Loading…
India Infra Updates on WhatsApp
Join the Tenderkart WhatsApp channel for India Tender Updates
Loading…
Tender ID
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹27.0 LAccepted-AOC 3838 2ND FLOOR SECTOR 46 C CHANDIGARH UT 160047 | CHANDIGARH | CHANDIGARH | CHANDIGARH | 160047 | L1 | Accepted-AOC The lowest bidder | |
| 2 | L2₹33.5 L+₹6.1 L (22.1%)Rejected-AOC 262 1 NEAR MANAV CHOWK NEW GRAIN MARKET AMBALA CITY HARYANA HARYANA 134003 | AMBALA | HARYANA | 134003 | L2 | Rejected-AOC Other than the lowest bidder |
Tender Value
₹25 L
EMD Value
₹50,000
Closing Date
2 Oct 2023, 6:00 pmClosed
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
GE (I) JUTOGH
GE (I) JUTOGH, JUTOGH CANTT SHIMLA (HP) - 171008
REPAIR AND MAINTENANCE OF LT ELECTRIC SUPPLY NETWORK ALONGWITH CONNECTED ITEMS AT JUTOGH, KUFRI, SANJAULI AND KELVIN GROVE UNDER GE(I) JUTOGH
2023_MES_617152_1
GE(I)/JUT-60 OF 2023-24
Open Tender
Civil Works
Item Rate
150 days
JUTOGH
CLASS E CATEGORY b (i)
7 documents required · 7 mandatory
₹500
GE (I) JUTOGH
₹50,000
Yes
28 Nov 2023
4 Sept 2023
4 Oct 2023
4 Sept 2023
2 Oct 2023
18 Sept 2023
4 Sept 2023 - 10 Sept 2023
Amount
Excavation in trenches n.exc 1.5 mtr wide and n.exc 1.5 mtr deep in loose/soft soil and getting out for underground cable/erection of poles, stays, trench etc complete all as specified and as directed.
Returning, filling in including spreading, leveling, watering and well ramming in layers n.exc 25 cm thick layers complete all as specified and directed.
Removal of excavated material n.exc 50 mtr away and depositing where directed at a level n.exc 1.5 mtr above from starting point complete all as specified and directed.
Supply, fixing or laying HDPE (DWC) tubing 100 mm dia as per IS:16205 part 24 fixing on poles, walls under floors, laying on surface etc as reqd at site including clamps to hold pipe at position complete all as specified and directed. Note: All items and accessories , bend, joints, nut bolts, clamps for wall fixing as per site requirement etc are incl in quoted rates.
Supply, fixing or laying HDPE (DWC) tubing 50 mm dia as per IS:16205 part 24 fixing on poles, walls under floors, laying on surface etc as reqd at site including clamps to hold pipe at position complete all as specified and directed. Note: All items and accessories , bend, joints, nut bolts, clamps for wall fixing as per site requirement etc are incl in quoted rates.
Disconnecting & taking out defective underground cable of any size and any type from trenches, pole, pipe, floor, wall etc complete all as specified and directed. Note: Old cable may different size and length and credit will be given as actual obtained from site.
Supply and laying, connecting and testing in replacement XLPE underground cable insulated, and overall sheathed with aluminium conductor heavy duty 1100 volts grade 400 sqmm single core laid in trenches/ on poles/ road crossing or passing through existing/new pipe under road crossing, clamping on wall etc. Note: (i) Earth work, removing, returning filling and pipe will be measured and paid separately. (ii) Cost of laying electrical cable through new/existing pipe under road, buildings, railway tracks, highways are incl in the quoted rates. (iii) All equipments, machinery or tools if required for laying electrical cable through new/existing pipes are provided by the contractor without any extra cost.
All as per Srl item No 7.00 above but for 3.5 core 240 Sqmm, complete all as specified and directed.
All as per Srl item No 7.00 above but for 3.5 core 185 Sqmm complete all as specified and directed.
All as per Srl item No 7.00 above but for 3.5 core 150 Sqmm, complete all as specified and directed.
All as per Srl item No 7.00 above but for 3.5 core 95 Sqmm, complete all as specified and directed.
All as per Srl item No 7.00 above but for 3.5 core 35 Sqmm, complete all as specified and directed.
All as per Srl item No 7.00 above but for 4 core 25 Sqmm, complete all as specified and directed.
All as per Srl item No 7.00 above but for 2 core 6 Sqmm, complete all as specified and directed.
Supply, installation, testing and commissioning of outdoor type cubical LT panel in replacement of size not less than 2.0 m x 2.0 m x 0.6 m with outer shell made out of 3.15 mm thick MS sheet and MS angle section 50 x 50 x 5mm on PCC 1:2:4 type B-2 platform 60cm above the ground level and 45cm below the ground level, factory fabricated with front openable , lockable, having pad lock arrangement , louvers and air vent, gasket ‘u’ type for natural flow of air, complete dust & vermin proof suitable for 3 phase 4 wire 415 volt 50 Hz factor fabricated ( Factory approved from CPRI) having modern fabrication followed by powder coated painting having thickness not less than 100 microns TPN aluminum bus bar 600 Amps insulated with colour coded heat shrinkable and shall be mounted on suitable size ‘F’ class insulators, marking connection with aluminum strip conductor of and general construction to IS-8623 of 1993 comprising of the following:-
INCOMING:-
MCCB FP 400A, Adj Thermal Fixed Magnetic release, 50 Hz, 415 Volts, 35 KA Main- 01No
OUTGOING:-
MCCB FP 250A, Adj Thermal Fixed Magnetic release, 50 Hz, 415 Volts, 25 KA- 02 Nos (EME SRI & Spare)
MCCB FP 100A, Adj Thermal Fixed Magnetic release, 50 Hz, 415 Volts, 16KA 02 Nos (F.No 17& ASC office)
MCCB FP 63A, Adj Thermal Fixed Magnetic release, 50 Hz, 415 Volts, 16KA 02Nos (F.No 3 & Guest Room)
Indicator lamps RYB with control fuses- 01 set (set of three)
Digital Multifunction meterwith Amps range (0-400) Amps & Voltage range (0-500) volt flush mounting type 4"X4" square dial with CTs of ratio 200/5- 01 No.
Supply, installation, testing and commissioning of outdoor type cubical LT panel in replacement of size not less than 1.5 m x 1.5 m x 0.6 m with outer shell made out of 3.15 mm thick MS sheet and MS angle section 50 x 50 x 5mm on PCC 1:2:4 type B-2 platform 60cm above the ground level and 45cm below the ground level, factory fabricated with front openable , lockable, having pad lock arrangement , louvers and air vent, gasket ‘u’ type for natural flow of air, complete dust & vermin proof suitable for 3 phase 4 wire 415 volt 50 Hz factor fabricated ( Factory approved from CPRI) having modern fabrication followed by powder coated painting having thickness not less than 100 microns TPN aluminum bus bar 400 Amps insulated with colour coded heat shrinkable and shall be mounted on suitable size ‘F’ class insulators, marking connection with aluminum strip conductor of and general construction to IS-8623 of 1993 comprising of the following:-
INCOMING:-
MCCB FP 250A, Adj Thermal Fixed Magnetic release, 50 Hz, 415 Volts, 25 KA Main- 01No
OUTGOING:-
MCCB FP 100A, Adj Thermal Fixed Magnetic release, 50 Hz, 415 Volts, 16KA- 01Nos (ECHS)
MCCB FP 63A, Adj Thermal Fixed Magnetic release, 50 Hz, 415 Volts, 16KA 02Nos (ETP & Qtrs)
MCB DP 63A, 50 Hz, 415 Volts, 16KA 07 Nos (Type 3 & 2 qtrs)
Indicator lamps RYB with control fuses- 01 set (set of three)
Digital Multifunction meterwith Amps range (0-200) Amps & Voltage range (0-500) volt flush mounting type 4"X4" square dial with CTs of ratio 200/5- 01 No.
Supply, installation, testing and commissioning of outdoor type cubical LT panel in replacement of size not less than 1.5 m x 1.5 m x 0.6 m with outer shell made out of 3.15 mm thick MS sheet and MS angle section 50 x 50 x 5mm on PCC 1:2:4 type B-2 platform 60cm above the ground level and 45cm below the ground level, factory fabricated with front openable , lockable, having pad lock arrangement , louvers and air vent, gasket ‘u’ type for natural flow of air, complete dust & vermin proof suitable for 3 phase 4 wire 415 volt 50 Hz factor fabricated ( Factory approved from CPRI) having modern fabrication followed by powder coated painting having thickness not less than 100 microns TPN aluminum bus bar 400 Amps insulated with colour coded heat shrinkable and shall be mounted on suitable size ‘F’ class insulators, marking connection with aluminum strip conductor of and general construction to IS-8623 of 1993 comprising of the following:-
INCOMING:-
MCCB FP 250A, Adj Thermal Fixed Magnetic release, 50 Hz, 415 Volts, 25KA Main- 01 No
OUTGOING:-
MCCB FP 160A, Adj Thermal Fixed Magnetic release, 50 Hz, 415 Volts, 25KA- 02 Nos
MCCB FP 63A, Adj Thermal Fixed Magnetic release, 50 Hz, 415 Volts, 16KA 02 Nos
Indicator lamps RYB with control fuses- 01 set (set of three)
Digital Multifunction meterwith Amps range (0-250) Amps & Voltage range (0-500) volt flush mounting type 4"X4" square dial with CTs of ratio 200/5- 01 No.
Supply, installation, testing and commissioning of outdoor type cubical LT panel in replacement of size not less than 1.5 m x 1.50 m x 0.6 m with outer shell made out of 3.15 mm thick MS sheet and MS angle section 50 x 50 x 5mm on PCC 1:2:4 type B-2 platform 60cm above the ground level and 45cm below the ground level, factory fabricated with front openable , lockable, having pad lock arrangement , louvers and air vent, gasket ‘u’ type for natural flow of air, complete dust & vermin proof suitable for 3 phase 4 wire 415 volt 50 Hz factor fabricated ( Factory approved from CPRI) having modern fabrication followed by powder coated painting having thickness not less than 100 microns TPN aluminum bus bar 300 Amps insulated with colour coded heat shrinkable and shall be mounted on suitable size ‘F’ class insulators, marking connection with aluminum strip conductor of and general construction to IS-8623 of 1993 comprising of the following:-
INCOMING:-
MCCB FP 160A, Adj Thermal Fixed Magnetic release, 50 Hz, 415 Volts, 25KA Main- 01 Nos (OQ31)
OUTGOING:-
MCCB FP 100A, Adj Thermal Fixed Magnetic release, 50 Hz, 415 Volts, 16KA- 02 Nos
Indicator lamps RYB with control fuses- 01 set (set of three)
Digital Multifunction meterwith Amps range (0-200) Amps & Voltage range (0-500) volt flush mounting type 4"X4" square dial with CTs of ratio 200/5- 01 No.
Supply, installation, commissioning in replacement of Busbar panel outdoor Step Type Design of size not less than 1.0x1.0x.6m with DMC insulators locking arrangement MS sheet covering 3.15 mm thick pedestal mounted vermin and weatherproof including four legs of 60 cm long of angle iron 40x40x5mm, front openable door having canopy for protection all surfaces painted with powder coated painting, embedding and including 400 Amp rated aluminium bus bars 4 Nos duly drilled for making connection with nut bolts of suitable size with colour code tape complete with PCC 1:3:6, type C-1, using 20 mm graded crushed stone aggregate for foundation for legs and dry 63mm aggregate of 75mm thickness around the panel after make good electrical connection as specified by EIC. Note: The rate are included with thimbles lugs, nut bolts,PCC foundation and aggregate.
M&L for earthing complete with galvanised steel earth plate electrode 600 x 600 x 6.0 mm thick burried directly in gorund (earth pit not less than 2.25 Mtr normal ground level),and top edge of earth plate not less than 1.5 mtr below normal ground level, using galvanised iron strip 32×6mm with bolts, nuts & check nuts, and washers of galvanised iron protection pipe light grade of 40 mm dia and watering pipe medium grade of 20 mm dia and filled with alternate layer of charcoal and common salt, watering funnel with wire mesh, earth pit chamber and cover CI frame PCC 1:3:6 type C-2 all as shown in electrical plate No-3 of SSR part-I of 2009 connected to earthing test point, including all earth work excavation, returning filling and disposal of surplus soil and testing on completion complete all as specified and directed.
All as per Srl item No 20.00 above but for copper plate 60×60cm ×3.15mm thick electrode and 20×3mm copper strip as earthing lead, complete all as specified and directed.
S&F in replacement earth continuity conductor or main earthing lead fixed to wall on batten or recess or chases or buried in ground or drawn in conduit/pipe or fixed to poles or any other indicated situation for loop earthing etc. as required 20x3mm copper strip complete all as specified and directed.
S&F in replacement for GI wire dia 4mm complete all as specified and directed
S&F in replacement ACB 4 Pole, 415 V, Manual Drawout type of capacity 630 Amps, Icu =50KA, Ics= 100% Icu rated short time withstand current for 1 sec Icw=50KA @ 415 Volts, disconnection time 23-32ms, horizontal/vertical type with to protect the electric circuit against the dangers such as overload shortcircuit incl complete accessories and connection with setting of tripping parameters incl dismantiling and taking down old unserviceable ACB complete all as specified and directed.
S&F in replacement off load changeover Switch (4 Pole) 630A with SS enclosure having four legs of angle iron frame 40x40x5mm 60cm long, complete all as specified and directed.
S&F in replacement off load changeover Switch (4 Pole) 400A with SS enclosure having four legs of angle iron frame 40x40x5mm 60cm long, complete all as specified and directed.
S&F cable jointing kit for 1.1 KV grade cable for outdoor termination , heat shrink type, joint complete with jointing material and accessories suitable for 3 ½ / 4 core XLPE, armoured, Al conductor cable of size 4-16 sqmm, complete all as specified and directed.
S&F cable jointing kit for 1.1 KV grade cable for outdoor termination , heat shrink type, joint complete with jointing material and accessories suitable for 3 ½ / 4 core XLPE, armoured, Al conductor cable of size 25-50 sqmm, complete all as specified and directed.
S&F cable jointing kit for 1.1 KV grade cable for outdoor termination , heat shrink type, joint complete with jointing material and accessories suitable for 3 ½ / 4 core XLPE, armoured, Al conductor cable of size 70-150 sqmm, complete all as specified and directed.
S&F cable jointing kit for 1.1 KV grade cable for outdoor termination , heat shrink type, joint complete with jointing material and accessories suitable for 3 ½ / 4 core XLPE, armoured, Al conductor cable of size 185-300 sqmm, complete all as specified and directed.
S&F cable jointing kit for 1.1 KV grade cable for outdoor termination , heat shrink type, joint complete with jointing material and accessories suitable for 3 ½ / 4 core XLPE, armoured, Al conductor cable of size 400 sqmm, complete all as specified and directed.
M&L for replacement of cable jointing kit for 1.1 KV grade cable for outdoor straight through , heat shrink type, joint complete with jointing material and accessories suitable for 3 ½ / 4 core XLPE, armoured, Al conductor cable of size 25-50 sqmm, complete all as specified and directed.
M&L for replacement of cable jointing kit for 1.1 KV grade cable for outdoor straight through , heat shrink type, joint complete with jointing material and accessories suitable for 3 ½ / 4 core XLPE, armoured, Al conductor cable of size 70-150 sqmm, complete all as specified and directed.
M&L for replacement MCCB 4 Pole, 415 V, Adjustable type, 630 Amps with breaking capacity 36 KA, complete all as specified and directed.
All as per Srl item No 34.00 above but for size 400A, complete all as specified and directed.
All as per Srl item No 34.00 above but for size 250A, with breaking capacity 25 KA, complete all as specified and directed.
All as per Srl item No 34.00 above but for size 200A, with breaking capacity 25 KA,complete all as specified and directed.
All as per Srl item No 34.00 above but for size 160A, with breaking capacity 25 KA, complete all as specified and directed.
All as per Srl item No 34.00 above but for size 125A, with breaking capacity 16 KA, complete all as specified and directed.
All as per Srl item No 34.00 above but for size 100A, with breaking capacity 16 KA, complete all as specified and directed.
All as per Srl item No 34.00 above but for size 63A, with breaking capacity 16 KA, complete all as specified and directed.
M&L for replacement CT of ratio 800/5 Amp including wiring and calibration with ammeter, complete all as specified and directed.
M&L for replacement CT of ratio 400/5 Amp including wiring and calibration with ammeter, complete all as specified and directed.
M&L for replacement CT of ratio 200/5 Amp including wiring and calibration with ammeter, complete all as specified and directed.
Supplying and laying in replacement synthetic Rubber insulated mats 2 mm thick for voltage upto 3.3 kv for electrical purpose as per IS 15652-2006, (superseding IS 5424) suitable for electrical shock safety of sizes 2m x 1m, complete all as specified and directed.
Restreching existing ACSR conductor on LT pole and binding conductor on insulator properly using new binding wire/jumper wire complte all as specified and directed.
M&L for replacement for PVC line seperator flat type 3 Phase 4/5 wire LT conductor with nut bolt fiited set, complete all as specified and directed.
M&L for 75 mm thick, PCC 1:4:8, type D-2, using 40 mm graded crushed stone aggregate as in path, paving etc finished even and smooth using extra cement, complete all as specified and directed.
Alpha Engineers and Builders
stage.html
html • 0.04 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .