Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹18.3 LAccepted-AOC | L1 | Accepted-AOC Being a first lowest | |
| 2 | L2₹21.0 L+₹2.8 L (15.1%)Rejected-Finance | L2 | Rejected-Finance Being not lowest | |
| 3 | L3₹21.2 L+₹2.9 L (15.8%)Rejected-Finance 99 MODEL TOWN PATHANKOT 145001 | PATHANKOT | PATHANKOT | PUNJAB | 145001 | L3 | Rejected-Finance Being not lowest | |
| 4 | L4₹23.4 L+₹5.1 L (28.1%)Rejected-Finance BYE PASS DALHOUSIE ROAD PATHANKOT 145001 PB | PATHANKOT | PATHANKOT | PUNJAB | 145001 | L4 | Rejected-Finance Being not lowest | |
| 5 | L5₹24.8 L+₹6.5 L (35.7%)Rejected-Finance H NO 07 SHIVAJI NAGAR PATHANKOT 145001 | PATHANKOT | PATHANKOT | PUNJAB | 145001 | L5 | Rejected-Finance Being not lowest |
Tender Value
Refer Docs
EMD Value
₹70,000
Closing Date
20 Feb 2024, 6:00 pmClosed
GE(W)Pathankot
GE(W)Pathankot
REPAIR REPLACEMENT IMPROVEMENT OF LT FEEDER PILLAR PANELS/CAPACITOR PANELS, MCCB AND ALLIED WORKS UNDER GE(WEST) PATHANKOT
2024_MES_638572_1
GE/PKT-67/2023-24
Open Tender
Miscellaneous Works
Item Rate
270 days
Pathankot
As per tender and NIT doc
9 documents required · 9 mandatory
₹500
GE(W)Pathankot
₹70,000
19 Mar 2024
22 Jan 2024
22 Feb 2024
22 Jan 2024
20 Feb 2024
6 Feb 2024
Amount
Supply, installation, testing & commissioning in replacement of factory made (CPRI test certified manufacturer) LT feeder pillar box of suitable size outdoor type double door, cubical compartmentalized type suitable for 415 volts supply system all as specified and directed having busbar chamber with insulated aluminium busbar 400 Amps rating (100% neutral) installed on porcelain insulators. The panel shall be dust and vermin proof made of 3mm (outer) & 2mm (inner) compartment door CRCA sheet duly powder coated with 7 tank process panel mounted on angle iron 40x40x6mm frame having 4 Nos legs 45 cm long of 40x40x6mm angle iron, included 15 cm grouted in PCC 1:2:4 type B-1 and 30cm clear space from ground level. Front and back opening type with aprons for cable entry with locking arrangement including internal wiring with PVC insulated multistranded copper conductor cable of suitable size and cable entry boxes with cable glands. The scope of the work also includes supply and fixing the following:-
Supply, installation, testing & commissioning in replacement of factory made (CPRI test certified manufacturer) LT feeder pillar box of suitable size outdoor type double door, cubical compartmentalized type suitable for 415 volts supply system all as specified and directed having busbar chamber with insulated aluminium busbar 800 Amps rating (100% neutral) installed on porcelain insulators. The panel shall be dust and vermin proof made of 3mm (outer) & 2mm (inner) compartment door CRCA sheet duly powder coated with 7 tank process panel mounted on angle iron 40x40x6mm frame having 4 Nos legs 45 cm long of 40x40x6mm angle iron, included 15 cm grouted in PCC 1:2:4 type B-1 and 30cm clear space from ground level. Front and back opening type with aprons for cable entry with locking arrangement including internal wiring with PVC insulated multistranded copper conductor cable of suitable size and cable entry boxes with cable glands. The scope of the work also includes supply and fixing the following:-
Supply, installation commissioning & testing in replacement of CPRI approved bus bar chamber of size 600mmx400mmx250mm made up of MS sheet 3.15mm powder quoted with 7 tank process with RAL 7032 code (siemens grey) and aluminium strip of capacity 400 Amps - 04 Nos (300mm long) with 250Amps, 36 KA, 4 pole MCCB having adjustable thermal adjustable magnetic release, ICS=ICU=100% conforming to IEC 60947 alongwith spreaded link for connection and mounted on angle iron 40x40x6mm having 4 Nos legs, length 45cm long, 15cm grouted in PCC 1:2:4 type B-1 including incoming and outgoing connection complete all as specified and as directed.
Supply, installation commissioning & testing in replacement of CPRI approved bus bar chamber of size 600mmx400mmx250mm made up of MS sheet 3.15mm powder quoted with 7 tank process with RAL 7032 code (siemens grey) and aluminium strip of capacity 300 Amps - 04 Nos (300mm long) with 200Amps, 36 KA, 4 pole MCCB having adjustable thermal adjustable magnetic release, ICS=ICU=100% conforming to IEC 60947 alongwith spreaded link for connection and mounted on angle iron 40x40x6mm having 4 Nos legs, length 45cm long, 15cm grouted in PCC 1:2:4 type B-1 including incoming and outgoing connection complete all as specified and as directed. Note:-Drawing for item No. 01 to 04 (panel & chamber) should be got approved from GE by contractor before placing the order.
S&F in replacement MCCB 630 Amps, 50 KA rupturing capacity, ICS=100% ICU, 4 Pole, 415 volts, 50 Hz, Adjustable thermal adjustable magnetic release including spreaders, thimbling carrying out modification in existing panel to MCCB complete all as specified and as directed.
S&F in replacement MCCB 400 Amps, 50 KA rupturing capacity, ICS=100% ICU, 4 Pole, 415 volts, 50 Hz, Adjustable thermal adjustable magnetic release including spreaders, thimbling carrying out modification in existing panel to MCCB complete all as specified and as directed.
S&F in replacement MCCB 250 Amps, 360 KA rupturing capacity, ICS=100% ICU, 4 Pole, 415 volts, 50 Hz, Adjustable thermal adjustable magnetic release including spreaders, thimbling carrying out modification in existing panel to MCCB complete all as specified and as directed.
S&F in replacement MCCB 200 Amps, 36 KA rupturing capacity, ICS=100% ICU, 4 Pole, 415 volts, 50 Hz, Adjustable thermal adjustable magnetic release including spreaders, thimbling carrying out modification in existing panel to MCCB complete all as specified and as directed.
S&F in replacement MCCB 160 Amps, 27 KA rupturing capacity, ICS=100% ICU, 4 Pole, 415 volts, 50 Hz, Adjustable thermal adjustable magnetic release including spreaders, thimbling carrying out modification in existing panel to MCCB complete all as specified and as directed.
S&F in replacement MCCB 125 Amps, 27 KA rupturing capacity, ICS=100% ICU, 4 Pole, 415 volts, 50 Hz, Adjustable thermal adjustable magnetic release including spreaders, thimbling carrying out modification in existing panel to MCCB complete all as specified and as directed.
S&F in replacement MCCB 100 Amps, 16 KA rupturing capacity, ICS=100% ICU, 4 Pole, 415 volts, 50 Hz, Adjustable thermal adjustable magnetic release including spreaders, thimbling carrying out modification in existing panel to MCCB complete all as specified and as directed.
S&F in replacement MCCB 63 Amps, 16 KA rupturing capacity, ICS=100% ICU, 4 Pole, 415 volts, 50 Hz, Adjustable thermal adjustable magnetic release including spreaders, thimbling carrying out modification in existing panel to MCCB complete all as specified and as directed.
M&L for cleaning/cutting the grass/tree/bushes around LT panel upto 2 mtr and painting with two coats of synthetic enamel paint to LT panel complete all as specified and as directed.
M&L for welding of existing LT panel broken door with heavy duty hings with the help of welding machine/ welding rod and fixing of sliding bolt complete all as specified and as directed.
M&L for disconnecting of incoming and outgoing un-insulated LT UG cable any type from MCCB's as per existing panel and cutting the un-insulated cable and thimbling for connection with the help of crimping tool including any other repair like tighting of bus bar, nut bolts, replacement of damaged insulator and any minor repair to make LT panel/ LT bus bar servicable deemed inclusive in the quoted rate complete all as specified and as directed by Engg-in-charge.
S&F in repair aluminium thimble of size 25 Sqmm after cutting peeling of LT cable complete all as specified and as directed.
S&F in repair aluminium thimble of size 35 Sqmm after cutting peeling of LT cable complete all as specified and as directed.
S&F in repair aluminium thimble of size 50 Sqmm after cutting peeling of LT cable complete all as specified and as directed.
S&F in repair aluminium thimble of size 70 Sqmm after cutting peeling of LT cable complete all as specified and as directed.
S&F in repair aluminium thimble of size 95 Sqmm after cutting peeling of LT cable complete all as specified and as directed.
S&F in repair aluminium thimble of size 120 Sqmm after cutting peeling of LT cable complete all as specified and as directed.
S&F in repair aluminium thimble of size 150 Sqmm after cutting peeling of LT cable complete all as specified and as directed.
S&F in repair aluminium thimble of size 185 Sqmm after cutting peeling of LT cable complete all as specified and as directed.
S&F in repair aluminium thimble of size 240 Sqmm after cutting peeling of LT cable complete all as specified and as directed.
S&F in repair aluminium thimble of size 300 Sqmm after cutting peeling of LT cable complete all as specified and as directed.
S&F in repair aluminium thimble of size 400 Sqmm after cutting peeling of LT cable complete all as specified and as directed.
S&F in repair RYB phase indication LED lamp on LT panel including wiring where required complete all as specified and as directed.
S&F in repair digital voltmeter (0-500 Volt) for LT panel including wiring where required complete all as specified and as directed.
S&F in repair digital ammeter (0-800 Amps) for LT panel including wiring where required complete all as specified and as directed.
M&L for Earthing complete with galvanised steel earth plate eletrode 60xm x 60cm x6 mm thick buried directly in ground (earth pit not less than 2.25 metres deep below normal ground level) with top edge of plate not less than 1.5 meters below normal ground level, connecting to the Galvanised iron earth lead 32x6mm size, by means of bolts, nuts, check buts and washers of galvanised iron and earth lead protected by provision of GI medium grade pipe 40mm bore including provision of aggregates with 40mm thick cover of RCC (1;2:4) reinfored with XPM (weight not less than 4 Kg/Sqm) and frame of angle iron 25x25x6mm with 6mm dia MS bar handle made to shape, GI light grade 20mm bore pipe for watering of suitable length placed on top edge of earth plate, common salt and charcoal filling, with fixing arrangement, funnel, wire mesh and earth work in any type of soil, returning filling in distance not exceeding 50 mtr and removal of surlus soil complete all as per plate No 3 of SSR-2009 Part-I and connecting to existing earth test point all as specified or indicated including testing on completion.
Excavation in trenches not exceeding 1.5 m wide and not exceeding 1.5 m in depth and getting out in soft/loose soil for laying of cable, pole foundation, stay, laying of pipe etc complete all as specified and directed.
Returning filling including spreading, leveling, watering and well ramming in layers not exc 25 cm complete all as specified and directed.
Removing excavated soil to a distance not exceeding 50 mtr and deposting where directed at a level not exceeding 1.5 mtr above the starting point complete all as specified and directed.
M&L for sand cushioning to under ground cables with a layer of sand 8 cm before laying the cable and 15 cm after laying the cable punned down to 18 cm complete all as specified and directed. Note :- Punned thickness 18 cm shall be measured for payment.
M&L for Brick covering with width equal to length of brick as mechanical protection to cable with well burnt sub class 'B' bricks laid as directed.
Supply, laying, connecting and testing in replacement, LT XLPE insulated, screened, PVC bedded, galvanised steel strip or wire armoured, electric power cable (heavy duty) with aluminium conductor, 1100 volts, grade cross sectional area 300 sq. mm 3.5 core complete all as specified
Supply, laying, connecting and testing in replacement, LT XLPE insulated, screened, PVC bedded, galvanised steel strip or wire armoured, electric power cable (heavy duty) with aluminium conductor, 1100 volts, grade cross sectional area 185 sq. mm 3.5 core complete all as specified
Supply, laying, connecting and testing in replacement, LT XLPE insulated, screened, PVC bedded, galvanised steel strip or wire armoured, electric power cable (heavy duty) with aluminium conductor, 1100 volts, grade cross sectional area 95 sq. mm 3.5 core complete all as specified
Supply, laying, connecting and testing in replacement, LT XLPE insulated, screened, PVC bedded, galvanised steel strip or wire armoured, electric power cable (heavy duty) with aluminium conductor, 1100 volts, grade cross sectional area 70 sq. mm 3.5 core complete all as specified
Supply, laying, connecting and testing in replacement, LT XLPE insulated, screened, PVC bedded, galvanised steel strip or wire armoured, electric power cable (heavy duty) with aluminium conductor, 1100 volts, grade cross sectional area 50 sq. mm 3.5 core complete all as specified
Supply, laying, connecting and testing in replacement, LT XLPE insulated, screened, PVC bedded, galvanised steel strip or wire armoured, electric power cable (heavy duty) with aluminium conductor, 1100 volts, grade cross sectional area 25 sq. mm 3.5 core complete all as specified
Supply, laying, connecting and testing in replacement, LT XLPE insulated, screened, PVC bedded, galvanised steel strip or wire armoured, electric power cable (heavy duty) with aluminium conductor, 1100 volts, grade cross sectional area 16 sq. mm 4 core complete all as specified
S&F in replacement GI tubing light grade 100 mm bore for cable protection laid in trenches in road crossing or fixed to wall/Pole complete all as specified and directed.
S&F in replacement GI tubing light grade 80 mm bore for cable protection laid in trenches in road crossing or fixed to wall/Pole complete all as specified and directed.
S&F in replacement GI tubing light grade 50 mm bore for cable protection laid in trenches in road crossing or fixed to wall/Pole complete all as specified and directed.
S&F in replacement GI tubing light grade 40 mm bore for cable protection laid in trenches in road crossing or fixed to wall/Pole complete all as specified and directed.
M&L for cutting of existing road for laying of XLPE cable of any size including necessary excavation and earth work including repairing the same as per existing level with PCC 1:2:4 complete all as specified and as directed by Engg-in-charge.
S&F in repairs cable straight through joint 25 to 50 Sqmm 3.5 core XLPE 1.1KV LT Cable heat shrinkable, including jointing accessories and cutting of faulty cable complete including necessary excavation and earth work complete all as specified and directed by Engr-in-Charge.
S&F in repairs cable straight through joint 70 to 95 Sqmm 3.5 core XLPE 1.1KV LT Cable heat shrinkable, including jointing accessories and cutting of faulty cable complete including necessary excavation and earth work complete all as specified and directed by Engr-in-Charge.
S&F in repairs cable straight through joint 120 to 185 Sqmm 3.5 core XLPE 1.1KV LT Cable heat shrinkable, including jointing accessories and cutting of faulty cable complete including necessary excavation and earth work complete all as specified and directed by Engr-in-Charge.
S&F in repairs cable end termination joint 70 to 150 Sqmm 3.5 core XLPE 1.1KV LT Cable heat shrinkable indoor type including jointing accessories and cutting of faulty cable complete including necessary excavation and earth work complete all as specified and directed by Engr-in-Charge.
S&F in repairs cable end termination joint 185 to 300 Sqmm 3.5 core XLPE 1.1KV LT Cable heat shrinkable indoor type including jointing accessories and cutting of faulty cable complete including necessary excavation and earth work complete all as specified and directed by Engr-in-Charge.
Note:-The accepted amount will be arrived after deducting the Sch of credit i.e. Rs 1,05,284.00 and any other reduction if any from quoted amount.
JAI DURGA CONSTRUCTION CO
satpal and brothers
M/S GULATI ENGINEERING WORKS
M/S SHAKTI ELECTRIC WORKS
M/S CANTILEVER ENGINEERS
M/s. Aggarwal Engineers
dinesh enterprises
INDIA ELECTRIC WORKS
stage.html
html • 0.07 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .