| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹24.9 LAdmitted-Finance BYE PASS DALHOUSIE ROAD PATHANKOT 145001 PB | PATHANKOT | PATHANKOT | PUNJAB | 145001 | ₹24.9 L | L1 | Admitted-Finance |
| 2 | L2₹29.2 LAdmitted-Finance 1ST FLOOR GURJEET MARKET DHANGU ROAD | ₹29.2 L | L2 | Admitted-Finance |
| Sl No | Description | Qty | Unit | Vijay Kumar Contractor and Engineers L2 | M/S GULATI ENGINEERING WORKS L1 |
|---|---|---|---|---|---|
| 1.00 | Excavating in trenches in hard/dense soil, n. exc. 1.5 m wide and n. exc. 1.5 m in depth, for foundation, laying cables etc. or for shafts, wells, cess pits, manholes, pier holes, etc n. exc. 10 sqm on plan and n. exc 1.5 m in depth and getting out complete all as specified and directed. | 860 | Cum | 50 ₹43,000 | 66 ₹56,760 |
| 2.00 | Excavating in trenches in hard/dense soil, n. exc. 1.5 m wide and exc. 1.5 m but n. exc.3 m in depth, for foundation, etc. or for shafts, wells, cess pits, manholes, pier holes, etc n. exc. 10 sqm on plan and exc 1.5 m but n. exc. 3 m in depth and getting out complete all as specified and directed. | 1 | Cum | 100 ₹100 | 2,000 ₹2,000 |
| 3.00 | Returning, filling in (soil), including spreading, leveling, watering and well ramming in layers not exc. 25 cm complete all as specified and directed. | 359 | Cum | 20 ₹7,180 | 44 ₹15,796 |
| 4.00 | Supply and laying of DWC (Double Wall Corrugated) pipe of 75 mm bore as per IS-16205 laid for protection of cables in trenches complete all as specified and diriected. | 2,052 | RM | 90 ₹1.8 L | 45 ₹92,340 |
| 5.00 | Supply and laying of DWC (Double Wall Corrugated) pipe of 63 mm bore as per IS-16205 laid for protection of cables in trenches complete all as specified and diriected. | 1,368 | RM | 60 ₹82,080 | 45 ₹61,560 |
| 6.00 | M&L for PCC 1:4:8 type D-2 using 40 mm graded stone aggregate in foundations, filling and mass concrete complete all as specified and directed.
Note:- Volume of pole/strut embedded shall be deducted for the purpose of payment. | 7 | CUM | 3,000 ₹21,000 | 1,800 ₹12,600 |
| 7.00 | M&L for PCC 1:3:6 type C1 using 20 mm graded stone aggregate as in pedestal/coping including necessary weathering and form work etc complete all as specified and directed.
Note:- Volume of pole/strut embedded shall be deducted for the purpose of payment. | 1 | CUM | 3,500 ₹3,500 | 2,000 ₹2,000 |
| 8.00 | Taking out old unservicable under ground LT XLPE/ PVC cable of any size from trenches/ wall/ roof/ pipe/ DB including taking out of brick layer of cable protection complete all as specified and as directed. Note : Excavation and earth wrok shall be measured and paid for separately. | 3,945 | RM | 5 ₹19,725 | 15 ₹59,175 |
| 9.00 | Supply and laying in trenches or fixed to wall/pole or passing through ducts or pipe, cable LT 1100 volts grade heavy duty, XLPE insulated , armoured heavy duty electric cable, with aluminium conductor of size 10 Sqmm x 4 core or fixed to wall/pole or passing through ducts or pipe of any size, any core, complete all as specified and directed. | 900 | RM | 190 ₹1.7 L | 111 ₹99,900 |
| 10.00 | Supply and laying in trenches or fixed to wall/pole or passing through ducts or pipe, cable LT 1100 volts grade heavy duty, XLPE insulated , armoured heavy duty electric cable, with aluminium conductor of size 16 Sqmm x 4 core or fixed to wall/pole or passing through ducts or pipe of any size, any core, complete all as specified and directed. | 820 | RM | 225 ₹1.8 L | 118 ₹96,760 |
Updated dates
Tender Value
₹32 L
EMD Value
₹64,000
Closing Date
30 Mar 2026, 6:00 pmClosed
GE (S) Mamun
GE (South) Mamun, MES Complex, Mamun Cantt, Pathankot
As specified in BOQ and Tender Documents
2026_MES_754857_1
GE(S)/M-82/2025-26
Open Tender
Civil Works
270 days
GE (South) Mamun, MES Complex, Mamun Cantt, Pathan
As per NIT
9 documents required · 9 mandatory
₹500
Yes
GE (S) Mamun
₹64,000
Yes
14 Apr 2026
2 Mar 2026
7 Apr 2026
2 Mar 2026
30 Mar 2026
16 Mar 2026
Excavating in trenches in hard/dense soil, n. exc. 1.5 m wide and n. exc. 1.5 m in depth, for foundation, laying cables etc. or for shafts, wells, cess pits, manholes, pier holes, etc n. exc. 10 sqm on plan and n. exc 1.5 m in depth and getting out complete all as specified and directed.
Excavating in trenches in hard/dense soil, n. exc. 1.5 m wide and exc. 1.5 m but n. exc.3 m in depth, for foundation, etc. or for shafts, wells, cess pits, manholes, pier holes, etc n. exc. 10 sqm on plan and exc 1.5 m but n. exc. 3 m in depth and getting out complete all as specified and directed.
Returning, filling in (soil), including spreading, leveling, watering and well ramming in layers not exc. 25 cm complete all as specified and directed.
Supply and laying of DWC (Double Wall Corrugated) pipe of 75 mm bore as per IS-16205 laid for protection of cables in trenches complete all as specified and diriected.
Supply and laying of DWC (Double Wall Corrugated) pipe of 63 mm bore as per IS-16205 laid for protection of cables in trenches complete all as specified and diriected.
M&L for PCC 1:4:8 type D-2 using 40 mm graded stone aggregate in foundations, filling and mass concrete complete all as specified and directed. Note:- Volume of pole/strut embedded shall be deducted for the purpose of payment.
M&L for PCC 1:3:6 type C1 using 20 mm graded stone aggregate as in pedestal/coping including necessary weathering and form work etc complete all as specified and directed. Note:- Volume of pole/strut embedded shall be deducted for the purpose of payment.
Taking out old unservicable under ground LT XLPE/ PVC cable of any size from trenches/ wall/ roof/ pipe/ DB including taking out of brick layer of cable protection complete all as specified and as directed. Note : Excavation and earth wrok shall be measured and paid for separately.
Supply and laying in trenches or fixed to wall/pole or passing through ducts or pipe, cable LT 1100 volts grade heavy duty, XLPE insulated , armoured heavy duty electric cable, with aluminium conductor of size 10 Sqmm x 4 core or fixed to wall/pole or passing through ducts or pipe of any size, any core, complete all as specified and directed.
Supply and laying in trenches or fixed to wall/pole or passing through ducts or pipe, cable LT 1100 volts grade heavy duty, XLPE insulated , armoured heavy duty electric cable, with aluminium conductor of size 16 Sqmm x 4 core or fixed to wall/pole or passing through ducts or pipe of any size, any core, complete all as specified and directed.
All as per description of srl item No. 10.00 here-in-before but size of cable 25 Sqmm 4 core
All as per description of srl item No. 10.00 here-in-before but size of cable 35 Sqmm 3.5 core.
All as per description of srl item No. 10.00 here-in-before but size of cable 50 Sqmm 3.5 core
All as per description of srl item No. 10.00 here-in-before but size of cable 70 Sqmm 3.5 core
All as per description of srl item No. 10.00 here-in-before but size of cable 95 Sqmm 3.5 core
All as per description of srl item No. 10.00 here-in-before but size of cable 120 Sqmm 3.5 core
Relaying only in trenches or fixed to wall/pole or passing through ducts or pipe, cable LT 1100 volts grade heavy duty, XLPE insulated, armoured heavy duty electric cable, with aluminium conductor of size 10/16 Sqmm x 2/4 core complete all as specified and directed.
All as per description of srl item No. 17.00 here-in-before but size of cable 25 Sqmm 3.5 core
All as per description of srl item No. 17.00 here-in-before but size of cable 35 Sqmm 3.5 core
All as per description of srl item No. 17.00 here-in-before but size of cable 50 Sqmm 3.5 core
All as per description of srl item No. 17.00 here-in-before but size of cable 70 Sqmm 3.5 core
All as per description of srl item No. 17.00 here-in-before but size of cable 95 Sqmm 3.5 core
All as per description of srl item No. 17.00 here-in-before but size of cable 120 Sqmm 3.5 core
All as per description of srl item No. 17.00 here-in-before but size of cable 185 Sqmm 3.5 core
All as per description of srl item No. 17.00 here-in-before but size of cable 240 Sqmm 3.5 core. Note for item No. 10.00 to 24.00:- Excavation & earth work, sand cushioning, brick cover and protection pipe etc. shall be measured and paid for separately.
Supplying, jointing and connecting in repairs cable end termination joint kit, out door, heat shrinkable type for underground cable including jointing kits and labour complete for making joints suitable for aluminium conductor cable of size 25 sqmm to 50 Sqmm 3.5 core, 1100 volts grade complete all as specified and directed.
Supplying, jointing and connecting in repairs cable end termination joint kit, out door, heat shrinkable type for underground cable including jointing kits and labour complete for making joints suitable for aluminium conductor cable of size 70 sqmm to 120 Sqmm 3.5 core, 1100 volts grade complete all as specified and directed.
Supplying, jointing and connecting in repairs cable end termination joint kit, out door, heat shrinkable type for underground cable including jointing kits and labour complete for making joints suitable for aluminium conductor cable of size 150 sqmm to 185 Sqmm 3.5 core, 1100 volts grade complete all as specified and directed.
Supplying, jointing and connecting in repairs cable end termination joint kit, out door, heat shrinkable type for underground cable including jointing kits and labour complete for making joints suitable for aluminium conductor cable of size 240 sqmm to 300 Sqmm 3.5 core, 1100 volts grade complete all as specified and directed.
Supplying, jointing and connecting in repairs straight through joint, heat shrinkable type for underground cable including jointing kits and labour complete for making joints suitable for aluminium conductor cable of size 25 sqmm to 50 Sqmm 3.5 core, 1100 volts grade complete all as specified and directed.
Supplying, jointing and connecting in repairs straight through joint, heat shrinkable type for underground cable including jointing kits and labour complete for making joints suitable for aluminium conductor cable of size 70 sqmm to 120 Sqmm 3.5 core, 1100 volts grade complete all as specified and directed.
Supplying, jointing and connecting in repairs straight through joint, heat shrinkable type for underground cable including jointing kits and labour complete for making joints suitable for aluminium conductor cable of size 150 sqmm to 185 Sqmm 3.5 core, 1100 volts grade complete all as specified and directed.
Supplying, jointing and connecting in repairs straight through joint, heat shrinkable type for underground cable including jointing kits and labour complete for making joints suitable for aluminium conductor cable of size 240 sqmm to 300 Sqmm 3.5 core, 1100 volts grade complete all as specified and directed.
M&L for replacement of 40 mm bore galvanised steel tubing, light grade, with all fittings, for protection of cable, laid in trenches/road crossing/floor or fixed to pole/wall with and including 02 Nos. MS clamp made of FI 25x4 mm, nuts, bolts and washers complete all as specified and directed.
M&L for replacement 50 mm bore galvanised steel tubing, light grade, with all fittings, for protection of cable, laid in trenches/road crossing/floor or fixed to pole/wall with and including 02 Nos. MS clamp made of FI 25x4 mm, nuts, bolts and washers complete all as specified and directed.
M&L for replacement 80 mm bore galvanised steel tubing, light grade, with all fittings, for protection of cable, laid in trenches/road crossing/floor or fixed to pole/wall with and including 02 Nos. MS clamp made of FI 25x4 mm, nuts, bolts and washers complete all as specified and directed.
S&F in repairs MCCB 4 Pole, 415 V, fixed type, 160 Amps rating, microprecesser based energy with rupturing capacity 36 KA, as approved complete all as specified and directed.
S&F in repairs MCCB 4 Pole, 415 V, fixed type, 200 Amps rating, microprecesser based energy with rupturing capacity 36 KA, as approved complete all as specified and directed.
S&F in repairs MCCB 4 Pole, 415 V, fixed type, 250 Amps rating, microprecesser based energy with rupturing capacity 36 KA, as approved complete all as specified and directed.
S&F in repairs MCCB 4 Pole, 415 V, fixed type, 315 Amps rating, microprecesser based energy with rupturing capacity 36 KA, as approved complete all as specified and directed.
S&F in repairs MCCB 4 Pole, 415 V,fixed type, 400 Amps rating, microprecesser based energy with rupturing capacity 36 KA, as approved complete all as specified and directed.
S&F in repairs MCCB 4 Pole, 415 V, fixed type, 630 Amps rating, microprecesser based energy with rupturing capacity 36 KA, as approved complete all as specified and directed.
Supply, installation, commissioning and testing of totally enclosed outdoor type LT Panel in replacement dust and vermin proof floor mounted type (IP-65 degree of protection) made out of 3 mm thick CRCA sheet of recommended size, All sheet metal parts separately chemically treated with 7 tank treatment process, The panel having both side opening door with locking arrangement, all doors fixed with aluminium hinges with suitable size nuts, bolts and shall have flexible fixing of each switchgear and controlgear compartment with cable alley tray of size not less than 30 cm, duly painted with two coats of synthetic enamel paint powder coated, having bus bar 1000 amps rating made of aluminium strip duly drilled holes for connections and mounted on epoxy based post insulators for 3 phase 4 wire 415 volts 50 HZ AC supply, thimbling, cable entry boxes, cable gland and LT panel shall be mounted on iron angle frame made out of 50mm x 50mm x 6 mm frame with 4 No. legs of size not less than 45 cms each fixed with nut bolts of suitable size at bottom portion of the panel, grouted in PCC foundation 1:2:4 type B-1 with 20 mm graded stone aggregates totally tested on completion, including taking down existing LT panel complete and suitable for and including the following :-
(i) MCCB 4 pole, 415 volts, Adjustastable Thermal Magnetic (TM) type, 630 amp rating, microprecesser based energy with rupturing capacity 50 KA - 01 No. as income. (ii) MCCB 4 pole, 415 volts, Adjustastable Thermal Magnetic (TM) type, 315 amp rating, with rupturing capacity 36 KA - 02 No. for outgoing (iii) MCCB 4 pole, 415 volts, Adjustastable Thermal Magnetic (TM) type, 250 amp rating, with rupturing capacity 36 KA - 02 No. for outgoing (iv) MCCB 4 pole, 415 volts, Adjustastable Thermal Magnetic (TM) type, 200 amp rating, with rupturing capacity 36 KA - 01 No. for outgoing (v) MCCB 4 pole, 415 volts, Adjustastable Thermal Magnetic (TM) type, 100 amp rating, with rupturing capacity 36 KA - 01 No. for outgoing (vi) Indicator set RYB -01 Set of 3 (vii) Multifunction digital panel meter suitable to display amps, volts, frequency etc - 01 No including CTs of appropriate ratio. (viii) All accessories prewired with suitable size copper conductor cable or strip including foundation as per manufacturer instruction all as required and directed.
Supply, installation, commissioning and testing of totally enclosed outdoor type LT Panel in replacement dust and vermin proof floor mounted type (IP-65 degree of protection) made out of 3 mm thick CRCA sheet of recommended size, All sheet metal parts separately chemically treated with 7 tank treatment process, The panel having both side opening door with locking arrangement, all doors fixed with aluminium hinges with suitable size nuts, bolts and shall have flexible fixing of each switchgear and controlgear compartment with cable alley tray of size not less than 30 cm, duly painted with two coats of synthetic enamel paint powder coated, having bus bar 600 amps rating made of aluminium strip duly drilled holes for connections and mounted on epoxy based post insulators for 3 phase 4 wire 415 volts 50 HZ AC supply, thimbling, cable entry boxes, cable gland and LT panel shall be mounted on iron angle frame made out of 50mm x 50mm x 6 mm frame with 4 No. legs of size not less than 45 cms each fixed with nut bolts of suitable size at bottom portion of the panel, grouted in PCC foundation 1:2:4 type B-1 with 20 mm graded stone aggregates totally tested on completion, including taking down existing LT panel complete and suitable for and including the following :-
(i) MCCB 4 pole, 415 volts, , 400 amp rating, microprecesser based energy with rupturing capacity 50 KA - 01 No. as income. (ii) MCCB 4 pole, 415 volts, Adjustastable Thermal Magnetic (TM) type, 250 amp rating, with rupturing capacity 36 KA - 02 No. for outgoing (iii) MCCB 4 pole, 415 volts, Adjustastable Thermal Magnetic (TM) type, 200 amp rating, with rupturing capacity 36 KA - 01 No. for outgoing (iv) MCCB 4 pole, 415 volts, Adjustastable Thermal Magnetic (TM) type, 100 amp rating, with rupturing capacity 36 KA - 02 No. for outgoing (v) Indicator set RYB -01 Set of 3 (vi) Multifunction digital panel meter suitable to display amps, volts, frequency etc - 01 No including CTs of appropriate ratio. (vii) All accessories prewired with suitable size copper conductor cable or strip including foundation as per manufacturer instruction all as required and directed.
Supply, installation, commissioning and testing of totally enclosed outdoor type LT Panel in replacement dust and vermin proof floor mounted type (IP-65 degree of protection) made out of 3 mm thick CRCA sheet of recommended size, All sheet metal parts separately chemically treated with 7 tank treatment process, The panel having both side opening door with locking arrangement, all doors fixed with aluminium hinges with suitable size nuts, bolts and shall have flexible fixing of each switchgear and controlgear compartment with cable alley tray of size not less than 30 cm, duly painted with two coats of synthetic enamel paint powder coated, having bus bar 600 amps rating made of aluminium strip duly drilled holes for connections and mounted on epoxy based post insulators for 3 phase 4 wire 415 volts 50 HZ AC supply, thimbling, cable entry boxes, cable gland and LT panel shall be mounted on iron angle frame made out of 50mm x 50mm x 6 mm frame with 4 No. legs of size not less than 45 cms each fixed with nut bolts of suitable size at bottom portion of the panel, grouted in PCC foundation 1:2:4 type B-1 with 20 mm graded stone aggregates totally tested on completion including taking down existing LT panel complete and suitable for and including the following :-
(i) MCCB 4 pole, 415 volts, 400 amp rating, microprecesser based energy with rupturing capacity 50 KA - 01 No. as income. (ii) MCCB 4 pole, 415 volts, Adjustastable Thermal Magnetic (TM) type, 315 amp rating, with rupturing capacity 36 KA - 01 No. for outgoing (iii) MCCB 4 pole, 415 volts, Adjustastable Thermal Magnetic (TM) type, 200 amp rating, with rupturing capacity 36 KA - 02 No. for outgoing (iv) MCCB 4 pole, 415 volts, Adjustastable Thermal Magnetic (TM) type, 100 amp rating, with rupturing capacity 36 KA - 01 No. for outgoing (v) Indicator set RYB -01 Set of 3 (vi) Multifunction digital panel meter suitable to display amps, volts, frequency etc - 01 No including CTs of appropriate ratio. (vii) All accessories prewired with suitable size copper conductor cable or strip including foundation as per manufacturer instruction all as required and directed.
Supply, installation, commissioning and testing of totally enclosed outdoor type LT Panel in replacement dust and vermin proof floor mounted type (IP-65 degree of protection) made out of 3 mm thick CRCA sheet of recommended size, All sheet metal parts separately chemically treated with 7 tank treatment process, The panel having both side opening door with locking arrangement, all doors fixed with aluminium hinges with suitable size nuts, bolts and shall have flexible fixing of each switchgear and controlgear compartment with cable alley tray of size not less than 30 cm, duly painted with two coats of synthetic enamel paint powder coated, having bus bar 600 amps rating made of aluminium strip duly drilled holes for connections and mounted on epoxy based post insulators for 3 phase 4 wire 415 volts 50 HZ AC supply, thimbling, cable entry boxes, cable gland and LT panel shall be mounted on iron angle frame made out of 50mm x 50mm x 6 mm frame with 4 No. legs of size not less than 45 cms each fixed with nut bolts of suitable size at bottom portion of the panel, grouted in PCC foundation 1:2:4 type B-1 with 20 mm graded stone aggregates totally tested on completion, including taking down existing LT panel complete and suitable for and including the following :-
(i) MCCB 4 pole, 415 volts, 400 amp rating, microprecesser based energy with rupturing capacity 50 KA - 01 No. as income. (ii) MCCB 4 pole, 415 volts, Adjustastable Thermal Magnetic (TM) type, 250 amp rating, with rupturing capacity 36 KA - 02 No. for outgoing (iii) MCCB 4 pole, 415 volts, Adjustastable Thermal Magnetic (TM) type, 100 amp rating, with rupturing capacity 36 KA - 01 No. for outgoing (iv) Indicator set RYB -01 Set of 3 (v) Multifunction digital panel meter suitable to display amps, volts, frequency etc - 01 No including CTs of appropriate ratio. (vi) All accessories prewired with suitable size copper conductor cable or strip including foundation as per manufacturer instruction all as required and directed.
Supply, installation, commissioning and testing of totally enclosed outdoor type LT Panel in replacement dust and vermin proof floor mounted type (IP-65 degree of protection) made out of 3 mm thick CRCA sheet of recommended size, All sheet metal parts separately chemically treated with 7 tank treatment process, The panel having both side opening door with locking arrangement, all doors fixed with aluminium hinges with suitable size nuts, bolts and shall have flexible fixing of each switchgear and controlgear compartment with cable alley tray of size not less than 30 cm, duly painted with two coats of synthetic enamel paint powder coated, having bus bar 600 amps rating made of aluminium strip duly drilled holes for connections and mounted on epoxy based post insulators for 3 phase 4 wire 415 volts 50 HZ AC supply, thimbling, cable entry boxes, cable gland and LT panel shall be mounted on iron angle frame made out of 50mm x 50mm x 6 mm frame with 4 No. legs of size not less than 45 cms each fixed with nut bolts of suitable size at bottom portion of the panel, grouted in PCC foundation 1:2:4 type B-1 with 20 mm graded stone aggregates totally tested on completion including taking down existing LT panel complete and suitable for and including the following :-
(i) MCCB 4 pole, 415 volts, 250 amp rating, microprecesser based energy with rupturing capacity 36 KA - 01 No. as incoming (ii) MCCB 4 pole, 415 volts, Adjustastable Thermal Magnetic (TM) type, 100 amp rating, with rupturing capacity 36 KA - 03 No. for outgoing (iii) Indicator set RYB -01 Set of 3 (iv) Multifunction digital panel meter suitable to display amps, volts, frequency etc - 01 No including CTs of appropriate ratio. (v) All accessories prewired with suitable size copper conductor cable or strip including foundation as per manufacturer instruction all as required and directed.
S&F in repairs junction box, factory fabricated, pole mounted, for street light, size 260mm x 160mm x 250 mm of approved make, made out of 2 mm thick CRCA powder coated sheet as per IP 65, including 63A,Three Phase four wire having four no. aluminium Bus Bar including 6A SP MCB. The box should have auto Door Lock facility with magnetic Lock (both side of plate) using necerssary fixing arrangement such as clamps ,nut, bolts and washer complete all as specified and directed.
Trimming up Bushes/ Tree branches upto 5 mtr all around security light poles & LT line, removing cut branches/ leaves from site complete all as specified and directed, Note :- (i) The overhead lines will be kept clear from all trees by trimming of tree branches with 5 mtr all around the line. (ii) Necessary permission shall be obtained by contractor from department one day prior to trimming and shut down in particular area will be arranged by department. (iii) Only effected Span where tree branches are touching nearly LT lines shall be measured.
M&L for detection of any type of fault in LT underground cable, laid in soil at plane area or forest area, with the help of Cable fault locator machine. Cable fault locator with carriyng vehicle and cable fault detection technician shall be provided by the contractor. Span of faulty cable shall be traced out by the technician by meggering LT cable. Note : (i) Detection of fault in one span of length will be measured as Each Job. (ii) Technicians will be employed by the working agencies. (iii) Excavation & Earth work shaill be measured and paid seperately. (iv) Replacement of cable & joints shall be measured and paid saperately. (v) Measurement & Payment shall be made only if the fault has been located & rectified.
M&L in repairs for mild steel cross arms, bracings, supports, clamps and back plates fabricated from structural steel sections including nuts, bolts, washers, welding, bending cold or hot, drilling holes for bolts, in any shape or size as indicated or directed and inclusive of one primer coat & two coats of aluminium paint including dismantling from pole complete all as specified and directed.
S&F in repairs industrial switchgear busbar chambers of 200 A, of size 600x600x150mm, 6 way for LT cable any size including Indicator for three phase, necessary PCC/Wall mounted work, cable gland, complete all as specified and directed.
S&F in repairs industrial switchgear busbar chambers of 400 A, of size 600x600x150mm, 6 way for LT cable any size including Indicator for three phase, necessary PCC/Wall mounted work, cable gland, complete all as specified and directed.
Dismantling of PCC or steel pole, any type any size including demolition of concrete in foundation etc. and removing from site complete all as specified and directed.
Supply and erecting in repairs in true vertical position steel tubular swaged poles of 9.0 metres long, type 410 SP-31 9mtr complete with cast iron base plate, goose neck bracket, finial taper plug, bolt, nuts & screws as specified and painting internal surface with anti-corrosive paint and external surface painting upto 1.5 m height from base of poles with two coats of synthetic enamel paint Ist quality black & yellow colour alternate strip 30 cm wide over a coat of red oxide primer and remaing portion with two coats of aluminum paint over a coat of red oxide primer, including demolition of PCC, complete all as specified and directed. Note:-Excavation & earth work and concrete in foundation and pedestal shall be measured and paid for separately.
Supply and erecting in repairs broken pole and disposed from site and fixing of new prestressed concrete pole, 9 m long, 102 mm x172 mm at top and 102 mm x 279 mm at bottom, class 10 including Zebra painting to PCC poles up to 1.5 m height from base of poles with two coats of synthetic enamel paint Ist quality black & yellow colour alternate strip 30 cm wide. Note:- Excavation and earth work and concrete in foundation and pedestal shall be measured and paid for separately.
Excavation in Road/ floor cutting of width 20 cm and depth 30 cm for inserting of GI pipe for protection of cable including making good the disturbed surface as per existing specifications complete all as specified and directed.
M&L for servicing /cleaning of solar water heater, complete i.e. Hot water Tank, Evacuated Tubes, Flat Plate tubes, SDR, UPVC Pipes, checking all working parts and removing of unservicable parts and installation new spares as required on site, comlpete all as specified and directed. NOTE:- Parts replaced shall be measured and paid seperately as supply only aganist the appropriate item.
Taking out the broken, rusted solar panels/solar tube frames with supporting angles of any size and M & L for mild steel work of grade Fe-290 (Grade E-165) in stand for solar panel, tank from angles, flats etc all as directed, framed brackets or angles or tees with web and flanges cut to shape, drilled and countersunk for screw, including bending and welding angles as necessar, gusset plates, riviting etc. complete all as specified and directed.
S&F in repairs, of 20mm dia CPVC pipes (Hot & Cold type) SDR 11 and Plain CPVC SDR 11 Fittings on walls/ceiling/trenches or laying in floors complete all as specified and directed.
S&F in repairs, of 25mm dia CPVC pipes (Hot & Cold type) SDR 11 and Plain CPVC SDR 11 Fittings on walls/ceiling/trenches or laying in floors, complete all as specified and directed.
S&F in repairs, of sub main wiring with 2 runs of PVC insulated but unsheathed multi stranded copper conductor FRLS cable 1100 volt grade of size 6 Sqmm and one run of 6 Sqmm single core PVC insulated but unsheathed multi stranded copper conductor FRLS cable 1100 volt grade as earth lead drawn through in and including non metallic PVC conduit of size 20 mm dia (external) with wall thickness not less than 1.8 mm, ISI marked concealed in wall including accessories like bends, tees junction boxes, etc fixed in wall or ceiling etc complete all as specified and directed. NOTE: Two runs of submain wiring cable alongwith one earth wire & conduit shall be counted as one unit.
All as per Srl item No 64 here in before but for 500 to 1000 LPD solar system
S&F in repairs broken flat collector plates tinted glass of solar panel size 2025 mm (Length) x 1025 mm (width) with new one including lifting from floor to roof of the building by manually or mechanically is included in the coated rates, complete all as specified and directed.
S&F in repairs for Rubber flexible Hose pipe of inner dia upto 25mm as per existing heat resistance type suitable for Solar plant of different capacity with suitable clamps, nut and bolts, complete all as specified and directed.
S&F in repairs water heating elements of capacity 2.0/3.0 KW for solar water heater, complete all as specified and as directed.
S&F in repairs, of thermostat for solar water heater complete all as specified and directed.
Attending complaint by deploying skilled Electrician /Plumber and Helper for checking electric motor, startor, Solar water heater and washing machine cum hydro extrator, tumbler and make it functionable and serviceable. Note:- (i) If contractor fail to attend complaint and resolve on same day an amount of Rs 1000.00 per day shall be recovered as penalty by department. (ii) All materials required for attending the complain shall be measured and paid seperately, however T&P shall be included in rate quoted.
S&F in repairs lagging to hot water pipe of superior quality of foam insulation nitrile rubber of thickness not less than 20mm, duly covered with aluminium foil of not less than 0.2mm and binded with suitable size of wire/net as required on site, complete all as specified.
S&F in repairs PP-R Ball valves (brass insert) of size for 20mm dia CPVC pipes as per requirement of the site, complete all as specified and directed.
S&F in repairs PP-R Ball valves (brass insert) of size suitable for 25mm dia CPVC pipes as per requirement of the site, complete all as specified and directed.
S&F in repairs Rotational moulded polyethlene water storage tank of capacity 500 Litres, three layers (cylindrical vertical with closed top), hoisted and fixed in position including 25mm dia PVC ball valve, high pressure with polythene float complete all as specified in SSR Part-1, complete all as specified and directed.
S&F in repairs for 15mm bore bib tap with flange, fancy type, chromium plated, cast copper alloy with crutch or butterfly handle, screwed down, screwed for iron pipe or for brass ferrule and fixed, complete all as specified and directed.
S&F in repairs factory made sheet enclosure for MCB DB SPN 2 way without bus bar 240 volts with single door, IP-43 protection duly fixed / concealed in wall complete and making good disturbed surfaces of wall floor etc including necessary connecting lugging with copper lugs pin / ring type complete all as specified & directed.
S&F in repairs, MCB SPN, 240 Volts, from 32 to 40 Amps with repturing capacity 10 KA 'C' series complete all as specified and directed.
S& F in repairs Solar water Heater Tank of Cap 100 ltr of existing shape and size/ type suitable for existing solar water heating system alongwith atleast 5 years of manufacturer's warranty. Note : Contractor shall provide the gurrantee of the manufacturer alongewith his own gurrentee.
S&F in repairs, Solar water Heater Tank of Cap 200 ltr of existing shape & size/ type for existing solar water heating system with 5 years of manufacturer warranty, complete all as specified and directed. Note : Contractor shall provide the gurrantee of the manufacturer alongewith his own gurrentee.
S& F in repairs Solar water Heater Tank of Cap 300/400 ltr of existing shape and size/ type suitable for existing solar water heating system alongwith atleast 5 years of manufacturer's warranty. Note : Contractor shall provide the gurrantee of the manufacturer alongewith his own gurrentee.
S&F in repairs, Solar water Heater Tank of Cap 500 ltr of existing shape & size/ type for existing solar water heating system with 5 years of manufacturer warranty, complete all as specified and directed. Note : Contractor shall provide the gurrantee of the manufacturer alongewith his own gurrentee.
M&L for plain cement concrete 1:3:6 type C-2 (using 40 mm graded crushed stone aggregate) as in foundation, filling and mass concrete/sunken floors, including demolation of existing PCC of any description, complete all as specified and directed.
M&L for general servicing of washing/ Laundary machine of capacity upto 30 KG by dismantalling all movable/revolving mechanical parts such as (Nut, bolt, washer, gland, greasing for motor) servicing / checking of electronic mechanism all circuits,wiring,push Button, controller, other electrical parts such as Heating element, thermostat, contactor, relays, MCCB, MCB etc. and rewinding of motor with reassembling all parts after necessary servicing and replacement in case of unsv parts, testing machine upto 1 hour of working all as required and directed including replacement of unservicable spare parts, complete all as specified and directed. NOTE:- (i) This Rate is Inclusive of rewinding of machine motors. (ii) Parts such as heating element thermostate contactor, relays, MCCB etc. shall be measured and paid separately as supply only.
Supply only the following parts (against Item No-86 to 96 of Washing Machine cum hydro extractor of capacity 30 kgs- 04 Nos complete all as specified and directed.
Push button with push button element for washing machine of cap 30 Kgs as per sample, complete all as specified and directed.
DTC and TC each for washing machine of cap 30 Kgs as per sample, complete all as specified and directed.
Timer 0 to 60 min for washing machine of cap 30 Kgs as per sample, complete all as specified and directed.
Reversing timer for washing machine of cap 30 kgs, complete all as specified and directed.
Stainless steel plate complete for washing machine of cap 30 kgs as per sample, complete all as specified and directed.
Pressure switch suitable for 30 Kgs washing machine as per sample, complete all as specified and directed.
Toggle switch for washing machine 30 Kgs motor as per sample, complete all as specified and directed.
Single phase preventer suitable for washing machine of cap 30 Kgs as per sample, complete all as specified and directed.
LS Contractor 3 pole 220 volts 32 Amps suitable for 30 Kgs washing machine as per simple, complete all as specified and directed.
Gland dori, fan belt and greasing etc for washing machine of cap 30 kgs as per sample, complete all as specified and directed.
IBLAR sleeves for 30 Kgs washing machine as per sample, complete all as specified and directed.
M&L for General Servicing of washing machine Tumbler Dryer of capacity upto 30 KG by dismentalling all movable/Revolving mechanical parts such as (Nut, bolt, washer, gland, greasing for motor) servicing/checking of electronic mechanism all circuits, wiring, push button, controller, other electrical parts such as Heating Element, Thermostat, contactor, Relays, MCCB, MCB etc. and also including rewinding of motor with reassembling all parts after necessary servicing and replacement in case of unsv parts, testing machine upto 1 hr of working all as required and directed including replacement of following unservicable spare parts. NOTE:- (i) This Rate is Inclusive of rewinding of machine motors. (ii) Parts replaced shall be measured and paid separately as Supply only
Suppply of the following parts (Item No 99 to 107 ) of Washing Machine Tumbler Dryer 25 Kgs- 04 Nos 3 phase 415 volts, 50 Hz AC complete and servicing, greasing and gland dori for Motors, and testing after completion of work, all as specified and directed.
Single phase preventer suitable for 25 Kgs Washing Machine Tumbler Dryer as per sample
Rubber seal and fan belt for 25 Kgs Washing Machine Tumbler Dryer as per sample
Strip heater for washing machine 25 Kgs Washing Machine Tumbler Dryer as per sample
Presser switch pipe suitable for 25 Kgs Washing machine Tumbler Dryer as per sample, complete all as specified and directed.
LS Contractor 3 pole 220 Volts 40 Amps suitable for 25 Kgs Dryer as per sample, complete all as specified and directed.
Relay 2.5 Amps to 8 amps for Dryer Machine Motor as per sample, complete all as specified and directed.
Stainless Steel Spring assy for 25 Kgs Laundry Machine and Dryer assy as per sample, complete all as specified and directed.
Door Open/Close sensor for Laundry Machine and Dryer of Capacity 25 Kgs as per sample, complete all as specified and directed.
MCB Four pole 63 Amps suitable for existing LT panel board to control of Dryer Machine of capacity 25 Kgs as per sample, complete all as specified and directed.
Please Enable Macros to View BoQ information
stage.html
html • 0.03 MB
technical_845468.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 0.28 MB
82TENDERDOCUMENT.pdf
Tender Documents • 0.71 MB
BOQ_845468.xls
BOQ • 3.74 MB
Download all tender documents and submit your bid