Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹7.4 LAccepted-AOC | L1 | Accepted-AOC L1 Bidder. | |
| 2 | L2₹7.4 L+₹6,543 (0.89%)Rejected-Finance | L2 | Rejected-Finance Not L1 Bidder. | |
| 3 | L3₹7.4 L+₹7,900 (1.07%)Rejected-Finance 17 BIPIN GANGULY ROAD KOL 30 | L3 | Rejected-Finance Not L1 Bidder. |
Tender Value
Refer Docs
EMD Value
₹14,900
Closing Date
11 Apr 2025, 12:30 pmClosed
Executive Engineer, PWD, DDED
Purta Bhavan,4 th Floor,Kachari Road,Balurghat,Dakshin Dinajpur,Pin-733101
Construction of New Fair Price Medicine Shop in the campus of Raiganj Government Medical College and Hospital -- Electrical Installation, AC, UPS, Fire Detection and allied works. (Electrical Work),Project ID - HF242526307S000
2025_WBPWD_831068_1
WBPWD/EE/DDED/e-NIQ- 40 of 2024-25
Open Tender
ELECTRICAL WORKS ORG
Item Rate
30 days
Raiganj, Uttar Dinajpur
Please refer Tender documents.
5 documents required · 5 mandatory
₹14,900
10 Jun 2025
26 Mar 2025
16 Apr 2025
26 Mar 2025
11 Apr 2025
26 Mar 2025
Amount
INTERNAL ELECTRICAL INSTALLATION
S&F of 415V, 125A TPN SFU with sheet steel enclosure on angle iron frame on wall with nuts bolts etc incl. S & F 3 nos. DIN type HRC fuse as per rating, as per GS. [Make: Siemens/L&T/Havells]
S&F of 415V, 63A TPN SFU with sheet steel enclosure on angle iron frame on wall with nuts bolts etc incl. S & F 3 nos. DIN type HRC fuse as per rating, as per GS .[Make: Siemens/L&T/Havells]
S&F of 415V, 32A TPN SFU with sheet steel enclosure on angle iron frame on wall with nuts bolts etc incl. S & F 3 nos. DIN type HRC fuse as per rating, as per GS. [Make: Siemens/L&T/Havells]
S&F 415 V, Horizontal type, TPN MCB DB (4-way) with SS enclosure double-door with IP-42/43 protection, with Four Pole Isolators as incomer and SPMCBs ('C' Curve, 10 KA) as outgoing, concealed in wall after cutting the wall & mending good the damages to original finish incl. Inter connection with suitable size of copper wire and neutral link & provision for earthing attachment as per GS. INCOMING-63 A FP Isolator -1 No. OUTGOING-6-32A SPMCB-18 Nos. [Make - Legrand/Siemens/Havells/L&T ]
S&F 250V, SPN MCBDB (2+12) way with SS enclosure double-door (Ivory White with IP-42/43 protection with DP Isolators as incomer and SPMCBs ('C' Curve, 10kA) as outgoing, concealed in wall after cutting the wall & mending good the damages to original finish incl. Inter connection with suitable size of copper wire and neutral link & provision for earthing attachment as per GS.INCOMING-40 A DP Isolator OUTGOING-12 Nos. 6-10A SPMCB [Make - Legrand/Siemens/Havells/L&T]
Supplying and Drawing 1.1 KV single core stranded 'FR' PVC insulated & unsheathed single core stranded copper wire (Brand approved by EIC) of the following sizes in the prelaid polythene pipe and by the prelaid GI fish wire and making necy. connection as required as per GS. [Make-Finolex/KEI/Havells/Polycab]
Do - Do - Do - 2x6sqmm + 1x4sqmm [HTPNDB to SPNDB]
Do - Do - Do - 2x4sqmm + 1x2.5sqmm [for AC]
Do - Do - Do - 2x2.5sqmm + 1x1.5sqmm [for Power plug, Comp. board]
Do - Do - Do - 3x1.5sqmm
Finising the end of above PVC insulated & unsheathed copper wire as per GS.
Do - Do - Do - 2x6sqmm + 1x4sqmm
Do - Do - Do - 2x4sqmm + 1x2.5sqmm
Do - Do - Do - 2x2.5sqmm + 1x1.5sqmm
Distn. wiring in 22/0.3 (1.5 sqmm) single core stranded 'FR' PVC insulated & unsheathed single core stranded copper wire (Brand approved by EIC) in 19 mm bore, 3 mm thick polythen pipe complete with all accessories embedded in wall to light/fan/call bell points with Modular type switch (Brand approved by EIC) fixed on Modular GI switch board with top cover plate flushed in wall incl. mending good damages to original finish 2x22/0.3 (Ph. & N) and 1x22/0.3 as ECC (Average run 7 mtr)
Supply & Fixing 240V, Modular Socket (2 Module) type fan regulator (Step type) (Brand approved by EIC) on existing Modular GI switch board with top cover plate incl. making necy. connections etc., as per GS.
Do - Do - Do - with to 240 V 6A 5 pin plug point incl. S&F 240 V 6A 3 pin Modular type plug socket & Modular type switch (Brand approved by EIC) incl. S&F earth continuity wire, fixed on 4 Module GI switch board with 3/4 Module top cover plate - Do - Do - Do - (On board )
S&F 240 V, 4 nos. 16 A, 3 pin Modular type plug socket with 4 nos. 16A Modular type switch (Brand approved by EIC), 20A Modular switch type SP MCB (C-Curve) and Indicator without plug top on 2 row 18 Module GI Modular type switch board with 2 row 18 Module top cover plate flushed in wall incl. S&F switch board and cover plate and making necy. connections with PVC Cu wire and earth continuity wire etc., as per GS.
S&F 240 V, 20 A, 3 pin Modular type plug socket (Brand approved by EIC) with 20A Modular type switch, without plug top on 4 Module GI Modular type switch board with top cover plate flushed in wall incl. S&F switch board and cover plate and making necy. connections with PVC Cu wire and earth continuity wire etc., as per GS.
Supply & Fixing 240 V, 25 A, 3 pin Modular type plug socket (Brand approved by EIC), incl. S&F 1no 240 V, 25 A, 3 pin Modular type plug top (Brand approved by EIC) and switch with 2 Module GI Modular type switch board with top cover plate flushed in wall and making necy. connections with PVC Cu wire and earth continuity wire as per GS.
S/F 240 V, 25 A, Modular type starter (Brand approved by EIC) with 25A Modular switch type DP MCB (CCurve) and 4 Module GI Modular type switch board with 4 Module top cover plate flushed in wall incl. S&F switch board and cover plate and making necy. connections with PVC Cu wire and earth continuity wire etc. as per GS.
Supplying & Fixing Industrial Plug & Socket board with 240 V, 20A, SPN & Earth Metal Industrial Plug socket & 20A Industrial top incl. S&F 20 A SP MCB breaking capcity 10kA (C- Curve) in SS enclosure fixed on wall and cecessary conection. [For UPS] [Make - Legrand/Siemens/Havells/ABB]
Supply & Delivery 4 core 25 sqmm XLPE/PVC Ar Al cable, as per direction of EIC. [Make - Polycab/Havells/RR Kabel]
Laying of one no above cable in u/g trench 460mm wide x 760mm average depth, with brick protection on the top of the cable with 8 (eight) Nos. bricks per Mtr. including filling the space between the bricks & cable and also the trenchwith shifted soil, leveling up & restoring surface duly rammed, as per GS.
S&F and fixing compression type gland complete with brassgland, brass ring & rubber ring for dust & moisture-proof entry of 4C 25 sqmm XLPE/PVC armoured cables, as per GS.
Finishing of 4 core 25 sqmm XLPE/PVC insulated armoured cable ends by soldering with cable sockets and insulated tapes etc., including supplying sockets, soldering materials, tapes etc. and making connection to switch, BDB and BBC etc., as per GS.
Supply and delivery of Single LED Fitting (20Watt, 230VAC, 50hZ, 4000K NW, THD<10%, bult in 2.5KV SPD) with all accessories and 1 nos LED Tube [Make: Philips TMC 502 P 1xT-LED, Havells, Bajaj, CG, Wipro, Legaro, Halonix, Panasonic or as per EIC]
Supply and delivery of Twin LED Fitting (2x20Watt, 230VAC, 50hZ, 4000K NW, THD<10%, bult in 2.5KV SPD) with all accessories and 1 nos LED Tube [Make: Philips TMC 502 P 2xT-LED, Havells, Bajaj, CG, Wipro, Legaro, Halonix, Panasonic or as per EIC]
Fixing only single/twin fluorescent light fitting suspended 25 cm bellow the ceiling with 2 No. 20 mm dia EI conduit (14 SWG) supports fixed with “L” type MS clamp whose one side fixed on ceiling with sutable size 4 nos. fastener and other side connected with the conduit with suitable size of bolts and nuts incl. S&F EI conduit, “L” type (125mmx125mm) 6mm thick and 25mm with MS clamps and connecting the length of PVC insulated wire and mending good damages to original finish and painting etc. by 2x24/0.20 mm (1.5sqmm.) flexible copper wire of 1.10 mt. length, as per GS.
Extra for suspension exceeding 25 cm with S&F additional 2 no. 20 mm dia EI conduit (14 SWG) supports & necy. PVC insulated wire and painting etc. as required by 2x24/0.20 mm (1.5sqmm.) flexible copper wire of 1.10 mt. length., as per GS.
Supply & delivery of 1200 mm sweep 230 volt AC Ceiling fan incl. Blades, canopy etc. With 18" down rod(14SWG), Fork(10SWG), Heavy type insulator, 3/8th inch bolt with nut, heavy type split pin etc., as directed by EIC [Make-Orient - New Breeze/Summercool or similar spec of Crompton/Usha Striker ]
Fixing only ceiling fan complete with blades, canopy, fork, rubber bush etc. incl. S&F connecting wire for down rod upto 30 cm incl. painting the rod with approved paint and making necessary connection as required by 2x1.5 sqmm flexible copper wire, as per GS.
Supply and delivery of 230V 450mm sweep Wall-fan, as directed by EIC. [Make: Orient-Tornado Wall II-Gun Metal / Usha / Crompton / Havells]
Fixing only cabin/wall fan on wall/ceiling by S&F rag bolts, nuts & washers (6mm dia x 62mm long) or as reqd. incl. S&F 24/0.20 PVC insulated flexible copper wire 0.5 mt. length, as per GS.
S&F of 9W LED lamp on exsting angular batten, as directed by EIC.
Earthing with 50mm dia GI pipe (ISI-M) 3.64mm thick x 3.04 Mts. long and 1x4 SWG GI (Hot Dip) wire (4 Mts. long), 13mm dia x 80mm long GI bolts, double nuts, double washers incl. S&F 15 mm dia GI pipe protection (1 Mts. long) to be filled with bitumen partly under-ground level and partly above-ground level driven to an average depth of 3.65 Mts. below the ground, as per GS.
Excavation of soil for installation of Earth Electrode and filling & ramming, for Soft Soil, as per GS.
S&F earth busbar of galvanized (Hot Dip) MS flat 25 mm x 6 mm on wall having clearance of 6 mm from wall including providing drilled holes on the busbar complete with GI bolts, nuts, washers, spacing insulators etc. as reqd., as per GS.
Connecting the equipments to earth busbar incl. S&F 2x8SWG GI (Hot Dip) wire on wall/floor with staples buried inside wall/floor as required and making connection to equipments with bolts, nuts, washers, cable lugs etc. as reqd. & mending good damages as per GS.
S&F 40 mm dia medium gauge GI Pipe (ISI-Medium) Protection with necessary fittings and jointing metarials as reqd, as per GS.
S&F of 250V double door AC Timer DB [equivalent of 2+8 way SPNDB] with sheet steel enclosure, pnosphitised powder coated neutral bar, DIN rail with IP-43 potection comprising with 1 no. 25A DPMCB ('C' curve 10KA), 1no. Programmable time switch-24 hrs with minimum switching of 15 minutes and 1 no. 18A/25A 2-Pole power contractor with inner-outer plate & internal wiring by suitable size of cu. wire incl. 1 no. Auto-Manual bypass toggle switch and provision for earthing attachment, incl. LED indication light for running condition with mechanical locking arrangement, as directed by EIC. [Make-ABB/L&T/Crabtree]
COMPOUND LIGHTING:
Fixing only above LED light fitting complete with all accessories to be fixed /projected from the wall of the building incl. making holes/providing clamping arrangement & necy. GI reducer as required. S&F 40 mm GI pipe (ISI-Medium) quality 1.5 mts. average length having suitable bend S&F necy. length of 1.5 sqmm PVC insulated single core stranded annealed copper wire and making connections as required and mending good damages to wall incl. painting etc., as directed by EIC.
Supply & delivery of 250V, 15W (Maximum) LED street light with IP-66, individual Secondary Optics Peanut Lens and Separate Toughned Glass Diffuser, Potted Driver to be used, 7000 lumen (minimum) output fittings, as directed by EIC [Make: Philips : BRP04214 CW MR S1 PSU PSU GR or equivalent spec of Havells /Crompton]
Supplying & Fixing GI waterproof type looping cable box size 200x150x100 mm deep having 4 mm thick comprising of one 250V 15 A kit-kat fuse unit, one NL on porcelain insulator, one compression type brass cable gland for upto 2- core 16 sqmm PVC/A cable and having lined with rubber gasketted GI top cover with brass machine screws etc., earthing terminal with lug, on steel tubular pole near base, including S&F 40x6 mm thick, MS clamps with bolts, nuts etc. including painting with anticorrosive paint, as per GS.
Wiring by 3x 1.5 sqmm single core PVC insulated copper wire through polythene pipe from loop box to fitting as per GS.[Make-Finolex/KEI/Havells/Polycab]
Supply & Delivery of 1.1 kv grade 2Cx6 sqmm XLPE-armoured AL. cable, as directed by EIC. [Make - Polycab/Havells/RR Kabel]
Laying of above 2Cx6 sq.mm. XLPE/Ar. AL Cable on wall/surface incl. S&F MS saddles with earthing attachment in 10 SWG GI (Hot Dip) Wire, making holes etc. as necy. mending good damages and painting, as per GS.
S&F compression type gland complete with brass gland, brass ring & rubber ring for dust & moisture-proof entry of 2Cx6 sqmm XLPE/PVC armoured cable, as per GS.
Finishing the end of 2Cx6 sqmm XLPE/PVC armoured cable by crimping method incl. supplying and fixing solderless socket (Dowels make), tapes, anticorrosive paste & jointing materials, as per GS.
S&F of 250V double door Timer DB [equivalent of 2+8 way SPNDB] with sheet steel enclosure, pnosphitised powder coated neutral bar, DIN rail with IP-43 potection comprising with 1 no. 25A DPMCB ('C' curve 10KA), 2 no. 16A SPMCB ('C' curve 10KA), 1no. Programmable time switch-24 hrs with minimum switching of 15 minutes and 1 no. 18A/25A 2-Pole power contractor with inner-outer plate & internal wiring by suitable size of cu. wire incl. 1 no. Auto-Manual bypass toggle switch and provision for earthing attachment, incl. LED indication light for running condition with mechanical locking arrangement, as directed by EIC.[Make-ABB/L&T/Crabtree]
SITC of AC
SITC of indoor & outdoor unit of High-wall Split-type Air-Conditioner having following specification: Cooling capacity not less than 6400 Watt Minimum ISEER - 3.5, BEE level - 3-Star or more Capacity - 2.0 TR IS Compliance - IS-1391 Refrigerant - R410A/R32 Compressor - Rotary/Scroll Evaporator & Condenser Coil - Copper Operating outdoor temperature - 50ºC and above Power supply - 230V, 50Hz (±tolerance as per IS) [Make: O.General/Mitsubishi Electric/Mitsubishi Heavy Duty]
Copper Refrigeration pipe line for Liquid Line (1/4" OD with 0.6mm thick) with proper supports & brackets for 2TR Hi-wall Split AC, as directed by EIC. (Make: Ryoku/Uniflow)
Copper Refrigeration pipe line for Suction Line (5/8" OD with 0.6mm thick) with proper supports & brackets for 2TR Hi-wall Split AC as directed by EIC.(Make: Ryoku/Uniflow)
Supply & Fixing Pipe Insulation for Liquid Line (1/4" OD with 9 mm thick) with proper insulating for 2TR Hi-wall Split AC as directed by EIC.(Make: Accroflex/Suprime)
Supply & Fixing Pipe Insulation for Suction Line (5/8" OD with 9 mm thick) with Proper insulating for 1.8/1.5/1.0 Tr Hi Wall Split air Conditioner as directed by EIC. (make: Accroflex/Suprime)
Control Cabling from Condensing Unit to Control Panel 3 Core 2.5 sq. mm. Communication Cable 2TR Hi-wall Split AC, as directed by EIC. (Make : Polycab/KEI/Finolex)
S&F angle structure/Pre-fabricated angle with mending works for installation of Split type AC ODU as directed by EIC.
Supply & layingSoft Drawn PVC Drain Pipe 19mm dia with proper supports & brackets as per direction EIC. (Make: Suprime/Oriplast)
GLOW SIGN BOARD
SITC of LED illuminated sign board fabricated by following size ACP box supported with 1"×1" MS hollow squre pipe or Aluminium hollow squire pipe of 18 SWG all around. The 3mm ACP fabricated should be provided by laser cutting 6mm laser cutt acrylic latters out of which 5mm rising and border line of the front side, should be with cover of 1" Aluminium channel as per the direction of EIC. The sign board should be glow by 1.5W LED module cool white in color incl. 12V, 250W power supply. Back side of the board covered witrh 26 SWG GI sheet to protect the rain water. The sign board should be fixed on roof of the building with providing necy. CC muffing, 1 no. CI water proof loop box haaving size 200mm × 150mm × 100mm. 40×6 mm MS angle for supporting the board as required & mending good damages as per direction of EIC. The cost of transpotation charges are included. The sign board should be made as per the matter provided by (In Bengali & English) EIC. Dimension: 6' (ft)x 4' (ft) x 4" (inch) depth
SITC of 5 KVA UPS along with battery bank (inclusive of batteries, racks, connecting links, etc.) as per the specifications noted Below.
Technical Specifications for UPS (Make:- Luminous/Genus Power /Numeric/Switching AVO/GPtronics)(Choice As per EIC)
Type : Microprocessor controlled ,Capacity : 5 KVA / 4000 Watt or better Charging style : Boost & Float/ trickle
Input voltage range: 160 - 270 VAC, Single phase Input frequency range : 45 to 60 Hz ,Input Power factor : 0.98 or better Output Voltage to Load: 230 VAC , Voltage regulation: ±1% Output frequency :47-53 Hz,Current crest ratio :3:1 Total Harmonic distortionwithin : < 3% for linear loads & < 6% for non linear loads AC mode to Battery mode :Bumpless transfer ,Inverter to bypass transfer: 5 ms or better Waveform shape: Pure Sinewave Efficiency in AC mode: 90% or better,Efficiency in Battery mode :93% or better
Overload sustaining capability: Shall be able to sustain for at least 60 seconds in case of 125% load without abnormal behaviour Battery Charging current : Shall be capable of charging the fully drained battery in around 12 hours Battery charging Voltage :Suitable for battery bank of up to 192 V, 120 AH LCD Display : Input Voltage, output Voltage, Output Current, Battery charge etc.
Audio indications: The UPS shall give distict audio signals / alarms for battery mode, low battery & other faults Ambiant Conditions :up to 40°C @ 95% RH Cooling :Fans shall be available for internal heat dissipation of UPS
Protection :Protection against Short circuit, Overload, Low input voltage, Surge in input voltage as per UL 1449, Over heat in the UPS, etc shall be available
Warranty :1 Years for UPS and batteries
Technical Specifications for Battery Bank
Battery Type: VRLA, Sealed maintenance free Battery voltage :12 V DC,(Make : Exide , Amar raja or as per EIC) nominal Battery capacity :minimum 6240 VAH Battery Back Up Time: 30 Minute Minimum .
Voltage of Battery bank :Battery bank shall be configured to suit the chargiing capacity of UPS , Terminals : Copper
Number of batteries in bank :As many required
Power discharge rating @NTP : 3000 W for 10 min & 1000W for 1 hour, or better
Battery outer body material : Polypropylene Co-Polymer Battery Charging voltage : 13.5 VDC approx
Battery charging current :Batteries shall be able to accept up to 9 Amp charging current Life expectancy : 4 Years or more
Compliance of standards: UL 2003 (MH26669), JIS C 8702, IEC 60896 2004, ISO14001:2004 and ISO9001.2000
Tests : Shock test(drop test), Large current discharge test, Vent valve function test, Over discharge test, Vibration test, Oven test, Coldproof test, Heat cycle test, Short circuit test
Self discharge rate (max) :within 1% of capacity per week Warranty: 2 Years or more
Racks, Integration, testing & commissioning Suitable seismically stable, durable, rust proof, high strength rack for mounting the batteries shall be supplied along with each battery bank. Supplier shall be responsible for installation rack and battries, connection of all batteries with UPS, testing & commissioning at site.
Fire Detection System
Supply, Installation,Testing & Commisioning of Analog Addressable Intelligent Optical-Thermal Multi-criteria Detector (UL/ULC approved). (Numbers of addressable devices in a group will be as per latest recommended standards) (Approved make : Honeywell )
Supply, installation, testing & commissioning of addressable Manual call point (UL/ULC approved). (Numbers of addressable devices in a group will be as per latest recommended standards) (Approved make : Honeywell )
Supply & Laying of 2 Core 1.5 sq.mm FRLS shielded copper Cable (For Loop) (Make : Finolex / Havells / RR Kabel / Polycab) with 20mm NB PVC 'FR' rigid conduit pipe on the surface of the wall. (Make : Polycab/Presto/Precision-Medium).
Commsioning Charges for new dectector to existing Panel (Make : Honeywell) Both addressable And non Conventional panel
The Rates to be quoted by all the bidders should be Inclusive of all taxes and duties including GST and LWC.
SAUMIK GHOSH (BID ID -6310079)
Dutta Enterprise (BID ID -6313491)
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .