Loading…
Loading…
| # | Company | Quoted % | Amount | Rank | Status |
|---|---|---|---|---|---|
| 1 | L1₹4.9 LAdmitted-Finance | -45.25% | ₹4.9 L | L1 | Admitted-Finance |
| 2 | L2₹5.1 L+₹20,104.17 (4.13%)Admitted-Finance | -42.99% | ₹5.1 L+₹20,104.17 (4.13%) | L2 | Admitted-Finance |
| 3 | L3₹5.7 L+₹87,800.06 (18.0%)Admitted-Finance WZ 400 PALAM VILLAGE DELHI WEST DELHI SOUTH WEST DELHI DELHI 110045 | SOUTH WEST DELHI | DELHI | 110045 | -35.38% | ₹5.7 L+₹87,800.06 (18.0%) | L3 | Admitted-Finance |
Tender Value
₹8.9 L
EMD Value
₹17,791
Closing Date
26 May 2026, 3:00 pmClosed
EE(E)/ELD-5/DDA
CENTRAL NURSERY SECTOR 5 DWARKA NEW DELHI
Running maintenance...................Split AC at Community Hall at Sector 2, Dwarka
2026_DDA_909349_1
06/EE/ELD-5/DDA/2026-27
Open Tender
Electrical Works
Works
90 days
EE(E)/ELD-5/DDA
Please refer Tender documents.
15 documents required · 15 mandatory
₹0
₹17,791
12 Jun 2026
19 May 2026
28 May 2026
19 May 2026
26 May 2026
19 May 2026
This is a percentage-rate BOQ. The schedule below shows estimated quantities and rates. Bidders quote a single percentage above or below the total estimated cost.
| Sl No | Description | Qty | Unit | Est. Rate | Est. Amount |
|---|---|---|---|---|---|
| 1 | Running maintenance & operation of 62.5 KVA D.G set, Fire Fighting pump system, ventilation & liftwell pressurization system, clear water booster pump, fire alarm system, PA system, Lift and General Lighting as per inventory terms and condition attached. | 9 | Per Month | 75,353 | ₹6,78,177 |
| 2 | Servicing of 62.5 KVA D.G. set (GREAVES make) i/c S/R of following parts/accessories, cartage testing on load etc complete as reqd.
i) Oil filter --- 1 No.
ii) Diesel filter (pre-micro)--- 1 set
iii) Air cleaner elements --- 1 No.
iv) Coolant ---- 5 ltr.
v) Engine Oil ,
vi) Labour charges for servicing, functioning and testing--- 1 job
vii) Radiator cleaning charges --- 1 job i/c removal & refixing Viii) Battery 110AH ix) Positive & Negative battery cable | 1 | Job | 24,671 | ₹24,671 |
| 3 | Supplying, installation, Testing & Commissioning of LED surface mounted Batten light of following body material and construction as per IS : 10322 with driver (Replaceable) as per the requirement with Driver efficiency >85% ,Operating voltage AC 140-270 Volt, freq 50/60 hz, Operating temp range -15 deg to 40 deg centigrade, internal surge protection of 2.5 KV with Short & Open circuit protection ,THD < 10% , P. F.≥0.95, IP20, CRI >80, Flicker free, (flicker should be below 5 %), life time (LED,Driver & electrical circuitary), of minimum 50000 Burning Hours with , 70% of initial Lumen maintained till life ends, CCT 3000°K / 4000°K / 5700°K /6000°K/6500°K (As per ANSI Bin), SDCM(Standard Deviation Color Matching) <3, Maximum power consumption should not more than the specified rating and Fixture shall be of relevant BIS standard and trade mark certificate ( T.C.). Manufactures Word Mark/ Name Engraved/ Embossing/ Screen printing on housing. complete in all respect i/c connections with 1.5 sq mm FRLS, PVC insulated copper conductor single core cable and earthing etc. as required with Minimum 5 year OEM warranty. System lumen efficacy ≥105 <120 lm/Watt output . LM79 & LM80Test report from NABL lab for all testing required for LED fixtures 8 per BIS shall be submitted. Shape size and CCT shall be as approved by Engineer-in-Charge as per requirement. (Thermal management: heat sink of aluminum housing such that LED junction temperature shall not rise above 90°C).
18- 22 watt | 45 | Each | 418 | ₹18,810 |
| 4 | Supply, Installation, Testing and Commissioning of ceiling fan with Brush Less Direct Current (BLDC) Motor, class of insulation: B, 3 nos. metal (Aluminum alloy) blades, 30 cm long down rod, 2 nos. canopies, shackle kit, safety rope, copper winding, steel/Al body Power Factor not less than 0.9,Service Value (CM/M/W) minimum as below, 350 RPM (tolerance as per IS : 374-2019), THD (Total Harmonic Distortion) less than 10%, suitable for operation with regulator for speed control and all remainingaccessories including safety pin, nut bolts, washers, temperature rise=75degree C (max.), insulation resistance more than 2 mega ohm, suitable for 230 V, 50 Hz, single phase AC Ceiling Fan compliant to IS 374:2019 fan
Supply, earthing etc. complete as req
1200mm, service value ≥ 6.0 CM/Min/Watt, air delivery 210 CM/Min(Minimum) | 12 | Each | 2,426 | ₹29,112 |
| 5 | Supplying and fixing 5 A to 32 A rating, 240/415 V, 10kA, "C" curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required. Single pole | 16 | Each | 185 | ₹2,960 |
| 6 | Double pole | 8 | Each | 592 | ₹4,736 |
| 7 | Triple pole and neutral | 2 | Each | 1,191 | ₹2,382 |
| 8 | Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc. as
required. 5/6 A switch | 25 | Each | 47 | ₹1,175 |
| 9 | 3 pin 5/6 A socket outlet | 25 | Each | 86 | ₹2,150 |
| 10 | 15/16 A switch | 10 | Each | 102 | ₹1,020 |
stage.html
html • 0.03 MB
tech_eval.pdf
boq_comp_chart.xlsx
xlsx
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 4.92 MB
NIT06PDF.pdf
Tender Documents • 2.41 MB
BOQ_955743.xls
BOQ • 0.34 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .