CE/NCTPS-I
NCTPS-I Chennai-600120
ICHS Dn Renovation of the existing defective Air Ventilation System by modification renewal of wornout parts testing and commissioning of Air Ventilation System for Switch Gear I in ICHS control room
2022_EB_275264_1
CE/NCTPSI/SE-MIISpNo60/2022-23
Open Tender
Power/Energy Projects/Products
Works
120 days
EE/ICHS/NCTPS1
Please refer Tender documents.
3 documents required · 3 mandatory
₹0
₹47,600
Yes
15 Mar 2023
26 Dec 2022
10 Jan 2023
26 Dec 2022
9 Jan 2023
26 Dec 2022
Amount
Material Portion:Supply of single skin cabinet type belt driven DIDW backward curve fan assembly with all accessories including fan casing, impeller shaft, slide rail, VCD, canvass connection, common base frame, vibration isolator. Motor Capacity: 81000 CMH, Static pressure: 75MM WG. Motor Capacity: 30 KW/ 6P. Make: Kirloskar, Crompton, ABB or Equivalent. Fan Outlet velocity:9.69m/ Sec.
Supply of Inlet filter Box assembly including filter frame, pre filters and fine filter. A) Filter inlet box MS thick size 4mm x 4mm x 0.94m x 1.5m length. B) Filter of size 610 x 610 x 50mm width 20 micron filter
Supply of GI Duct connection including square duct, fan outlet duct with end flanges, GI common plenum duct with flanges 1200mm x 2200mm x 2400mm. GI Reducer duct fan outlet to plenum Duct 1360mm x 960mm. B) Round to square MS duct connection 0.94 x 0.94 x dis.0.94 x 50m length.
Supporting structures for fan assembly, fan and motor assembly and all ducting.
Labour Portion:Dismantling of the existing defective fan assembly with all accessories and shifting, lifting up to terrace, assembling the new fan assembly with all accessories including T&P and consumables and scrap devolution to store.
Dismantling of the existing damaged/ worn out inlet filter box assembly and assembling new inlet filter box assembly with pre filters and fine filters including T&P and consumables and scrap devolution to store.
Dismantling of the existing damaged/ worn out ducts and erection of common plenum duct with acoustic insulation and flanges including consumables and T&P and scrap devolution to store.
Dismantling of existing corroded/ damaged supporting structure and erect the new supporting structure including painting, consumables & T&P and scrap devolution to store.
Complete Cleaning of all air ducts with wire brush & air in the switch gear room, arresting of air leak in flange joints of entire duct cleaning and checking of existing 44 Nos of supply air grill testing and commissioning of Air ventilation system including consumables, T&P.
SUNIL ENTERPRISES
stage.html
html • 0.03 MB
tech_eval.pdf
boq_comp_chart.xlsx
xlsx
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .