type, relay free smooth and silent operation with 1st filling Transformer oil up to level having following specifications:- | 1 | Each | 3,10,000 ₹3,10,000 | 2,45,097 ₹2,45,097 | 4,19,400 ₹4,19,400 | 4,50,000 ₹4,50,000 | 2,32,250 ₹2,32,250 | 2,30,000 ₹2,30,000 Lowest | 2,99,999 ₹2,99,999 | 2,77,777 ₹2,77,777 |
| 6.01(a) Capacity 75 KVA (b) Type – Suitable for unbalanced load and unbalanced input. (c) Input voltage – 360 Volt to 480V, Input frequency 50 HZ. (d) Output voltage – stabilized at any designed/ desired voltage 415 plus or minus 1%. (e) Rated frequency – 50 HZ. (f) Wave form distortion – Nil. (g) Response time – not to exceed 20 milliseconds. (h) Sensitivity – Plus or Minus 1%. (j) Rate of correction – Not less than 6 Volt/ second between phase and neutral. (k) Efficiency – more than 95%. (l) Type of load – three phase, unbalanced type. (m) Metering – Digital display voltmeter/ Ammeter with multi functional meter. (n) Operating temperature – For indoor use up to max ambient temperature + 55 degree centigrade. | |||||||||||
| 6.02(o) Class of insulation – Class F. (p) Mode of operation : Automatic and manual alongwith bypass arangement. (q) Winding temperature rise – Max 55 degree centigrade (10 degree centigrade above operating temp). (r) Transformer oil – IS 335 marked. (s) Core – CRGO M4 Grade/CRNO (Cold Roll Grain Oriented) Cold Rolled Non-oriented). (t) Auto transformer (VARIAC) – 100 Percent copper wound Electrolytic Grade. (u) Losses – As per IS Norms. (v) Power factor – Not less than 0.95 (w) Protection :- (i) Over load protection. (ii) Short circuit protection. (iii) High/low voltage cut off. (iv) By pass arrangement in case of Emergency. (v) Single phase sequence change/ phase fail protection. (vi) Earth fault protection. (x) Standard fitting & Accessories e.g Marking plate, lifting lugs, CI Rollers, Earthing Terminals etc cable box complete all as specified and directed. Each 01 Nos. | |||||||||||
| 7.00 | M&L Brick platform of size 2.5m x 2.5 m x 1.5 m and upto depth of 1.0 meter below ground in cement mortar 1:6 with PCC foundation 1:4:8 type D-2 using 40 mm graded stone aggregate, PCC 1:2:4, type B-1 using 20 mm graded stone aggregate, 20 cm thick coping over brick work, plastering to exposed surfaces of brick work with cement mortar 1:4, 15mm thick complete all as specified and as directed. | 3 | Each job | 15,100 ₹45,300 | 78,125 ₹2,34,375 | 9,000 ₹27,000 Lowest | 63,000 ₹1,89,000 | 65,000 ₹1,95,000 | 50,000 ₹1,50,000 | 39,999 ₹1,19,997 | 37,999 ₹1,13,997 |
| 8.00 | Supply, installation, commissioning and testing in replacement of float cum boost SCR controlled 110 volt 25 Amps single phase 4 feeder Battery charger and D.C. Distribution Board in a Common Cubicle. The Charger is suitable for 230V +/-10%, AC Input and the Output is suitable to Charge of 110VDC 100AH Batteries and also supply Load. The Output Voltage remains constant within +/- 2 % for AC Input Voltage variation 230V +/- 10% and Load variation 0-100 %. CURRENT RATING: 25.0A complete all as specified and as directed.
(i) Supply and fixing of three core 4 sqmm PVC insulated FRLS copper cables - 90 RM
(ii) Supply, install and commissioning Sealed Maintenance Free VRLA Battery Bank 110Volt. 100AH consisting of 55Nos. Cell of 02Volt each complete with Inter-cell cooper connector, SS Nut Bolt, MS Powder coated stand in factory charged condition.
Note: The Unserviceable equipment disconnected and Transported and deposited to AGE E/M Storeyard. | 1 | Each | 2,49,274 ₹2,49,274 | 4,50,000 ₹4,50,000 | 5,01,111 ₹5,01,111 | 4,00,000 ₹4,00,000 | 4,06,250 ₹4,06,250 | 7,39,000 ₹7,39,000 | 99,999 ₹99,999 Lowest | 3,22,222 ₹3,22,222 |
Tender Value
₹84.5 L
EMD Value
₹1.5 L
Closing Date
25 Aug 2025, 6:00 pmClosed
CWE (AF) Secunderabad
CWE (AF) Secunderabad
SPECIAL REPAIR / REPLACEMENT OF ELECTRIC SUPPLY NETWORK AND OTHER CONNECTED ITEMS AT AFS HAKIMPET
2025_MES_721745_1
84809/E8
Open Tender
Electrical and Maintenance Works
Item Rate
270 days
GE (AF) Hakimpet
As per NIT
9 documents required · 9 mandatory
₹1,000
GE AF HAKIMPET
₹1.5 L
Yes
13 Oct 2025
21 Jul 2025
27 Aug 2025
21 Jul 2025
25 Aug 2025
11 Aug 2025
21 Jul 2025 - 7 Aug 2025
Amount
Supply and install Transformer Step down Outdoor type complete with standard fittings HT, 11KV 3 Phase, LT 433V, 3 Phase, 4 wire copper wound Energy efficiency Level 2 with off load tap changer in 7 steps of 2.5% for range of +/- 7.5% step down outdoor type on HT side to very secondary voltage within limit all as per IS-1180 : 2014 (Amendment No 4 of Mar 2021) of capacity 63 KVA transformer shall be of oil immersed naturally cooled type (ONAN) complete Including disconnecting and takingout from position, transporting and diposited to AGE E/M Store yard consists following specifications complete all as specified and as directed :- (a) Two earthing terminals for body earthing and two additional for neutral brought on bushing. (b) Oil level gauge indicating oil level minimum and maximum. (c) lifting lugs. (d) Drain cum sampling valve. (e) Thermometer pocket. (f) Oil filling hole with cover. (g) Dehydrating breathing device. (h) Rating and terminal marking plates. (j) Three nos of porcelain bushing HT 11 KV with bushing rods, nuts, bolts inside cable end box. (k) One cable box LV side consists of 4 Nos of brass bushing rods with nuts, bolts with two nos of cable glands of suitable size. (l) Explosion vents. (m) Air relief valve plug. (n) Intial filling to transformer oil. Location : Substation at 09 End and 27 End.
All as per Item No 1 here in above but of transformer capacity of 100 KVA Loc: STP AFS
All as per Item No 1 here in above but of transformer capacity of 160 KVA Location: AFNET
All as per Item No 1 here in above but of transformer capacity of 200 KVA , Location : WT, 44R&SU
Supply and install Transformer Step Up Outdoor type complete with standard fittings HT, 11KV 3 Phase, LT 433V, 3 Phase, 4 wire copper wound Energy efficiantLevel 2 all as per IS -1180 : 2014 (Amendment No 4 of Mar 2021) of capacity 100 KVA transformer shall be of oil immersed naturally cooled (ONAN) type complete Including disconnecting and takingout from position, transporting and diposited to AGE E/M Store yard consists following specifications complete all as specified and as directed :- (a) Two earthing terminals for body earthing and two additional for neutral brought on bushing. (b) Oil level gauge indicating oil level minimum and maximum. (c) lifting lugs. (d) Drain cum sampling valve. (e) Thermometer pocket. (f) Oil filling hole with cover. (g) Dehydrating breathing device. (h) Rating and terminal marking plates. (i) Three nos of porcelain bushing HT 11 KV with bushing rods, nuts, bolts inside cable end box. (j) One cable box LV side consists of 4 Nos of brass bushing rods with nuts, bolts with two nos of cable glands of suitable size. (k) Explosion vents. (l) Air relief valve plug. (m) intial filling to transformer oil. Location : Substation ATC.
Supply, installation, testing and commissioning in replacement of Servo controlled voltage stabilizer (Confirming to BIS 9815 (Part-1): 1994, reaffirmation 2019 latest version). Three phase, four wire (RYBN), 50HZ Naturally Oil cooled, indoor, unbalanced type, cooper wound, metallic body duly powder coated with lifting hooks two Nos, digital display type, relay free smooth and silent operation with 1st filling Transformer oil up to level having following specifications:-
(a) Capacity 75 KVA (b) Type – Suitable for unbalanced load and unbalanced input. (c) Input voltage – 360 Volt to 480V, Input frequency 50 HZ. (d) Output voltage – stabilized at any designed/ desired voltage 415 plus or minus 1%. (e) Rated frequency – 50 HZ. (f) Wave form distortion – Nil. (g) Response time – not to exceed 20 milliseconds. (h) Sensitivity – Plus or Minus 1%. (j) Rate of correction – Not less than 6 Volt/ second between phase and neutral. (k) Efficiency – more than 95%. (l) Type of load – three phase, unbalanced type. (m) Metering – Digital display voltmeter/ Ammeter with multi functional meter. (n) Operating temperature – For indoor use up to max ambient temperature + 55 degree centigrade.
(o) Class of insulation – Class F. (p) Mode of operation : Automatic and manual alongwith bypass arangement. (q) Winding temperature rise – Max 55 degree centigrade (10 degree centigrade above operating temp). (r) Transformer oil – IS 335 marked. (s) Core – CRGO M4 Grade/CRNO (Cold Roll Grain Oriented) Cold Rolled Non-oriented). (t) Auto transformer (VARIAC) – 100 Percent copper wound Electrolytic Grade. (u) Losses – As per IS Norms. (v) Power factor – Not less than 0.95 (w) Protection :- (i) Over load protection. (ii) Short circuit protection. (iii) High/low voltage cut off. (iv) By pass arrangement in case of Emergency. (v) Single phase sequence change/ phase fail protection. (vi) Earth fault protection. (x) Standard fitting & Accessories e.g Marking plate, lifting lugs, CI Rollers, Earthing Terminals etc cable box complete all as specified and directed. Each 01 Nos.
M&L Brick platform of size 2.5m x 2.5 m x 1.5 m and upto depth of 1.0 meter below ground in cement mortar 1:6 with PCC foundation 1:4:8 type D-2 using 40 mm graded stone aggregate, PCC 1:2:4, type B-1 using 20 mm graded stone aggregate, 20 cm thick coping over brick work, plastering to exposed surfaces of brick work with cement mortar 1:4, 15mm thick complete all as specified and as directed.
Supply, installation, commissioning and testing in replacement of float cum boost SCR controlled 110 volt 25 Amps single phase 4 feeder Battery charger and D.C. Distribution Board in a Common Cubicle. The Charger is suitable for 230V +/-10%, AC Input and the Output is suitable to Charge of 110VDC 100AH Batteries and also supply Load. The Output Voltage remains constant within +/- 2 % for AC Input Voltage variation 230V +/- 10% and Load variation 0-100 %. CURRENT RATING: 25.0A complete all as specified and as directed. (i) Supply and fixing of three core 4 sqmm PVC insulated FRLS copper cables - 90 RM (ii) Supply, install and commissioning Sealed Maintenance Free VRLA Battery Bank 110Volt. 100AH consisting of 55Nos. Cell of 02Volt each complete with Inter-cell cooper connector, SS Nut Bolt, MS Powder coated stand in factory charged condition. Note: The Unserviceable equipment disconnected and Transported and deposited to AGE E/M Storeyard.
M&L for Earthing complete with galvanized steel earth plate electrode 600x600x6mm thick buried directly in ground earth pit not less than 2.25mtr deep below normal ground level with top edge of the plate not less than 1.5 mtr below ground level connected to galvanized iron or steel earth lead strip 32x6 mm size upto 7.5 mtr long in single length by mean of nut/bolt and washer of galvanized iron or steel as shown in electrical Plate No 3 of SSR part I including necessary excavation in hard/dense soil and earth work GI pipe 20mm dia mediumj grade for watering and GI 40mm dia light grade pipe for protection of GI earth wire etc, PCC chamber with PCC cover in cement concrete 1:2:4 Type B1(20mm graded aggregate), funnel, wire mesh, charcoal dust, salt etc, connected to LT panel board as indicated including testing complete and taking out retrived materials fron U/S earthing complete all as specified and as directed.
S&F in replacement of XLPE insulated screened,PVC bedded, galvanised steel strip or wire armoured, electric power cables (heavy duty) with aluminium conductor, 11000 volts grade,earthed , cross sectional area 95 Sqmm, 3 core HT under ground cable complete all as specified and as directed.
S&F LT XLPE insulated strip armoured multi stranded aluminium underground cable of 185 Sqmm 3.5 core in trenches or fixed on pole/wall or drawn through pipes including suitable size of Lugs & Glands etc complete all as specified and as directed.
All as per Item No 13 above but of cross sectional area of 3.5 core 120 Sqmm
All as per Item No 13 above but of cross sectional area of 4 core 16 Sqmm
All as per Item No 13 above but of cross sectional area of 4 core 10 Sqmm
Excavation in trenches not exceeding 1.5m wide and not exceeding 1.5m depth and getting in hard/dense soil for laying of cables/ for erection of poles/ for stay assembly etc complete all as specified and as directed.
Supply and spread clean dry river sand in trenches for cushioning of cable complete all as specified and as directed. Note: Punned down thickness only shall be measured for the purpose of payment.
Supply and lay un-reinforced precast concrete cable cover, Class LV , Type - I flat size 250 x 150 x 40 mm laid dry in treches over under ground cables complete all as specified and as directed.
Returning, filling in trenches including spreading, levelling, watering and well ramming in layers not exceeding 25 cm complete all as specified and as directed.
Removing surplus excavated material to a distance not exc 50m and depositing where directed at a level not exceeding 1.5m above the starting point complete all as specified and as directed.
Supply and lay un-reinforced precast concrete cable cover , class HV , Type I flat size 300 x 180 x 40 mm laid dry in treches over under ground cables complete all as specified and as directed.
S&F Octagonal shaped GI hot dipped electric pole, Polished finished (7 metre long) complete with PCC base, bolts, nuts, washers and base plaes including the following complete all as specified and as directed :- (a) Excavation in post hole not exceeding for pole foundation & getting out in soft loose soil, returning, filling in the excavated soil after fixing the pole in foundation, ramming earth around in layers n.exc 25 cm thick and disposal of surplus soil to a distance n.exc 50 metres. (b) M&L for Providing RCC 1:4:8, type D2 (using 40 mm graded stone aggregate) in foundation as per manufacturers design upto GL including Nuts, bolts, washers and base plates of suitable size and length for grouting in as per manufacturer's design. (c) Inbuilt internal junction box consists of incomer of MCB TPN 32 Amp 10 KA and alluminium connector 16 Amp, 03 phase, 04 Nos fixed on epoxy insulated pole and internal wiring complete.
Supply and fix in repair LED street light fitting 60 Watt 230 V AC outdoor type with high pressure die cast aluminum hosing and heat resistant complete with driver, lamp bracket with impact and corrosion resistant including thermal management in multiple optics complete with IP 66 protection complete all as specified and as directed.
Dismantling of PCC Poles of any size, type, make complete all as specified and as directed.
Dismantling of ACSR conductor of any size, make, type complete all as specified and as directed.
Dismantling of insulators of any type, make complete all as specified and as directed.
Dismantling of Cross arms of MS Channel of any size, make, type complete all as specified and as directed.
Dismantling of street light fitting including bracket of any size, make, type and deposit at MES E/M Store complete all as specified and as directed.
Supply and connect PVC insulated, PVC Sheathed three core cable with stranded aluminium conductor of size 2.5 sqmm complete all as specified and as directed.
Dismantling of all electrical connections and takingdown from its original position and handedover to complete set to AGE E/M Storeyard and Supply and fixing of Single Girder Type H.O.T Crane 1.0 Ton capacity as per IS 801 & IS 4137 Standard crane with Two coats of primer and two coats of golden yellow Paint, RAL 1004 and carrying load testing as per manufacturer recommendations and following specifications of crane are as follows complete all as specified and as directed :- (a) Main Girder : I Beam type Girder (b) Span : 12 meters (c) Height of Lift : 9 meters (Actual lift will be set as per site condition ) (d) Chain Pully block : 6 mm dia, grade 80 (e) 1 Fall (f) Open Type End carriage (g) Gantry & rail 22 meters + 22 meters Long travel (h) Hook : Pulley, swivelling C Type Hook IS:3815 (j) LT Wheel : En8, (hardness 200 to 250 BHN), Flanged (k) CT Wheel : En8 (Hardness 200 to 250 BHN), Flanged. Location : 12 TS
M&L cable jointing Kit in replacement for 11KV grade cable for outdoor termination, heat shrink type joint complete with jointing material and accessories suitable for 3 core XLPE armoured aluminum conductor cable of size 95 Sqmm complete all as specified and as directed.
Supply, installation, testing and commissioning of oudoor type double door cubicle panel board suitable for 3 phase, 50 Hz supply system CPRI approved factory fabricated made out of 3 mm thick CRCA sheet for outer shell and 2 mm thick for inner shell with front and rear openable double lief doors with locking arrangement complete with powder coat painting and suitable packing material for IP- 55 degree of protection and confirming to IS:8623-1993 and including 50mmx50mmx6mm angle iron base frame of suitable size for mounting the panel board at a height of 450mm from GL and grouted on PCC foundation complete all as specified and directed by Engineer-in-Charge. The size of panel board shall be suitable for accommodating and including provision of following switchgears complete:- (a) Aluminium bus bar of capacity 250 Amp with heat shrinkable coloured PVC sleeve insulation mounted on suitable insulators for 3 phases and half of the capacity for neutral - 01 Set (b) Incomer MCCB of 160 Amps 16 KA -01 Nos (d) LED type pilot indicator lamps for R,Y,B phases - 01 Set of 3 (e) Hardware of panel board including bolt, nuts gaskets etc. (f) Errection, testing & commissioning including PCC foundation blocks of 2x PCC block of size, 500mm x 300 mm x 100 mm for grouting of panel as directed by Engr In Charge - 01 Job
M/S ADHIKARI CONSTRUCTION CO. (BID ID -3397775)
OM SAI POWER SYSTEMS (BID ID -3397559)
Roy and Sons Infrastructures (BID ID -3398303)
Haasith constructions (BID ID -3404739)
M/S AMRIT DAS MAHAPATRA (BID ID -3398154)
Srinivasa Consructions (BID ID -3404757)
VBK ELECTRICALS AND AGENCIES PRIVATE LIMITED (BID ID -3403866)
stage.html
html • 0.06 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .