Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹1.9 CrAdmitted-Finance | ₹1.9 Cr | L1 | Admitted-Finance |
| 2 | L2₹2.1 CrAdmitted-Finance | ₹2.1 Cr | L2 | Admitted-Finance |
| 3 | L3₹2.2 CrAdmitted-Finance | ₹2.2 Cr | L3 | Admitted-Finance |
| 4 | L4₹2.2 CrAdmitted-Finance | ₹2.2 Cr | L4 | Admitted-Finance |
| 5 | L5₹2.2 CrAdmitted-Finance | ₹2.2 Cr | L5 | Admitted-Finance |
| Sl No | Description | Qty | Unit | The Trikuta Engineer L7 | SNS TECHNOLOGIES L9 | M/s Rahul Road and Highway Constr. Co L6 | M/S COMBINE GROUP OF ENGINEERS L3 | CEEKAY EPC PROJECTS PRIVATE LIMITED L12 | FABRICO INDIA PRIVATE LIMITED L13 | M/S A G ELECTRICALS L1 | INDUSTRIAL ELECTRICALS L10 | M/s R.S CONSTRUCTIONS L8 | VEENA CONSTRUCTION CO. L2 | GUARDIAN ENGINEERS L5 | M/S RATHER CONSTRUCTIONS AND TRADERS L4 | Power Control Systems L11 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 1.00Creation of 11/0.415 KV, 630KVA (9 Nos) Distribution Sub Station for E-Buses Charging Port at Bhagwati Nagar | ||||||||||||||||
| 1.01 | Supply, Installation & commissioning of 630 kVA Distribution Transformer (DT) out door type equipped with an On-Load Tap Changer (OLTC) is designed for EV Charging applications, providing automatic voltage regulation without interrupting the power supply. These units typically feature copper windings, CRGO silicon steel cores, and operate using ONAN (Oil Natural Air Natural) cooling.
Key Specifications for 630 kVA OLTC Transformers
Capacity: 630 kVA (Three-phase)
Voltage Ratio: 11 kV/415 V
OLTC Range: Typically +5% to -15% in 1.25% steps
Vector Group: Usually Dyn11
Impedance: Approximately 4.5% to 6%
Cooling: ONAN (Oil Natural Air Natural)
Standards: IS 1180 / IS 2026 / IEC 60076
Losses: Designed with low no-load and load losses (To be submitted during detailed Engineering )
OLTC and Connection Features
Function: The OLTC regulates output voltage, compensating for input fluctuations to maintain a stable 415V output.
Motor Drive Unit (MDU): Operates under load via an Automated Voltage Regulator (AVR).
Installation: Suitable for outdoor, plinth-mounted applications, featuring robust porcelain bushings.
Protection: Includes Buchholz relay, pressure relief device, and silica gel breather for safety. | 9 | No | 15,75,000 ₹1.4 Cr | 17,60,000 ₹1.6 Cr | 14,50,000 ₹1.3 Cr | 14,90,000 ₹1.3 Cr | 20,80,000 ₹1.9 Cr | 18,25,165 ₹1.6 Cr | 12,60,000 ₹1.1 Cr | 18,00,000 ₹1.6 Cr | 15,00,000 ₹1.4 Cr | 17,00,000 ₹1.5 Cr | 16,75,000 ₹1.5 Cr | 17,00,000 ₹1.5 Cr | 17,25,000 ₹1.6 Cr |
| 1.02 | LT Distribution box with components of 630 kVA LT DB Main MCCB: 1000A, 3P/4P, 50kA/70kA breaking capacity.Outgoing Feeders: Multiple MCCBs for 2 feeders of 400A or 630A).Busbar: Aluminum /Copper , capacity \(>1000A\).Cable Glands: Suitable for \(3\frac{1}{2}\) core XLPE Aluminum cables. | 9 | No | 90,000 ₹8.1 L | 1,90,000 ₹17.1 L | 4,60,000 ₹41.4 L | 2,25,000 ₹20.3 L | 60,000 ₹5.4 L | 1,25,523 ₹11.3 L | 63,000 ₹5.7 L | 1,20,000 ₹10.8 L | 1,50,000 ₹13.5 L | 55,000 ₹5.0 L | 80,000 ₹7.2 L | 75,000 ₹6.8 L | 1,75,000 ₹15.8 L |
| 1.03 | Supply & Fixing of Gapless Surge Arrestor,9 kV ,10 kA ,LA with polymer housing, Stn. Type | 9 | Set | 2,500 ₹22,500 | 4,500 ₹40,500 | 3,500 ₹31,500 | 15,000 ₹1.4 L | 3,450 ₹31,050 | 5,835 ₹52,515 | 9,000 ₹81,000 | 7,000 ₹63,000 | 10,000 ₹90,000 | 3,500 ₹31,500 | 7,000 ₹63,000 | 8,000 ₹72,000 | 6,000 ₹54,000 |
| 1.04 | Supply, Installation, Testing & Commissioning of 11kV GO, AB Switch 3-Phase, 3-Pole, 200 Amp, Vertical Type | 9 | Set | 10,000 ₹90,000 | 9,000 ₹81,000 | 30,000 ₹2.7 L | 22,000 ₹2.0 L | 7,000 ₹63,000 | 11,942 ₹1.1 L | 9,000 ₹81,000 | 8,000 ₹72,000 | 10,000 ₹90,000 | 8,000 ₹72,000 | 10,000 ₹90,000 | 9,000 ₹81,000 | 8,000 ₹72,000 |
| 1.05 | Supply, Installation, Testing & Commissioning of 11 kV Horn Gap Fuse Set 3 Phase 200A | 9 | Set | 2,500 ₹22,500 | 4,500 ₹40,500 | 2,000 ₹18,000 | 18,000 ₹1.6 L | 3,500 ₹31,500 | 5,292 ₹47,628 | 9,000 ₹81,000 | 3,500 ₹31,500 | 5,000 ₹45,000 | 3,500 ₹31,500 | 4,000 ₹36,000 | 4,000 ₹36,000 | 5,000 ₹45,000 |
| 1.06 | Providing & Fixing of 400mm2 (2Ckt) cable, 1.1 KV Grade, PVC Insulated Stranded Conductor FRLS Type. | 792 | Mtr | 725 ₹5.7 L | 750 ₹5.9 L | 350 ₹2.8 L | 630 ₹5.0 L | 500 ₹4.0 L | 1,561 ₹12.4 L | 900 ₹7.1 L | 700 ₹5.5 L | 600 ₹4.8 L | 700 ₹5.5 L | 600 ₹4.8 L | 600 ₹4.8 L | 400 ₹3.2 L |
| 1.07 | Providing of 9Mtr Long Pole , ST-410 SP33 | 18 | No | 16,400 ₹3.0 L | 14,000 ₹2.5 L | 4,000 ₹72,000 | 12,000 ₹2.2 L | 17,000 ₹3.1 L | 19,345 ₹3.5 L | 18,000 ₹3.2 L | 17,000 ₹3.1 L | 20,000 ₹3.6 L | 15,500 ₹2.8 L | 15,500 ₹2.8 L | 16,000 ₹2.9 L | 16,000 ₹2.9 L |
| 1.08 | Providing & Fixing of 11kV Polymeric composite Disc Insulator 12kV with Fitting ,min failing load 45kN, Lighting Impulse 75kV Positive and 80kV Negative, creepage distance 320mm | 27 | No | 300 ₹8,100 | 400 ₹10,800 | 200 ₹5,400 | 320 ₹8,640 | 500 ₹13,500 | 217 ₹5,859 | 450 ₹12,150 | 250 ₹6,750 | 200 ₹5,400 | 400 ₹10,800 | 650 ₹17,550 | 600 ₹16,200 | 800 ₹21,600 |
| 1.09 | Providing of GI Channel/angle/Flat of sizes including clamps | 1,350 | Kgs | 130 ₹1.8 L | 150 ₹2.0 L | 15 ₹20,250 | 100 ₹1.4 L | 90 ₹1.2 L | 116 ₹1.6 L | 117 ₹1.6 L | 135 ₹1.8 L | 100 ₹1.4 L | 120 ₹1.6 L | 125 ₹1.7 L | 120 ₹1.6 L | 125 ₹1.7 L |
Updated dates
Tender Value
Refer Docs
EMD Value
₹5.6 L
Closing Date
11 Mar 2026, 2:00 pmClosed
Executive Engineer ED-III
Office of Executive Engineer ED-III, Bhagwati Nagar
Construction of downstream network for EBuses Charging Port comprising of substations 9x 630 KVA 11 0.4KV and associated HTLT network at Bhagwati Nagar falling under the jurisdiction of Electric Sub Division Canal JPDCL Jammu on turnkey basis
2026_PDD_302845_1
ED-III/Jammu/57 of 2025-26
Open Tender
Electrical Works
90 days
Jurisdiction Of Electric SD Canal
Please refer Tender documents.
7 documents required · 7 mandatory
₹5,000
Executive Engineer ED-III
₹5.6 L
Office of Executive Engineer ED-III
21 May 2026
11 Feb 2026
12 Mar 2026
11 Feb 2026
11 Mar 2026
11 Feb 2026
13 Feb 2026
Supply, Installation & commissioning of 630 kVA Distribution Transformer (DT) out door type equipped with an On-Load Tap Changer (OLTC) is designed for EV Charging applications, providing automatic voltage regulation without interrupting the power supply. These units typically feature copper windings, CRGO silicon steel cores, and operate using ONAN (Oil Natural Air Natural) cooling. Key Specifications for 630 kVA OLTC Transformers Capacity: 630 kVA (Three-phase) Voltage Ratio: 11 kV/415 V OLTC Range: Typically +5% to -15% in 1.25% steps Vector Group: Usually Dyn11 Impedance: Approximately 4.5% to 6% Cooling: ONAN (Oil Natural Air Natural) Standards: IS 1180 / IS 2026 / IEC 60076 Losses: Designed with low no-load and load losses (To be submitted during detailed Engineering ) OLTC and Connection Features Function: The OLTC regulates output voltage, compensating for input fluctuations to maintain a stable 415V output. Motor Drive Unit (MDU): Operates under load via an Automated Voltage Regulator (AVR). Installation: Suitable for outdoor, plinth-mounted applications, featuring robust porcelain bushings. Protection: Includes Buchholz relay, pressure relief device, and silica gel breather for safety.
Supply & Fixing of Gapless Surge Arrestor,9 kV ,10 kA ,LA with polymer housing, Stn. Type
Supply, Installation, Testing & Commissioning of 11 kV Horn Gap Fuse Set 3 Phase 200A
Providing of 9Mtr Long Pole , ST-410 SP33
Providing of GI Channel/angle/Flat of sizes including clamps
Providing of Earthing of substation --Excavation of earth pit of dia 650 mm & depth 3000 mm, installation of Earthing pipe of 40 mm Nominal bore & 4mm wall thickness & length 2.5 mtr long as Per IS 1239.GI Strip for neutral earthing of size 25 mm x 3 mm for connection of transformer body,G.O Set & lightening arrestor as per IS 2629/85, GI nuts & bolts,refilled with earth enhancement materials and earth Chamber made of brick masonary with RCC slab cover.
Providing & Fixing of Galvanised Stay Set with 50 x 8 mm Stay Clamp, Guy Insulator (2 Nos), Anchoring Plate (200 x 200 x 6 mm), Nut & Bolts, 2 No Turn Buckle, 1.8m long, 16 mm diameter solid Stay Rod & 7/3.15 mm dia stranded wire complete
Providing & Fixing of Danger Plates with Clamps
Providing of Cement bottoming 1:2:4 mix as per REC standards 0.4 cum/pole
Painting Of Poles Aluminium Paint
RCC Platform/ Bed for placing the transformer for 630 KVA Transformer as per approved design including GI mesh fencing of 6 feet height complete job (Design to be finalized during detailed Engineering )
Sundry items like Aluminuim Lugs, Jumpers, Binding tape
Steel Tubular Pole 9.0 Mtr long (ST-410 SP-33) including excavation of pit and back filling of soil & consolidating by ramming, watering etc.
11 kV Ring Main Unit (RMU) is a compact, SF6 gas-insulated or solid-dielectric switchgear designed for indoor/outdoor secondary distribution networks (11 kV, 3-phase, 50 Hz). It typically features 630A Load Break Switches (LBS) for incoming/outgoing lines and 200A/630A Vacuum Circuit Breakers (VCB) with protection relays for transformer feeders.
GI Channel,Angle and flat iron
11kv outdore heat shrinkable cable termination kit 185mm2
Galvanized Nuts and Bolts
Anti-Climbing Device with clamps
Red Oxide
Cement bottoming 1:2:4 mix as per REC Standard .45 cum/ pole
Galvanised Stay Set with 50 x 8 mm Stay Clamp, Guy Insulator (2 Nos), Anchoring Plate (200 x 200 x 6 mm), Nut & Bolts, 2 No Turn Buckle, 1.8m long, 16 mm diameter solid GS Stay Rod & 7/3.15 mm dia GI stranded wire complete
Minor land development works such as Bush cutting , Earth filling etc at site to be made available by JSCL (Jammu Smart City Limited)
# of occurrences
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Tendernotice_1.pdf
PDF • 2.23 MB
Tendernotice_2.pdf
PDF • 1.42 MB
BOQ_982950.xls
BOQ • 0.32 MB
STRFor630KVADistributionSubstaionwithAVR.pdf
Tender Documents • 0.26 MB
GuaranteedTechnicalRequirements.pdf
Tender Documents • 11.04 MB
Download all tender documents and submit your bid