Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹67.5 LAdmitted-Finance 205 PARSHAV VIHAR PLOT NO 50 IP EXTN PARPARGANJ DELHI 110092 | EAST | DELHI | 110092 | ₹67.5 L | L1 | Admitted-Finance |
| 2 | L2₹67.7 L+₹16,205 (0.24%)Admitted-Finance | ₹67.7 L+₹16,205 (0.24%) | L2 | Admitted-Finance |
| 3 | L3₹68.1 L+₹58,947 (0.87%)Admitted-Finance 441 G F LIG FLATS PH 2 SEC 14 PKT 3 DWARKA NEW DELHI SECTOR 14 DWARKA DWARKA SOUTH WEST DELHI DELHI 110078 | SOUTH WEST DELHI | DELHI | 110078 | ₹68.1 L+₹58,947 (0.87%) | L3 | Admitted-Finance |
| 4 | Rejected-Technical A 3 257 JANAKPURI NEW DELHI 110058 | WEST DELHI | DELHI | 110058 | - | - | Rejected-Technical REJECTED DUE TO NOT SUBMITTED MOU |
| Sl No | Description | Qty | Unit | Saini Enterprises L1 | J D ENTERPRISES L2 | OMVIN ENTERPRISES LLP L3 |
|---|---|---|---|---|---|---|
| 1.00 | M&L for Comprehensive Maintenance of Diesel Generator (DG) Set mentioned at Appx-A, covering all routine scheduled services, running repairs, breakdown maintenance and replacement of all wear-and-tear parts, lubricants, filters, and consumables necessary for the smooth and reliable operation of the DG set.
The scope includes:
1.Preventive Maintenance: Execution of all mandatory periodic services (A-Check, B-Check, C-Check,D-Check as per OEM), including replacement of Engine Oil, Coolant, Fuel Filters, Oil Filters, Air Filters, and all associated consumables (The item should be measure and paid seperatly in repective item of this schedule).
2.Breakdown Maintenance: Unlimited call-outs for emergency breakdown repairs, including all required labor and consumables.
3.Replacement of Parts: Replacement of all non-structural, wear-and-tear components (e.g., fan belts, hoses, sensors, batteries, minor electrical components, etc.) that fail or require replacement during the contract period to ensure operational readiness. Excludes major engine overhaul components (e.g., block, crank, major alternator winding) unless explicitly stated in the contract/tender documents.
4.Testing and Load Trials: Quarterly load banking or on-load testing of the DG set for a minimum duration of 1 hour, documenting performance parameters (voltage, frequency, current, oil pressure, temperature).
5.Logbook and Reporting: Maintaining a comprehensive service logbook and providing detailed service reports after every PM visit and breakdown call.
NOTE:-All work shall be carried out only by authorised Rep of OEM and using all genuine spare parts supplied by OEM only, in this regard an Annual Maintenance Contract (AMC). In this regard, a Memorandum of Understanding (MOU) must be executed between the Contractor and either M/S Airmen Engineers & Services Private Limited or M/S Powerol Services or any authorized services dealer of the OEM. | 11 | Per Month | 86,000 ₹9,46,000 | 69,150 ₹7,60,650 | 60,000 ₹6,60,000 Lowest |
| 1.01Appx-A 1.Main Power House - 320 KVA 2.Trauma Center-320 KVA 3.Gynae Department- 40 KVA 4.GE Center-200KVA 5.ICU Base Hospital-62.5 KVA 6.Sur III -200 KVA 7.CPL Lab- 160 KVA 8.X-Ray Sub- 320 KVA 9.OT S/S - 500 KVA 10. Pump House-160 KVA 11.Ortho-I &II - 200 KVA 12.NICU Ward- 160 KVA 13.Dialysis Center-62.5 KVA 14.Morchary BHDC-50 KVA 15.Psy Ward-160 KVA 16.Pead Ward-100 KVA 17.OT S/S - 160 KVA 18.Trauma Center-160 KVA 19.COVID ICU- 400 KVA 20.NEW OPD -750 KVA | ||||||
| 1.02General Terms and Condition For Item no 01 (i) All work shall be carried out through an Annual Maintenance Contract (AMC), utilizing genuine spare parts provided by the OEM only. (ii) Contractor should be responsible of proper functioning of all the system from current condition (either in malfunctioning or working) in the initial phase of contract and rate for for the same shall be included in the quoted. Nothing extra in that respect shall be paid to the contractor. (iii) Contractor shall be resonsible for repair and replacement of all defective parts of the equipment as per Engg-in-charge recommendation during entire comprehensive maintenance period. (iv) Preventive maintenance of all systems on monthly basis. (v) Attending all complaints within 24 working hours intimated by Engg-in-Charge. (vi) Field service report shall be maintained and submitted to the Engg-incharge after expiry of every month and before submission of RAR . (vii) The rates quoted by the contractor shall deemed to be inclusive of T&P etc | ||||||
| 1.03 | Supply only Kit fuel filter insert prim & sec cat part no. 123306370785 complete in all aspect all as specified and as directed. | 12 | Each | 490 ₹5,880 | 400 ₹4,800 | 350 ₹4,200 Lowest |
| 1.04 | Supply only L.O. filter and element V8/V6 cat part no. 605411880009 complete in all aspect all as specified and as directed. | 12 | Each | 690 ₹8,280 | 450 ₹5,400 | 350 ₹4,200 Lowest |
| 1.05 | Supply only air filter element primary 8" (XRB08) cat part no. 141109234232 complete in all aspect all as specified and as directed. | 6 | Each | 1,450 ₹8,700 Lowest | 3,500 ₹21,000 | 2,600 ₹15,600 |
| 1.06 | Supply only air filter element safety 8" (XRB08) cat part no. 141109234233 complete in all aspect all as specified and as directed. | 6 | Each | 780 ₹4,680 Lowest | 1,500 ₹9,000 | 2,000 ₹12,000 |
| 1.07 | Supply only element-pre-fuel filter cat part no. 1200240911 complete in all aspect all as specified and as directed. | 42 | Each | 355 ₹14,910 | 275 ₹11,550 Lowest | 300 ₹12,600 |
| 1.08 | Supply only element-micro-fuel filter cat part no. 1200240912 complete in all aspect all as specified and as directed. | 42 | Each | 365 ₹15,330 | 250 ₹10,500 | 200 ₹8,400 Lowest |
| 1.09 | Supply only lube oil filter(232V12) cat part no. 605411880008 complete in all aspect all as specified and as directed. | 24 | Each | 995 ₹23,880 | 700 ₹16,800 Lowest | 850 ₹20,400 |
Tender Value
₹64.8 L
EMD Value
₹1.2 L
Closing Date
15 Aug 2026, 6:00 pmClosed
CWE DELHI CANTT
HQ CWE DELHI CANTT 110010
COMPREHENSIVE MAINTENANCE AND REPAIR MAINT OF DG SET INSTALLATION AND LIFT INCLUDING BATTERY COLLANT AND OTHER CONNECTED PANELS AT VARIOUS WARDS AT BHDC AND NEW OPE AND OTHER LOCATION UNDER GE EAST DELHI CANTT
2026_MES_758854_2
CWE/D-104/2025-26
Open Tender
Civil Works
Item Rate
270 days
DELHI CANTT
Please refer Tender documents.
7 documents required · 7 mandatory
₹1,000
GE EAST DELHI CANTT
₹1.2 L
Yes
2 Sept 2026
18 Jul 2026
17 Aug 2026
18 Jul 2026
15 Aug 2026
1 Aug 2026
| Sl No | Description | Qty | Unit | Est. Rate | Est. Amount |
|---|---|---|---|---|---|
| 1 | M&L for Comprehensive Maintenance of Diesel Generator (DG) Set mentioned at Appx-A, covering all routine scheduled services, running repairs, breakdown maintenance and replacement of all wear-and-tear parts, lubricants, filters, and consumables necessary for the smooth and reliable operation of the DG set.
The scope includes:
1.Preventive Maintenance: Execution of all mandatory periodic services (A-Check, B-Check, C-Check,D-Check as per OEM), including replacement of Engine Oil, Coolant, Fuel Filters, Oil Filters, Air Filters, and all associated consumables (The item should be measure and paid seperatly in repective item of this schedule).
2.Breakdown Maintenance: Unlimited call-outs for emergency breakdown repairs, including all required labor and consumables.
3.Replacement of Parts: Replacement of all non-structural, wear-and-tear components (e.g., fan belts, hoses, sensors, batteries, minor electrical components, etc.) that fail or require replacement during the contract period to ensure operational readiness. Excludes major engine overhaul components (e.g., block, crank, major alternator winding) unless explicitly stated in the contract/tender documents.
4.Testing and Load Trials: Quarterly load banking or on-load testing of the DG set for a minimum duration of 1 hour, documenting performance parameters (voltage, frequency, current, oil pressure, temperature).
5.Logbook and Reporting: Maintaining a comprehensive service logbook and providing detailed service reports after every PM visit and breakdown call.
NOTE:-All work shall be carried out only by authorised Rep of OEM and using all genuine spare parts supplied by OEM only, in this regard an MOU between OEM i.e M/S Cotton Greaves and the Contractor must be perform , A copy of the same MOU shall be uploaded with the tender document . | 11 | Per Month | - | - |
| 1.01 | Appx-A
1.Main Power House - 320 KVA
2.Trauma Center-320 KVA
3.Gynae Department- 40 KVA
4.GE Center-200KVA
5.ICU Base Hospital-62.5 KVA
6.Sur III -200 KVA
7.CPL Lab- 160 KVA
8.X-Ray Sub- 320 KVA
9.OT S/S - 500 KVA
10. Pump House-160 KVA
11.Ortho-I &II - 200 KVA
12.NICU Ward- 160 KVA
13.Dialysis Center-62.5 KVA
14.Morchary BHDC-50 KVA
15.Psy Ward-160 KVA
16.Pead Ward-100 KVA
17.OT S/S - 160 KVA
18.Trauma Center-160 KVA
19.COVID ICU- 400 KVA
20.NEW OPD -750 KVA | - | - | - | - |
| 1.02 | General Terms and Condition For Item no 01
(i) All work shall be carried out only by authorised Rep of OEM and using all genuine spare parts supplied by OEM only.
(ii) Contractor should be responsible of proper functioning of all the system from current condition (either in malfunctioning or working) in the initial phase of contract and rate for for the same shall be included in the quoted. Nothing extra in that respect shall be paid to the contractor.
(iii) Contractor through OEM shall be responsible for repair and replacement of all defective parts of the equipment as per OEM recommendation during entire comprehensive maintenance period.
(iii) Preventive maintenance of all systems on monthly basis.
(iv) Attending all complaints within 24 working hours intimated by Engg-in-Charge.
(v) Field service report shall be maintained and submitted to the Engg-incharge after expiry of every month and before submission of RAR .
(vi) The rates quoted by the contractor shall deemed to be inclusive of T&P etc | - | - | - | - |
| 1.03 | Supply only Kit fuel filter insert prim & sec cat part no. 123306370785 complete in all aspect all as specified and as directed. | 12 | Each | - | - |
| 1.04 | Supply only L.O. filter and element V8/V6 cat part no. 605411880009 complete in all aspect all as specified and as directed. | 12 | Each | - | - |
| 1.05 | Supply only air filter element primary 8" (XRB08) cat part no. 141109234232 complete in all aspect all as specified and as directed. | 6 | Each | - | - |
| 1.06 | Supply only air filter element safety 8" (XRB08) cat part no. 141109234233 complete in all aspect all as specified and as directed. | 6 | Each | - | - |
| 1.07 | Supply only element-pre-fuel filter cat part no. 1200240911 complete in all aspect all as specified and as directed. | 42 | Each | - | - |
| 1.08 | Supply only element-micro-fuel filter cat part no. 1200240912 complete in all aspect all as specified and as directed. | 42 | Each | - | - |
| 1.09 | Supply only lube oil filter(232V12) cat part no. 605411880008 complete in all aspect all as specified and as directed. | 24 | Each | - | - |
stage.html
html • 0.03 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 0.53 MB
TENDERDOUCMENT.pdf
Tender Documents • 1.55 MB
BOQ_873047.xls
BOQ • 0.38 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .