Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹1.3 CrAccepted-AOC 53 VAISHAILI ENCLAVE SECTOR 9 INDIRA NAGAR LUCKNOW | LUCKNOW | ₹1.3 Cr Quoted ₹134.61 | L1 | Accepted-AOC 1st Lowest |
| 2 | L2₹167.52+₹32.91 (24.4%)Rejected-Finance 12 041 BHASKAR COMPLEX ASHOK NAGAR GAUTAM BUDDHA MARG LUCKNOW 226018 | LUCKNOW | LUCKNOW | UTTAR PRADESH | 226018 | ₹167.52+₹32.91 (24.4%) | L2 | Rejected-Finance Second Lowest |
| 3 | Rejected-Technical 2 284 JANKIPURAM VISTAR LUCKNOW UTTAR PRADESH 226021 | LUCKNOW | UTTAR PRADESH | 226021 | - | - | Rejected-Technical Experience Certificate Not fulfill criteria as per NIT and Tender Document |
| 4 | Rejected-Technical | - | - | Rejected-Technical Validity of Solvency Certificate has been expired |
| 5 | Rejected-Technical | - | - | Rejected-Technical Experience Certificate Not fulfill criteria as per NIT and Tender Document |
Tender Value
₹1.5 Cr
EMD Value
₹2.9 L
Closing Date
28 May 2020, 4:00 pmClosed
Project Manager
Unit-13, CnDS, UP Jal Nigam, 2/128, Vikrant Khand Gomti Nagar, Lucknow
Supply, Installation, Testing and Commissioning of 750 KVA Silent DG Set, 1000 KVA Transformer, LT Panel, AMF Panel, Internal and External Electricity work as described in BOQ and Tender document
2020_UPCDS_471765_2
495/E-Tender/35 dated-11.05.2020
Open Tender
Electrical Works
Item Rate
90 days
SGPGIMS
As per NIT and Tender Documents
5 documents required · 5 mandatory
₹11,800
Director, CnDS, UP Jal Nigam, Unit-13
₹2.9 L
2 Sept 2020
19 May 2020
28 May 2020
19 May 2020
28 May 2020
19 May 2020
Amount
11kV Indoor Substation
11KV Switch Gear (Incoming cum Outgoing VCB Panel)
SITC of Single Panel (Incoming cum Outgoing) set 11KV, 500MVA indoor type metal clad floor mounted vermin proof horizontal drawout fully interlocked vertical/Horizontal isolation vacuum circuit breaker panel board fabricated out of minimum 2mm thick CRCA sheet as per specifications. The panel shall be complete with all accessories / fitting / wiring like insulated copper Busbar, cable termination boxes suitable for upto 3C x 300 Sqmm XLPE armoured, aluminium conductor cable for incoming and outgoing feeder, foundation bolts etc. complete as required and as specified below complete with foundation :- MAKE (SCHININDER/CROMFTON/ABB OR OTHER EQUIVALENT APPROVED MAKE)
Incoming cum outgoing : 1 set (Each Consisting of)
One (1) Nos. 11KV 630 Amps. 500MVA, 26.3kA for 3sec. Electrically/ manually operated draw out type vacuum circuit breaker complete with trip free spring charged closing mechanism, necessary auxiliary relays, control switches, emergency hand trip devices and mechanical ON / OFF indicator etc.
One (1) Multifunction Meter showing all Electrical Paramater ie Volt, Ampere, kw, kVA, P.F., kWH etc.
One (1) digital type ammeter with 11kV Cast resin CTs for metering (100/50 /5-5A, CL- 1, 15VA) with ASS and 2 Amp SP MCB.
One (1) voltmeter (0-15KV) with VSS.
One (1) Set of phase indication lamps with 2Amp SP MCB for protection (Red, Yellow and Blue).
One (1) set of Red/ Green indicating lamp for close and open position.
One (1) No. amber indicating lamp for auto trip.
One (1) No. clear indicating lamp for trip circuit healthy.
One (1) blue indicating lamp for spring charged.
One (1) strip heater to prevent absorption of moisture.
One (1) set of 3 O/C + 1E/F (with High Set) Neumerical Relay with 3 Nos. 11kV Resin Cast CTs 100/50/5-5A, CL 10P10, 15VA.
Master Trip Relay.
Trip circuit supervision relay
One (1) No. Potential Transformer 11KV/√3/110/√3 100VA burden
One (1) set of 3Element 24V DC Aux. Relay with H/R flag for tripping of Transfomer Fault ie. OTI, WTI & Buchholz Tripping.
One (1) set of 3Element 24V DC Aux. Relay with H/R flag for Alarm of Transfomer Fault ie. OTI, WTI & Buchholz Alarm.
One (1) set of 8 Stage 24V DC Annunciator with builtin test/Accept/ Reset Push Button along with 24V DC Hooter.
Master Trip Relay.
12 Window Annunciator
Auxiliary switch/relay, master trip, anti pumping relay Trip circuit supervision relay and other control relays etc. as per requirements.
Power Pack :
One (1) Set 230V A.C, / 24V DC, 42AH Battery Backup, Power Pack to operate atlease 3Nos. Operation without AC Supply.
1000kVA 11kV / 0.415kV TRANSFORMER:
Design, manufacture, supply, installation, testing and commissioning of 11kV/0.415kV, 1000KVA Transformer with percentage impedance 6.25% (Approx.) (without negative tolerance), 3 phase, 50 Hz delta/star connected, outdoor, oil filled, ONAN type transformer, complete with all fittings such as marhslling Box thermometers (OTI), WTI, Buchholz relay, Off Load Tapp Changer with + 5 % to –12.5%, tapping at the step of 1.25% bi-directional roller, diagrams & rating plate & Winding temperature indicator, oil temperature indicator, lifting lugs, H. T. cable box/ LT Cable Box suitable for Termination of Cable. transformner shall confirm to Latest IS : 1180 Energy Efficiensy Level-II complete with foundation. MAKE (CROMFTON/SCHININDER/ABB OR OTHER EQUIVALENT APPROVED MAKE)
750A Silent DG Set
SITC of 750kVA, 415V Silent DG Set with comprising of Kirloskar/Caterpillar/Perkins/ Cummins or Other Equivalent approved make Engine developing 987 BHP at 1500 RPM under NTP conditions water cooled 4 stroke 12 Cylender, Electric Start, Turbo Charged and after cooled model, Conforming to BS:5514/ ISO 3046 with capacity of 10 percent overloading for 1 hours in 12 twelve hour duration desined on minimum ambient tempreture of 50 Degree Celcius, coupled to 750kVA 415V, Alternator mounted on common base complete with following accessories and filling with full diesel, batteries and leads, Residential silencer, First fill of Lube oil, AVM Pads, Acoustic enclosure and shade for DG. Complete with dynamic foundation as per direction E/I.
Fuel Tank ( filling with diesel complete )
Battery and Battery Leads
Acoustic Enclosure
Residential Silenser
First fill of Lube Oil
AVM Pads
Standard Control Panel
LT Distribution Boards
Important Notes: Common for all Panel Board:
The BOQ shall be read inconjunction with general notes, specification and Single Line Diagram (attached for Ref.). Incase of any discrepancy between specification, BOQ and SLD, the same shall be brought to the notice of Client before quoting the rates, otherwise stringent condition shall be deemed to have been considered.
Fault current wherever mentioned shall be Ics value.
All MCCB shall be provided with door interlocked rotary handle with ON/TRIP/OFF position indicator, thermal magnetic O/C and S/C releases.
All TP feeders shall have solid isolable neutral link.
All MCB shall be of 'C' Curve
All outgoing terminals (power and control) shall be brought upto cable alley.
Removable lifting hook shall be provided in all transportation section.
All CT, PT shall be Capsulated or cast resin.
All meters shall be digital type.
Panel shall be powder coated of approved shade with minimum 60 micron thickness.
MCCB's/ MCBs in one particular panel shall be of one similar make.
Size of Voltmeter / Ammeter for incomer also, 96mm x 96mm flush mounted with shrouded terminal shall be used in the panel.
Bus bar chamber shall be kept at top of the all panels.
All bus bar shall be insulated with coloured PVC Sleeve i.e.RYB,BK as per colour code.
Internal wiring of panel shall be with size 1.5sqmm Flexible Copper Conductor for CT circuit and control wiring with 1.5 sqmm.
All indicating light shall be LED type .
All the makes shall be as per Client approved make list only.
Main Building Main LT Panel cum AMF Panel
LT PANEL & AMF Panel
Design, Manufacturing, Supply Installation, Testing & Commissioning of LT switchgear panels suitable for 433 V, 3 phase, 4 wire, 50 Hz power distribution system. The panel shall be Indoor, free standing, floor mounting, sheet metal clad, cubicle, dead front, dust and vermin proof type compartmentalised design fabricated out of 14 SWG CRCA sheet steel, complete with colour coded, heat shrinkable PVC insulated, aluminium bus bars and separate earth bus bar of adequate cross section through out the length of the panel. The incoming and outgoing feeders shall be accommodated in a fully segregated, modular multitier arrangement with adequate size and distinct cable alley, bus bar alley/chamber. The panel shall be complete with name plate, earthing, numbering, danger plate etc. as required and as per specifications and drawings. The panel shall withstand the fault level of 25kA as per Single Line Diagram complete with foundation etc. MAKE -SCHININDER/ABB/L&T OR OTHER EQUIVALENT APPROVED MAKE)
a) 1 Nos. Incoming 1600A 50kA FP Electrically Operated Draw out type ACB with Microprocessor Based O/C, S/C & E/F Protection, CT, Metering, AMF Logic & Battery Charger compelete with all fuses wiring etc and as per SLD. From 1000kVA Transformer
a) 1 No.Outgoing 1000A 50kA FP Manually Operated Draw out type ACB with Microprocessor Based O/C, S/C & E/F Protection, CT, Metering, compelete with all fuses wiring etc and as per SLD
a) 2 No.Outgoing 800A 50kA FP Manually Operated Draw out type ACB with Microprocessor Based O/C, S/C & E/F Protection, CT, Metering, compelete with all fuses wiring etc and as per SLD AT NEW OPD BUILDING.
AMF PANEL
a) 2 No.INCOMING 800A 50kA FP Manually Operated Draw out type ACB with Microprocessor Based O/C, S/C & E/F Protection, CT, Metering, AMF logic &battry charger compelete with all fuses wiring etc and as per SLD AND AMF LOGIC SYSTEM NEAR DAIGNOSTIC BUILDING.
a) 1 No.Outgoing 800A 50kATPN Aluminium Bus bar
b) 1 No.AMF Logic CIRCUITORY complete in all respect to achieve AMF function along with 01 no. battery charger
APFC Panel
Design, Manufacturing, Supply Installation, Testing & Commissioning of LT APFC Panel as under suitable with Incomer Bus Bar for 433 V, 3 phase, 4 wire, 50 Hz power distribution system. The panel shall be Indoor, free standing, floor mounting, sheet metal clad, cubicle, dead front, dust and vermin proof type compartmentalised design fabricated out of 14 SWG CRCA sheet steel, complete coded, heat shrinkable PVC insulated, aluminium bus bars and separate earth bus bar of adequate cross section through out the length of the panel. The incoming and outgoing feeders shall be accommodated in a fully segregated, modular multitier arrangement with adequate size and distinct cable alley, bus bar alley/chamber. The panel shall be complete with name plate, earthing, numbering, danger plate etc. as required and as per specifications and drawings. The panel shall withstand the fault level of 25kA. The Panel shall be completed in all respect as per below mentioned BOQ and as per SLD complete with foundation. MAKE (SCHININDER/ABB/L&T OR OTHER EQUIVALENT APPROVED MAKE))
a) 500kVAr 12 stage with 800A TP, 25kA MCCB Incomer with Metering & Individal MCB/MCCB for Feeder Protection alongwith Microprocessor Based APFC Relay as per SLD
11kV Cable laying :
Supplying, laying, testing and commissioning of 11 KV grade aluminium conductor, cross linked polyethylene (XLPE) insulated individual core screened extruded inner sheath, flat steel/strip armoured PVC sheathed cable and suitable for UE system complete as required of following Sizes:MAKE -HAVELLS/ POLYCAB OR OTHER EQUIVALENT APPROVED MAKE)
3C x 185 Sqmm, 11KV XLPE
End Termination (HT) :
SITC of Cable jointing Kit of 11 KV grade XLPE insulated armoured cable with suitable for cable termination using RAYCHEM/Birla 3M/MECP KITS including all accessories i.e. Sockets, lugs, gland etc as required but without cable box.
3C x 185 Sqmm, 11KV XLPE (Indoor Cable Terminations)
LT / Control Cables in Under Ground / Trench :
Supply, installation, testing and commissioning of following sizes of PVC sheathed XLPE insulated aluminium conductor/ copper conductor power/multicore control armoured cable of 1.1 KV grade in ground including digging the trench, laying the cable with sand and brick covering, back filling reaming etc as required. (MAKE -HAVELLS/ POLYCAB/KEI OR OTHER EQUIVALENT APPROVED MAKE)
3.5 C 400 Sqmm XLPE Al. Cable
2 C 2.5 Sqmm PVC cable
6 C 2.5 Sqmm PVC cable
LT / Control Cable Termination :
Supply and making end termination with brass double compression glands for the following XLPE insulated PVC sheathed 1100 V grade cable including cost of crimping lugs/ferrules, compression glands, solder, cable sockets, insulation tap etc complete as required.
3 ½ core 400 Sqmm XLPE Al cable
2 C x 2.5 Sqmm
6 C x 2.5 Sqmm
Earthing System:
Supply, installation, testing and commissioning of copper plate earthing stations making earth pits, earthing with copper earth plate 600 mm x 600 mm x 3.15 mm thick including funnel, charcoal/coke, salt, all earth work. Providing masonry enclosure with 10 mm thick C.I. cover plate having locking arrangement and watering pipe, disconnecting/ testing links etc as per IS –3043 complete as required. 2 Trs (4 Nos.).
Supply, installation, testing and commissioning of GI Pipe earthing stations making earth pits, earthing with GI pipe 3500 mm x 80 mm Dia including funnel, charcoal/coke, salt, all earth work. Providing masonry enclosure with 10 mm thick C.I. cover plate having locking arrangement and watering pipe, disconnecting/ testing links etc as per IS–3043 complete as required.
Earthing Strip/Wires :
Supply, installation, testing and commissioning of following sizes of GI/ Copper strip/wire clamped to walls, cable trays, bus ducts, cables in recess or surface etc for equipment/ System earthing complete as required including inter connection between length at joints, all fixing accessories saddles, clamps, lugs etc and other fixing hardware material as required for proper installation.
50 x 6 mm GI strip
50 x 6 mm Copper strip
SUB STATION SAFETY EQUIPMENT :
Supplying and fixing 2000 mm x 1000 mm wide checkered rubber matting conforming to IS 5424-1969 complete as required & suitable for 11kV HT <.
Excavating trenches of required width for pipes, cables, etc including excavation for sockets, and dressing of sides, ramming of bottoms, depth upto 1.5 m, including getting out the excavated soil, and then returning the soil as required, in layers not exceeding 20 cm in depth, including consolidating each deposited layer by ramming, watering, etc. and disposing of surplus excavated soil as directed, within a lead of 50 m :
Pipes, cables etc. exceeding 80 mm dia. but not exceeding 300 mm dia
Dismantling manually/ by mechanical means including stacking of serviceable material and disposal of unserviceable material within 50 metres lead as per direction of Engineer-in-charge :
bituminous road
Demolishing cement concrete manually/ by mechanical means including disposal of material within 50 metres lead as per direction of Engineer - in - charge.
Nominal concrete 1:4:8 or leaner mix (i/c equivalent design mix)
const of new road over the existing one.
Supply, fixing & placing of U shaped RCC 250x250 cable channel to carry A.C line & cables with all respect as per direction of engineers-in-charge
INTERNAL ELECTRIFICATION
Wiring Point for light with 1.0 Sq.mm. PVC insulated multistrand single core copper conductor cable in PVC conduit with 1.5 Sq.mm. FR PVC insulated multistrand copper conductor cable as earthing wire drawn inside the conduit partly concealed in the wall and partly laid in slab along with reinforcement before concerting, complete with moduler type switch & ceiling rose/angle/batten holder on 3 mm thick phenolic laminated backelite sheet etc. complete in all respects including matching colour wash.
Wiring Point for fan with 1 PVC insulated single core copper conductor cable in PVC conduit with 1.5 sq.mm. FR PVC insulated multistrand copper conductor cable as eatrhing wire drawn inside the conduit partly concealed in wall and partly laid in slab alongwith the reinforcement before concerting, complete with 8 SWG GI earth continuity wire, pino type switch and ceiling rose on 3mm. thick phenolic laminated backlite sheet etc, complete in all respects including matching colour wash.
Wiring Point for plug with 1.0 Sq.mm. PVC insulated multistrand single core copper conductor cable in PVC conduit with 1.5 Sq.mm. FR PVC insulated multistrand copper conductor cable as earthing wire drawn inside the conduit partly concealed in the wall and partly laid in slab along with reinforcement before concerting, complete with moduler type switch & ceiling rose/angle/batten holder on 3 mm thick phenolic laminated backelite sheet etc. complete in all respects including matching colour wash.
Wiring Point for exhaust fan with 1.5 Sq.mm. PVC insulated multistrand single core copper conductor cable in PVC conduit with 1.5 Sq.mm. FR PVC insulated multistrand copper conductor cable as earthing wire drawn inside the conduit partly concealed in the wall and partly laid in slab along with reinforcement before concerting, complete with moduler type switch & ceiling rose/angle/batten holder on 3 mm thick phenolic laminated backelite sheet etc. complete in all respects including matching colour wash.
Supply and fixing and concealing of 25 mm. dia. 2mm. Thick PVC conduit pipe with ISI mark enbossed and with PVC accessories confirming to IS No. 3419 for drawing wires duly sealed at joints, plastering with cement sand mortar finished to the level with ma
Supply and wiring of submain with two number 4 Sq.mm. FR PVC insulated 1100 V grade multistrand single core copor conductor cable in 20 mm dia heavy duty (2mm thick) PVC Condute partly concealed in wall and partly laid in slab along with reinforcement be
Supply and wiring of submains with 2 nos. 2.5 sq mm & with 1 no earth wire of 1.5 sq mm FRLSH PVC insulated 1100 V grade single core multistrand copper conductor cable in existing PVC conduit complete, including supply of all material, labour and T & P etc. required for proper completion of the work as directed by Engineer in charge.
Supply & laying of aluminium conductor PVC insulated armoured served sheathed cables 1100 Volts grade at a depth of 750mm. below ground level over a cushion of 75mm. thick sand all around and protected with burnt bricks on sides and on top. On surface the cable run shall be fixed on M.S clamps etc. of suitable size or as directed by the Engineer - Incharge, complete in all respect. The armouring of the cable shall be properly connected with the earth conductor by clamps etc.
10 Sq.mm. 2 Core.
35 Sq.mm.3-1/ 2 Core.
Supply and laying of 25mm x 3mm G.I. strip earth electrode directly in the ground as required complete in all respects.
S&F of 6 Amp. to 32 Amp. SP MCB (10 KA) (Legrand Lexic)
S&F of 100 Amp 4 pole MCCB (25 KA) Thermal Magnetic release
S&F surface/flush mounting 8 ways V TPN distribution board (Legrand Lexic) with additional metal door without MCB complete in all respect, as directed at site by Engineer in charge.
Supply and fixing of LED Tube Light with batten suitable for up to 1 X 22 watt LED tube light complete including tube etc on surface complete in all respect.
CAT- AAA
Supply & burying of safe earthing Electrode T-39 Zn. zinc coated, Length 3000mm, Outer pipe 76.3mm x 3.2mm inner pipe 42.4mm x 2.6mm, terminal dia 12mm, coating 80-100micron filled with crysteline conductive mixture (CCM) havinbg anti corrosive & conductive properly with 50Kg activated soil (BFC) capable of reducing the soil restivity with good mixture of retaining capacity and one earthing lead of 20 x 3 G.I. Strip upto Switch board with 30cm square C.I. frame with hinged cover & masonary housing.
Rates are Including all applicable taxes but excluding GST as applicable
M/s Acme Pumps and Power Projects Limited
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .