Tender Value
Refer Docs
EMD Value
₹96,000
Closing Date
19 Dec 2020, 6:00 pmClosed
GE I R and D Kanchanbagh
GE I R and D Kanchanbagh Kanchanbagh Post Hyderabad 500058
REPAIR/ MAINT OF E/M PORTION OF DISTRIBUTION BOARDS, HT/LT PANELS SWITCHGERS, RELAYS, CAPACITOR BANKS DISTRIBUTION/ POWER TRANFORMER AND ITS ACCESSORIES LT/HT UG CABLES OVERHEAD LINES UNDER AGE E/M-1, KANCHANBAGH, HYDERABAD.
2020_MES_399257_1
GE I KBAGH TOKEN 66 OF 2020 2021
Open Tender
Electrical and Maintenance Works
Item Rate
270 days
Hyderabad
Please refer Tender documents.
8 documents required · 8 mandatory
₹500
Yes
GE I R and D Kanchanbagh
₹96,000
Yes
4 Jan 2021
28 Nov 2020
21 Dec 2020
28 Nov 2020
19 Dec 2020
12 Dec 2020
30 Nov 2020 - 7 Dec 2020
Amount
Dismantling the defective jumpers of 11 KV, supply and connect new jumper with ACSR conductor with proper binding to HT/LT over head line conductor including binding wire, bolts, nuts, washers and suitable aluminium lugs complete for HT/LT over head line, structures complete all as directed.
Servicing of existing 33 KV Air break Switch of rating upto 800 Amps duly applying petroleum jelly after cleaning the contact from the rust and deposited carbon including tightening of all the loose connections making good for operation complete all as directed.
Renewal of 33 KV worn out structure jumper with new aluminium jumper (panther size) with new aluminium clamp including bolts, nuts and washers complete all as directed.
M&L for disconnection of old unserviceable clamp and S&F of new Busbar Clamps of existing size and GI pipe support for aluminium pipe suitable for 33 KV complete all as directed.
Supply and Fixing in repairs explusion type fuses with holder 11000 Volts, 40 Amps for outdoor Capacitor complete all as directed. Make- Magnewin
Servicing of existing 33 KV Breakers by disconnecting all control wiring connection and after completion reconnecting the same with all moving & all non moving parts by cleaning and removing dust and applying petrolium jelly & oil to all moving parts and repairs to minor parts and check all parts are functioning including draw out mechanism servicing and oiling including tightening of all the loose connections/ parts and making good for operation complete all as directed Note:- (i)Spare Parts costing upto Rs 1500.00 shall be included in the quoted rate.(ii)Major parts shall be measured and paid seperately under relevant items.
Servicing of existing 11 KV Breakers (SF6 or VCB type) by disconnecting all control wiring connection and after completion reconnecting the same. Opening of All Mechanical and non mechanical parts including charging mechanism, chain by cleaning and removing dust & old oil/grease and applying petrolium jelly & oil to all moving parts and repairs to minor parts and check all parts are functioning including draw out mechanism servicing and oiling including tightening of all the loose connections/ parts and making good for operation complete all as directed . Note :- (i)Spare Parts costing upto Rs 1500.00 shall be included in the quoted rate.(ii)Major parts shall be measured and paid seperately under relevant items.
Cutting and trimming tree branches of any girth and of any size touching the overhead lines and clearing the distance upto 1.5 mtr length on both sides of OH line with in a span 35 metres each, disposing the same and clearing the site complete all as directed .
Servicing of 11 KV AB switches upto 400Amps by dismantling & overhauling and re-assembling, testing & commissioning complete all as directed. Note: Male/female contacts shall be measured and paid separately under relevant items.
Supply only Male contacts suitable for 33/11 KV Air Break switch complete all as directed.
Supply only Female contacts suitable for 33/11 KV Air Break switch complete all as directed.
S&F disc insulator single disc 11 KV grade porcelain vitreous brown or green 145mm high and 255 mm dia including taking out old unserviceable insulator complete all as directed.
S&F pin type insulator single disc 11 KV grade porcelain vitreous brown or green insulator including one galvanised iron washer and one nut 150mm high and 150 mm dia including taking out old unserviceable insulator complete all as directed.
Disconnecting the electric supply and taking down the broken unserviceable post top insulator and S&F post top porcelain insulator vitreous brown with GI clamp, nuts & bolts etc suitable for 11000 Volts grade working pressure complete all as directed.
Isolate,disconnect,dismantle the burnt out lugs from main switches/MCCB and crimping with new lugs as per existing one including fixing, insulation, termination to main switch/MCCB for the following sizes of cables complete all as directed Note : For new Cable cleaning both end insulation as required length and fixing new lugs as per size including well crimping to the lugs for both ends of cable complete shall be included in quoted rates.
35 sqmm to 50 sqmm
70 sqmm to 95 sqmm
120 sqm to 240 sqmm
240 sqmm to 300 sqmm
Meggering of cable for checking of fault for fault rectification of any size any palce after disconnection of cable from both side including relooping and relaying and refixing the same after fault rectification.
Meggering of HT Overhead conductor between Span to Span/Six pole structure/four pole structure of any type of insulator with complete diconnection & reconnection of jumper for checking of fault and rectification for any size at any place after disconnection of AB switch complete all as directed.
Disconnecting and taking down old exisiting CTs from VCB after taking shutdown complete, breaker removing, Supply and fixing New CT on position with all connection complete testing and commissioning of Metering and Protective CT 11000V Core-1- 150/5 A Burden-15VA Class-1, Core-2- 150/5A, Burden-15VA Class-5P, ISF/ALF-10 of STC-18.4 KV for 3 Sec, 50 Hz, Insulating level- 12/28/75 KV complete all as directed. Make: SCHNEIDER/CROMPTON GREAVES/ KAPPA/AE/ STATCON
Disconnecting and taking down old exisiting Bus bar insulator from VCB after taking shutdown complete breaker removing, Supply and fixing New Bus bar insulator in position with all connection complete testing and commissioning 11000V of capacity 1250 Amps on existing aluminium bus bar including cleaning with CTC and insulation of bus bar complete all as directed.
Supply & fixing Trip/ Closing Coils for SF6 Brakers operated on 30/110Volts DC including taking down old unserviceable Coil complete all as directed. (Note- one trip & one closing coil 30/110 volt treated as one set)
M&L for Cable jointing kit for 11 KV (earthed) grade cable for indoor termination heat shrink type joint complete with jointing material and accessories suitable for 3 core XLPE armoured aluminium conductor cable of size 50 to 95 Sqmm including taking down unserviceable jointing kit complete all as directed.
M&L for Cable jointing kit for 11 KV (earthed) grade cable for indoor termination heat shrink type joint complete with jointing material and accessories suitable for 3 core XLPE armoured aluminium conductor cable of size 120 to 185 Sqmm including taking down unserviceable jointing kit complete all as directed.
M&L for Cable jointing kit for 11 KV (earthed) grade cable for indoor termination heat shrink type joint complete with jointing material and accessories suitable for 3 core XLPE armoured aluminium conductor cable of size 240 to 300 Sqmm including taking down unserviceable jointing kit complete all as directed.
M&L for Cable jointing kit for Eleven KV (earthed) grade cable for straight through heat shrink type joint complete with jointing material and accessories suitable for 3 core XLPE armoured aluminium conductor cable of size 50 to 95 Sqmm including taking down unserviceable jointing kit complete all as directed.
M&L for Cable jointing kit for Eleven KV (earthed) grade cable for straight through heat shrink type joint complete with jointing material and accessories suitable for 3 core XLPE armoured aluminium conductor cable of size 120 to 185 Sqmm including taking down unserviceable jointing kit complete all as directed..
M&L for Cable jointing kit for Eleven KV (earthed) grade cable for straight through heat shrink type joint complete with jointing material and accessories suitable for 3 core XLPE armoured aluminium conductor cable of size 240 to 400 Sqmm including taking down unserviceable jointing kit complete all as directed.
M&L for Cable jointing kit for 11 KV (earthed) grade cable for outdoor termination heat shrink type joint complete with jointing material and accessories suitable for 3 core XLPE armoured aluminium conductor cable of size 240 to 300 Sqmm complete all as directed.
M&L for Cable jointing kit for 11 KV (earthed) grade cable for outdoor termination heat shrink type joint complete with jointing material and accessories suitable for 3 core XLPE armoured aluminium conductor cable of size 120 to 185 Sqmm including taking down unserviceable jointing kit complete all as directed.
M&L for Cable jointing kit for 11 KV (earthed) grade cable for outdoor termination heat shrink type joint complete with jointing material and accessories suitable for 3 core XLPE armoured aluminium conductor cable of size 50 to 95 Sqmm including taking down unserviceable jointing kit complete all as directed. Make for item No. 24 to 32:- REYCHEM/ DENSON/ M-SEAL/3M
Supply and filling of transformer oil in transformer of plinth / pole mounted including testing complete all directed. Make :- SERVO/POWER OIL
Dehydration including filtration cleaning of transformer oil in transformer indoor/ outdoor type at different location of DMRL area by centrifusion / machine having minimum capacity 1000 to 3000 ltrs/ hour including testing oil before and after dehydration complete all as directed.
Replacement of Silica gel complete all as directed.
M&L for Renewal of Fuse wire by using appropriate amp rating tinned copper fuze wire with all safety precaution like hand gloves Earth rod at site of any height of six/four/two pole structure all as directed. One Job includes all three fuse wires)
Supplying only Tinned Copper fuse wire of 16SWG to 22 SWG or 30Amps to 200 Amps capacity
Excavation in trenches not exceeding 1.5m wide and not exceeding 1.5m in depth and getting out in hard/dense soil for foundation of poles, structures, stay rods, laying of underground cable etc complete all as directed.
Returning, filling in, including spreading, leveling, watering and well ramming in layers each not exceeding 25cm thick using soil complete all as directed .
Removing excavated soil to a distance not exceeding 50m and depositing where directed at a level not exceeding 1.5m above the starting point complete all as directed.
Supply and spreading of dry river sand in trenches/ transformer yard / two pole structure yard for cable protection complete all as directed. Note:- Punned thickness only shall be measured for payment purpose.
M&L for laying common burnt bricks, sub class 'B', of size 230 x 115 x 75 mm in trenches for cable protection complete all as directed.
Supply, laying, testing and commissioning in trenches/ ducts, fixed on walls/panels of LTUG cable, 1100 volts grade, PVC insulated, PVC unsheathed armoured with aluminum conductor cable complete including lugs of requied sizes for the following nominal cross sectional areas of cables including taking down old unserviceable cable complete all as directed:- Make: HAVELL'S/UNIVERSAL/CCI/GLOSTER/KEI/ POLYCAB/ KEC INTERNATIONAL (RPG)
2 core x 10 Sqmm
4 core x 16 Sqmm
4 core x 25 Sqmm
3.5 core x 50 Sqmm
3.5 core x 70Sqmm
3.5 core x 120Sqmm
3.5 core x 185 Sqmm
3.5 core x 400 Sqmm
3.5 core x 240 Sqmm
Material and Labour for cutting existing BT road/PCC of size 45cm x 60cm for taking out/laying of underground cable and including necessary earth work and refilling the same in layers well ramming including watering as required and matching with the existing surface with 200mm thick PCC 1:2:4 type B1 and curing the same with wet gunny bags and removing debris to a distance not less than 50m complete all as specified and directed.
Supply and lay GI tubing 100mm dia, light grade for cable protection at road crossing/on poles and tubing sealed at bith ends after laying the cables including taking out old GI tubing complete all as directed.
All as per iem No 42 here-in-before but 80mm dia Make for item Nos.42 & 43: ZENITH/ TATA/ JINDAL/SWASTIC
M&L for earthing complete with Galvanised steel earth plate electrode 60cm x 60cm x 6.0mm, buried directly in ground( earth pit not less than 2.25 mtr deep below ground level) with top edge of the plate not less than 1.5m below ground level connected to and including GI strip 25x4 mm protected with GI light grade pipe 40mm dia for earth electrode upto test point or upto 7.5 mtr whichever is less by means of bolts, nuts, check nuts and washers all as shown in electrical plate No 3 (of SSR part-I) connected to earthing test point including provision of necessary excavation and earth work in any type of soil, PCC 1:3:6, type C1 as in earth pit, RCC 1:2:4 type B1, cover slab, 50mm thick with 8mm dia TMT bars @ 100cm c/c both ways, GI water pipe 20mm bore medium grade, water funnel, comman salt, charcoal, including testing, including taking out existing earth pit, completion complete all as specified.
S&F in repairs MCCB 200 Amps, 4 pole 50 HZ, 25 KA, complete all as directed.
S&F in repairs MCCB 100 Amps, 4 pole 50 HZ, 25 KA, complete all as directed.
S&F in repairs MCCB 125 Amps, 4 pole 50 HZ, 25 KA, complete all as directed.
S&F in repairs MCCB 400 Amps, FP, 50HZ, 35/36KA complete all as directed.
S&F in repairs MCCB 630 Amps, 4 pole 50 HZ, 35/36 KA , complete all as directed. Note for item No. 45 to 49: Cost of fixing on to walls/surface on suitable angle iron bracket support and civil work shall be included quoted rate.
S&F in repairs MCCB 100 Amps, 4 pole 50 HZ, 35/36 KA, complete all as directed.
S&F in repairs MCCB 125 Amps, 4 pole 50 HZ, 35/36 KA, complete all as directed.
S&F in repairs MCCB 160 Amps, 4 pole 50 HZ, 35 KA, complete all as directed. Make for item Nos.45 to 52:- ABB (T-Max)/ SIEMENS(3VT)/ LEGRAND (DPX)/ L&T (D-Sin)/ SCHNEIDER (NSX) CONTROL & SWITCHGEARS/ HAVELLS
S&F in replacment MCCB enclosure of suitable size for MCCBs 4P upto 250Amps capacityof existing size complete all as directed.
S&F in replacment MCCB enclosure of suitable size for MCCBs 4P 400/630Amps capacityof existing size complete all as directed.
Replacement of air breather of any type up to 625 KVA transformer complete with filled silica gel complete all as directed.
M&L for steel tubular swaged pole, type 410, SP-31 (9.0 meter long) complete with CI base plate and errection of pole including excavation and earth work and PCC (1:3:6) type D2 for foundation base and for foundation and coping with PCC (1:2:4) type B1 and painting with two coats of aluminium painting over a coat of red oxide primer & white wash for PCC coping including taking down old pole complete all as directed and all as per SSR part I. Make: National tubing co.,/India Tubes co.,/ Bharat Poles. Note:- Crane charges for erection shall be deemed to be included in quoted rate.
Supply & stringing in repairs ACSR conductor including binding wire/ necessary clamps etc.,complete all as directed.
S & F in repairs cross arms, bracings, supports, clamps and back plates fabricated from structural steel sections including nuts, bolts, washers, welding, bending cold or hot, drilling holes for bolts, in any shape or size as indicated or directed inclusive of two coats of aluminum painting over a coar of primer complete all as directed.
Demolition of old broken PCC coping for LT/HT pole and M&L for PCC 1:2:4, type B-1 (using 20mm graded stone aggregate) as in coping of size 60x60x60cm including use of form work (straight or curved), weathering , slightly rounded or chamgerged angles and throating and white wash complete all as directed.
Dismantling of LT pole of any height by taking out from PCC foundation and shifting to other location as directed , fixing the pole in true vertical position including excavation and earth work, PCC 1:3:6 type C2 (using 40mm graded stone aggregate) as in base concrete, foundation base & foundation and PCC 1:2:4, type B1 for coping of poles all as specified in SSR Part I-2009 including white wash to concrete surface complete all as directed.
Painting to the existing cubical type LT control panel board made out of CRCA sheet mounted on PCC near transformers including preparation by rubbing, scrapping removing rust/dirt or grease from the surface and painting with duco spray painting with smoke grey synthetic enamel paint and paint shall conform to IS 2032 complete all as directed.
M&L for renewal of earth chambers of PCC 1:3:6 type C1 and 40 mm thick RCC cover slab 1:2:4 type B1 with 8 mm dia TMT Bars at 140 mm c/c including replacement funnel and takingout unserviceable earth chamber complet all as directed.
Renewal of existing unserviceable ACSR jumper connect proper binding to in HT/LT Over Head line as that of existing size not exceeding to 1.5 m length including binding wire, nuts & bolts washers and suitable aluminium lugs complete all as specified and directed.
Disconnection of all Primary/Secondary connection of the defective transformer of any KV rating, out door / indoor any make taking down / out from plinth / pole / platform with the help of crane and transporting the same carefully to workshop for repair and bringing back and install, with all connections as per directions, after repair to its existing position, upto 800 KVA capacity of transformer complete with testing and commissioning, complete all as directed.
Opening of the 11 KV / 0.433 KV transformer 500 KVA to 1000 KVA by removing the inspection cover / top cover, decanning of the transformer oil up to the required level for replacement of leaked cork seal with insulator or LT/HT bush (which is unsv) complete from the shell and making again connections of LT/HT bush to avoid leakage of oil refilling back to existing oil into the transformer testing & commissioning complete all as directed Note : HT/LT bush will measured and paid separately under relevant item and cork seal with insulator is deemed to be included in quoted rate.
M&L for opening the top of Transformer upto 1000 KVA for renewal of jumpering (with brazing or welding) with new copper wire of existing size after removal of burnt out jumpering including decanning of oil upto required level and testing the tranformer complete all as directed.
Restringing of HT/LT overhead ACSR conductor from pin/ disk/ Shackle insulators for removing excessive sag and tying the same with suitable binding wire to insulators and connecting in position complete all as directed by Engr-in-charge. Note :- complete span of conductors between two poles shall be measured as one job
Removing of stone aggregate from the yard and depositing a side for 2 pole structure yard for the filling of stone dust in yard and refilling the same duly cleaning (first 40mm aggregate and 20mm aggregate after it) from the foreign materials and dust after laying stone dust layers complete all as directed by Engr-in-Charge. Note :- Minimum 6 inches Stone dust shall be filled after punning down.
All as per ser Item No. 68 but for 4/6 Pole Structures.
Supply and spread grade stone aggregate 40mm in structure yard 2/4 poles complete all as directed
Supply and spread grade stone aggregate 20mm in structure yard 2/4 poles complete all as directed
Supply & Fixing flood lights 80 watts including removal of existing & complete all as directed
Supply & Fixing flood lights 150 watts including removal of existing & complete all as directed
Dismantling of old unserviceable Panel and Supply & fabrication of LT Panel Board CPRI approved cubical type made of 2 mm thick sheet steel indoor type with IP 67 grade of protection CRCA sheet powder coated with support of angle iron of 50 x 50 x 6 mm angle iron bottom legs with minimum height of 20 cm frame with double hinged front openable shutters of each feeder control unit with locking arrangement in front and back openable inspection doors PVC sleeved Aluminium bus bar of 500 Amps capacity for each phases and half neutral fixed on suitable insulator all housed in suitable bus bar chamber and cable alloy including provision and fixing of digital Voltmeter -01 No, Ammeter-01 No, CTs of suitable ratio, and Indicating LED type lamp for Red, Yellow and Blue in incomer phases complete along with provision of necessary cable entry/exit boxes for all incoming and out going cables with suitable cable glands etc fixed on suitable PCC foundations, testing and commissioning complete and consisting the following :- (Drawing of Panel and connections shall be approved by Engr-in-Charge before starting the panel work. (a) MCCB 4 Pole 250 Amps 35KA -01 No. (as Incoming) (b) MCCB 3 Pole 125 Amps 25KA -03 No. (as Outgoing) Make-L&T/Schneider/ABB/Havells/C&S
Supply & fixiing of air termination single pointed copper rod 12mm dia and 300 mm long including removal of the existing and complete all as directed
S & F Aluminium strip 25 x 3 mm with saddles and fixing screws etc for roof conductors and down conductors above ground including removal of existing and complete all as directed
M&L for Renewal of Fuse wire by using appropriate amp rating tinned copper fuze wire with all safety precaution like hand gloves Earth rod at site of any height of six/four/two pole structure all as directed. One Job includes all three fuse wires)
Supplying only Tinned Copper fuse wire of 16SWG to 22 SWG or 30 Amps to 200 Amps capacity
S&F in repairs for Test point terminal block made out of gun metal or phosphorus bronzed size 75x75x25mm, drilled and screwed including 03 Nos 8mm dia 25mm long hexagonal head screw all as specified and directed
S&F in repairs for GI pipe light grade 50 mm bore , 1.2 mtr long duly threaded on both side for fixing GI socket & making necessary arragement for holding of air terminal rod all as specified & directed
M&L for opening the top of Transformer upto 625 KVA for renewal of jumpering (with brazing or welding) with new copper wire of existing size after removal of burnt out jumpering including decanning of oil upto required level for completing the work and testing the tranformer complete all as directed.
Disconnection of all Primery/Secondary connection of the defective transformer of any KV rating, out door / indoor, of any make, taking down / out from plinth / pole / platform with the help of crane and transporting the same carefully to workshop for repair including and bringing back and install, with all connections as per direction, after repair in its existing position, upto 625 KVA capacity of transformer, testing and commissioning complete all as directed.
Making Primery/Secondary coil with insulating copper wire of required gauge, craft paper, cotton tape, HT/LT insulation including oven charges and labour charges as per specification of old transformer including making of coil as required of various capacity of transformer complete all as directed.
Supply and fixing of HT bushing including metal parts and washer complete for any make of plinth/pole mounted transformer up to 625 KVA capacity complete all as directed.
Supply and fixing of LT rod / studs for up to 625 KVA transformer made of brass with nuts and washers, Insulator and fittings etc as per size and shape of original complete all as directed.
Supply and fixing Gasket set upto 625 KVA for top of transformer or conservator tank after decanning the required level of oil and refilling the decanned oil after fixing the gasket complete all as directed.
Dismantling of old unserviceable Panel and Supply & fabrication of LT Panel Board CPRI approved cubical type made of 2 mm thick sheet steel indoor type with IP 67 grade of protection CRCA sheet powder coated with support of angle iron of 50 x 50 x 6 mm angle iron bottom legs with minimum height of 20 cm frame with double hinged front openable shutters of each feeder control unit with locking arrangement in front and back openable inspection doors PVC sleeved Aluminium bus bar of 500 Amps capacity for each phases and half neutral fixed on suitable insulator all housed in suitable bus bar chamber and cable alloy including provision and fixing of digital Voltmeter -01 No, Ammeter-01 No, CTs of suitable ratio, and Indicating LED type lamp for Red, Yellow and Blue in incomer phases complete along with provision of necessary cable entry/exit boxes for all incoming and out going cables with suitable cable glands etc fixed on suitable PCC foundations, testing and commissioning complete and consisting the following :- (Drawing of Panel and connections shall be approved by Engr-in-Charge before starting the panel work. (a) MCCB 4 Pole 200 Amps 35KA -01 No. (as Incoming) (b) MCCB 3 Pole 63 Amps 25KA -04 No. (as Outgoing) Make-L&T/Schneider/ABB/Havells/C&S
Supply and fixing in repairs post top porcelain insulator vitreous brown with GI clamp, nuts, bolts etc suitable for 11000 Volts grade working pressure complete all as directed.
S&F 11 KV Grade, Lightning arresters expulsion type complete (Set of Three) with all fittings, transmission class,11000Volts discharge capacity 65KA complete all as directed
S & F in repairs drop out fuse assembly 11KV (set of three) , rated current 100A, complete all as directed
Supply and Fixing Battery cell UPST 100 for 110V or 30 V Battery Bank. Make :- Exide - UPST 100.
M&L for cable end termination kit, heat shrinkable, outdoor type, suitable for 3 core x 120 to 185 Sqmm HT, 11 KV cable with necessary lugs complete all as directed
M & L Galvanised iron tubing 80 mm dia light grade laind in trenches/floors/walls for eath lead protection and cables at road crossing etc complete all as specified and directed. Make: ZENITH/ TATA/ JINDAL/SWASTIC
M&L in replacement of analog type Winding tempreture indicator ,50-60 HZ ,110-220 V IP 48 temperature 0-160 degree mild steel body and indicator for oil/ temperature for any type/size /capacity transformer all as specified and directed
M&L in replacement of analog type Oil tempreture indicator, 50-60 HZ,110-220 V IP 48 temperature 0-160 degree mild steel body and indicator for oil/ temperatureor any type/size /capacity transformer all as specified and directed
M&L in replacement of Mog Magnetic oil level indicator,of aluminium body, industrial use of size 1500mm, temprture indication upto 30 DC , works on max pressure4Kg/sqcm accuracy 95% complete for any type/size /capacity transformer all as specified and directed
M&L in replacement of buchholz relay/gas operative relay of existing size and shapeall as specified and directed
Supply, erect, Testing & Commissioning of numerical directional Over Current & Earth fault relay WITH 16 DI, 16 DO, 4 groups , complete control wiring with material, Programming/setting/calibration including software of relays required and necessary addition/alternation of panel alongwith dismantling of old unserviceable old type of relay Make- C&S , Schneider, ABB/L&T/Semiens
Disconnecting of11 KV VCB for shifting including crane, transportation to new location with in 2km & manual labour any required for the job and fixing in new location with all cables, nuts, bolts etc complete all as directed.
Servicing of VCB including checking of mechanism fixed and moving contacts tightning of mechanism complete cleaning and testing of control wiring closing of circuit wiring testing of CTS & PTS insulation resistance valves, testing of operation manually including complete cleaning of panel and bus chamber complete all as directed.
Servicing of existing On Load Tap Changer of Power Transformer including repair/ replacement of wornout parts/ coils, moving contact and testing to founctioning properly complete all as directed.
Comprehensive Maintenance for 9 (Nine) months of Boom Barriers (04 Nos)/Hydraullic bollards (02 Nos)/Tyre shredder (01 Nos) Make-Godrej installed at Main Gate DLRL including checking, testing, carrying out Inspection visit and service visit compete along with attending breakdown on phone calls as directed Note (i) Comprehensive maintenance should carried out by Original Equipment Manufacturer only and service reports shall be submitted. (ii) The contractor would need to have an agreement with the OEM or OEM partner to provide Comprehensive Maintenance for 9 (Nine) months and submit the agreement copy to the Engineer-in-charge before commencement (iii) Visits shall includes service and inspections (iv) The OEM or OEM partner would setup a dedicated email or mobile No to receive and attend the issues, It would also provide an escalation matrix and contact numbers.
S&F in repairs Control PCB for G6000 Boom Barrier testing & commissioning complete all as specified.
M.R.ENTERPRISES
ELEVATORS MAINTENANCE ENGINEER WORKS
saradhi construction combines
Indu Electricals
Shreshta Associates
omsai thermax engineers
Maruthi international
stage.html
html • 0.06 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .