Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹1.3 CrAccepted-AOC | ₹1.3 Cr Quoted ₹1.1 Cr | L1 | Accepted-AOC quoted lowest |
| 2 | L2₹1.3 Cr+₹19.2 L (17.4%)Rejected-Finance NO 5 MAIN CHANNEL ROAD ULSOOR BANGALORE KARNATAKA 560008 | BENGALURU URBAN | KARNATAKA | 560008 | ₹1.3 Cr+₹19.2 L (17.4%) | L2 | Rejected-Finance Quoted second lowest amount |
| 3 | Rejected-Technical | - | - | Rejected-Technical all documents mentioned in tender document are not fulfilled |
| 4 | Rejected-Technical OFFICE NO 301 VASANTASAKHA PLAZA NARHE PUNE MAHARASHTRA 411041 | PUNE | PUNE | MAHARASHTRA | 411041 | - | - | Rejected-Technical all documents mentioned in tender document are not fulfilled |
Tender Value
Refer Docs
Closing Date
2 Oct 2024, 2:00 pmClosed
President, Shivtej Farmer Producer Company Limited
Shivtej Farmer Producer Company Limited, Pune Santrushti Prestige Building, Shop No. 05, Opp. Gosavi Hospital, NarayangaonTq. Junnar, Dist. Pune 410504
Supply and Installation Of Refrigeration System
2024_DOAWB_1074860_1
Pune/Shivtej/Goods/2024/20
Open Tender
Farm Machinery and Equipments
Item Rate
60 days
Shivtej Farmer Producer Company Limited
Please refer Tender documents.
8 documents required · 8 mandatory
₹1,000
Exempted
District implementation unit,Pune
1 Jan 2025
28 Aug 2024
3 Oct 2024
28 Aug 2024
2 Oct 2024
28 Aug 2024
9 Sept 2024
Amount
SUPPLY & INSTALLATION OF REFRIGERATION SYSTEM , ELECTRICAL WORK FOR REFRIGERATION The work includes designing, engineering, providing, installing, testing and commissioning of the refrigeration and air conditioning system covering the equipment / materials / services covered in the technical specification, BOQ and the drawings., The erection, testing and commissioning will include lifting of equipment placement and alignment in position, interconnecting piping, controls etc. The system shall be pressure tested and evacuated as per standard practice before charging the refrigerant gas. The plant shall be run on load for 3 days for satisfactory performance; All tools and tackles / welding machines, rods and gases etc. required for fabrication, erection, testing and commissioning etc. shall be arranged by the contractor at his own cost.
SUPPLY & INSTALLATION OF WATER COOLED REFRIGERATION RACK WITHOUT CONDENSOR FOR PRE-COOLING-03 NOS
Indoor Units:- Approved Make:-Star-Cooler & Alfa laval • Product Type : Ceiling Mounted Cooler • Model No : CF-49-64-SP (Star Cooler Make) • No. of Units :3 No’s • Design Duty :75 kw • Room Temp : 0°C • Refrigerant : R404a evaporating @ -5°C ( DX System ) • Air Volume :80000 CMH • Fans :4 x 800 mm Dia Axial Fan, 1440 rpm; • Motor = 3.7 kW ( Each Fan) 415V/3ph./50Hz • Coil Data :4 FPI , Copper tubes With Plain Aluminum Fins. • Internal Volume: 156 dm³,Heat transfer Area:-639.7 m2 • Defrost: Coil= NA , Tray= NA , Fan =NA • Outer Body: GI Powder Coated • Electrical Junction Box Should be of IP 45 Protection. Approved Makes: Star Cooler Make.
EVAPORATIVE TYPE OF CONDENSER • Product Type : Evaporative Condenser (Mix Flow Type) • No. of Units : 1 No’s • Design Duty : 420 kw. • Condensing Temp: 39 °C • Wet bulb Temp: 27 °C • Refrigerant : R404a evaporating • Air Volume : 41000 CMH • Fans : 1 x 1000 mm Dia Axial Fan, 6P-960 rpm; • Motor = 5.5 kW ( Each Fan) 415V/3ph./50Hz,with VFD compatible • Pump:-1.5 kw • Water flow:- 52 CMH • Evaporation rate:- 0.62 m3/h • Heat Transfer area:490 m2 (Coils + Fills) 65 +425 • Tube Volume:- 303 dm3 • Tubes:-19mm0.8 mm SS304 L • Water tank:-SS304 • Casing:-ZAM • Tank volume:-1500 ltrs Approved Makes: Thermax / Starcooler • MOC of fan:-PAG /PPG type high efficiency low power Axial fan should be suitable for quiet operation and made of corrosion resistant material in order to ensure long life and minimal maintenance requirement for the air handling components. Adjustable angle Multi-blade fans for power saving in all weather conditions to be direct driven. Fan motor shall be TEFC type, high efficiency suitable 415 Volts, three phase, 50 hertz supply . • No. of spray pumps each:-The recirculating spray water pump will be close coupled, centrifugal pump with TEFC motor 415 Volts, three phase, 50 hertz supply. • MOC of casing:-All casing panels and structural elements shall be of heavy duty construction made up of • JSW AZ-150 (Aluminium Zinc Coated CS Sheets) • MOC of coil:-SS 304L • •The Coil section shall be fabricated of continuous lengths of SS304L & pneumatically tested at 375 psig. • MOC of cold water basin:-JSW SS 304 Basin shall include tapered basin with drain/ clean out connection. The basin area under the fill area shall be sloped towards the drain outlet to facilitate cleaning. There should be no leakage in the water basin. The basin will be provided with suction strainer • at pump inlet. The water make up assembly shall be adjustable float type. • Fan Make:-Siemens/Hindustan • Pump Make:-Grundfos/KSB • Maintenance:-Access Door • Safety:-Handrails • Ladder:-Unit mounted Ladder
ALLIED ACCESSORIES FOR PRE COOLING ROOMS. • Supply of Liquid & Suction Refrigerant piping with Suction Line Rubber Nitrile Insulation connecting Indoor unit to Outdoor Unit For Medium Temperature Application. Refrigeration System as per Specifications suitable for site installation conditions with necessary supports / brackets , fittings & Clamps. (AS PER GA DRAWING) • Supply of Electrical Cabling connecting Indoor unit to Outdoor Unit & control panel for Medium Temperature Application. Refrigeration System as per Specifications suitable for site installation conditions with necessary supports / brackets,fittings & Clamps.(AS PER GA DRAWING) • Supply of Electronic Expantion Valve with all Components in Suction & Liquid Line. • IP 65 Internal lighting & Cabling. • Supply of PVC drain piping as per Specifications for Cold Rooms. • Supply of Epoxy Coated M S Base Frame for Installing Evaporator units in Precooler Rooms. • Supply of Solid Cable Tray of 18 Gauge , Painted with RAL-9002 white, 400 mm Wide x 50 mm Collar Height with all necessary supports for Supporting & routing Refrigerated Copper Piping & Cables neatly as per Specifications • Electrum Make Control Panel with all auotomatic function with Data system. • Copper Pipe 14 Gauge & Armaflex Insulation ,Polycab or Finolex make copper cables , for Drain consider C Pvc Pipe with fitting.
SUPPLY & INSTALLATION OF AIR COOLED CDU WITH AIRCOOLED CONDENSOR FOR COLD STORAGE-1
CDU:-(Approved Make:-Bitzer Imported/ Frascold) • Refrigerant: R404 a • Room Temp: 0* C • Evap. Temp: -5* C • COP: 1.58 • Ambient: 45 *c • Compressor Type Semi-Hermetic Reciprocating Compressor • Actual Capacity (KW) 25 kw • Comp. Power (KW). 15 kw • Condenser 2 Fan suitable for High ambient • Oil separator • Adequate receiver with sight-glasses, safety valve and service angle valve. • HP/LP • Filter Drier • Solenoid valve • Suction Accumulator • Pressure Gauge • Refrigeration controls Make DANFOSS / EMERSON /CASTEL • Structure material (Channel / Square section) M.S. With PU Painting / Coating
INDOOR UNIT:- (Approved Make:-Star Cooler/ Alfa-Luve) • Product Type : Ceiling Mounted Cooler • Design Duty :25 kw (1 Circuit) • Room Temp : 0°C • Refrigerant : R404a evaporating @ -5°C ( DX System ) • Air Volume :26000 CMH • Fans :2 x 710 mm Dia Axial Fan, 1440 rpm; • Motor = 1.1 kW ( Each Fan) 415V/3ph./50Hz • Coil Data :4 FPI , Copper tubes With Plain Aluminum Fins. • Internal Volume:42 dm³ • Heat Transfer Area :-147m2 • Defrost: Coil= NA , Tray= NA , Fan =NA • Outer Body: GI Powder Coated • Electrical Junction Box Should be of IP 45 Protection.
ALLIED ACCESSORIES • Supply of Liquid & Suction Refrigerant piping with Suction Line Rubber Nitrile Insulation connecting Indoor unit to Outdoor Unit For Medium Temperature Application. Refrigeration System as per Specifications suitable for site installation conditions with necessary supports / brackets , fittings & Clamps. • Supply of Electrical Cabling connecting Indoor unit to Outdoor Unit & control panel for Medium Temperature Application. Refrigeration System as per Specifications suitable for site installation conditions with necessary supports / brackets, fittings & Clamps. • Supply of Expantion Valve with all Components in Suction & Liquid Line. • IP 65 Internal lighting & Cabling • Supply of PVC drain piping as per Specifications for Cold Rooms. • Supply of Epoxy Coated M S Base Frame for Installing Evaporator units in Precooler Rooms • Supply of Solid Cable Tray of 18 Gauge, Painted with RAL-9002 white, 400 mm Wide x 50 mm Collar Height with all necessary supports for Supporting & routing Refrigerated Copper Piping & Cables neatly as per Specifications. • Supply of Refrigerant R-404A For Refrigerated Equipment. • Copper Pipe 14 Gauge & Armaflex Insulation , Polycab or Finolex make copper cables , for Drain consider C Pvc Pipe with fitting. • Electrum Make Control Panel with all auotomatic function with Data system • Electrical control panel cubicle type, dust and vermin proof copper bus bars and suitable for 415 Volts, 3 phase, 50 C/s A.C. supply and incorporating the following: a) Incoming MCCB Rating as required. b) Earth leakage current ELR and suitable ELCB c) MCBs and starters for condensing units, air handling unit, ACUs in cold stores, ante room
SUPPLY & INSTALLATION OF AIR COOLED CDU WITH AIRCOOLED CONDENSOR FOR COLD STORAGE-2
CDU:-(Approved Make:-Bitzer Imported/ Frascold) • Refrigerant: R404 a • Room Temp: 0* C • Evap. Temp: -5* C • COP: 1.58 • Ambient: 45 *c • Compressor Type Semi-Hermetic Reciprocating Compressor • Actual Capacity (KW) 28 kw • Comp. Power (KW). 20 kw • Condenser 2 Fan suitable for High ambient • Oil separator • Adequate receiver with sight-glasses, safety valve and service angle valve. • HP/LP • Filter Drier • Solenoid valve • Suction Accumulator • Pressure Gauge • Refrigeration controls Make DANFOSS / EMERSON /CASTEL • Structure material (Channel / Square section) M.S. With PU Painting / Coating
INDOOR UNIT:- (Approved Make:-Star Cooler/ Alfa-Luve) • Product Type : Ceiling Mounted Cooler • Design Duty :28 kw (1 Circuit) • Room Temp : 0°C • Refrigerant : R404a evaporating @ -5°C ( DX System ) • Air Volume :32500 CMH • Fans :3 x 710 mm Dia Axial Fan, 1440 rpm; • Motor = 1.1 kW ( Each Fan) 415V/3ph./50Hz • Coil Data :4 FPI , Copper tubes With Plain Aluminum Fins. • Internal Volume:50 dm³ • Heat Transfer Area :-177m2 • Defrost: Coil= NA , Tray= NA , Fan =NA • Outer Body: GI Powder Coated • Electrical Junction Box Should be of IP 45 Protection.
ALLIED ACCESSORIES • Supply of Liquid & Suction Refrigerant piping with Suction Line Rubber Nitrile Insulation connecting Indoor unit to Outdoor Unit For Medium Temperature Application. Refrigeration System as per Specifications suitable for site installation conditions with necessary supports / brackets , fittings & Clamps. • Supply of Electrical Cabling connecting Indoor unit to Outdoor Unit & control panel for Medium Temperature Application. Refrigeration System as per Specifications suitable for site installation conditions with necessary supports / brackets, fittings & Clamps. • Supply of Expantion Valve with all Components in Suction & Liquid Line. • IP 65 Internal lighting & Cabling • Supply of PVC drain piping as per Specifications for Cold Rooms. • Supply of Epoxy Coated M S Base Frame for Installing Evaporator units in Precooler Rooms • Supply of Solid Cable Tray of 18 Gauge, Painted with RAL-9002 white, 400 mm Wide x 50 mm Collar Height with all necessary supports for Supporting & routing Refrigerated Copper Piping & Cables neatly as per Specifications. • Supply of Refrigerant R-404A For Refrigerated Equipment. • Copper Pipe 14 Gauge & Armaflex Insulation , Polycab or Finolex make copper cables , for Drain consider C Pvc Pipe with fitting. • Electrum Make Control Panel with all auotomatic function with Data system • Electrical control panel cubicle type, dust and vermin proof copper bus bars and suitable for 415 Volts, 3 phase, 50 C/s A.C. supply and incorporating the following: a) Incoming MCCB Rating as required. b) Earth leakage current ELR and suitable ELCB MCBs and starters for condensing units, air handling unit, ACUs in cold stores, ante room
RINAC INDIA LIMITED
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .