| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹19.8 LAccepted-AOC AT ROAD MES TINALI PO CHABUA DISTT DIBRUGARH ASSAM 84 | CHABUA | DIBRUGARH | ASSAM | 786102 | L1 | Accepted-AOC Accepted being L1 | |
| 2 | L2₹24.2 L+₹4.4 L (22.3%)Rejected-Finance | L2 | Rejected-Finance Rejected being L2 | |
| 3 | L3₹24.6 L+₹4.8 L (24.2%)Rejected-Finance COLLEGE ROAD CHABUA PO CHABUA DIST DIBRUGARH ASSAM 786184 | DIBRUGARH | ASSAM | 786184 | L3 | Rejected-Finance Rejected being L3 | |
| 4 | L4₹25.5 L+₹5.7 L (28.8%)Rejected-Finance 1389 RADHETENAMENT SOCIETY SARDAR ROAD SURENDRANAGAR SURENDRA NAGAR GUJARAT 363001 | SURENDRANAGAR | GUJARAT | 363001 | L4 | Rejected-Finance Rejected being L4 | |
| 5 | L5₹25.6 L+₹5.8 L (29.4%)Rejected-Finance 7TH MILE UPPER SHILLONG P O NONGLYER SHILLONG 793009 MEGHALAYA | EAST KHASI HILLS | MEGHALAYA | 793009 | L5 | Rejected-Finance Rejected being L5 |
Tender Value
₹21 L
EMD Value
₹42,000
Closing Date
29 Jun 2022, 6:00 pmClosed
GE(AF) CHABUA
GE (AF) CHABUA, POST-CHABUA AIR FIELD, DIST-DIBRUGARH, ASSAM-786102
AMC FOR FIRE ALARM AND WIRELESS TEMPERATURE MONITORING SYSTEM AT VARIOUS LOCATIONS AT STN UNDER GE(AF) CHABUA
2022_MES_526972_1
390/E8
Open Tender
Electrical and Maintenance Works
Item Rate
330 days
GE(AF) CHABUA
Please refer Tender documents.
6 documents required · 6 mandatory
₹500
GE(AF) CHABUA
₹42,000
Yes
10 Aug 2022
27 May 2022
1 Jul 2022
27 May 2022
29 Jun 2022
22 Jun 2022
27 May 2022 - 3 Jun 2022
Amount
Comprehensive Service/Repair/maintenance and monthly visit for regular maintenance for the Automation of intelligent addressable fire alarm control panel and flowchart based programmable RTU at tech flight hanger, 102 SQN hanger, Logistic Hanger , BCR Building, AFNET site -2, and EE hall including checking testing and cleaning of Loop card ,Main board, LCD display, Printer Panel, AC filter, Transformer, Lead acid batteries, Inverter, Multisensor, sounder, MCP, Beam Detector, Repeater Panel, Zone monitor Module, UV&IR detector, Remote Response indicator, Loop Isolator, Amplifier and Loud speakers carrying out normal repairs for the trouble free and efficient functioning of the entire fire alarm system by providing one engineer for Monthly visit all as directed AND AS PER SPECIFIED NFPA 72 and Guidelines. Note:- (i) Cost of new components shall be paid for separately under relevant items of schedule 'A" (ii) Contractor's rep will visit minimum once in a month to every panel and take serviceability certificate duly signed by the user.
Dismantling, Servicing of multisensor detector with heat and smoke combination photoelectric as per exact locations with the help of manufacturer's instructions and testing for exact fault locations including cleaning through air blower then reinstalling every six month complete all as specified and as directed.
Serviceability and testing of inverter once in every month complete all as specified and as directed.
Serviceability and Testing of Beam detector and its transmitter and receiver alignment with testing kit as and when directed complete all as specified and as directed.
Serviceability and Testing of UV & IR flame detector and its alignment to detect flame with Testing Kit and when directed complete all as specified and as directed.
Supply of GSM SIM card services with validity SMS packs for 8 months for control & monitoring charges. Note:- GSM service provider shall be chosen (as per network availability) by Engr-in-Charge.
Supply & fix in repairs 12 V, 42 AH battery for Inverter supply for back up to all FACP and RTU panel complete all as specified and as directed. Make: EXIDE/AMAR RAJA/AMCO/AMARON
Supply & fix in repairs Printer Cartridge and Printer Paper Roll complete all as specified and as directed.
Comprehensive Service/Repair/maintenance/including spares and monthly visit for regular maintenance for the Automation of Wireless SCADA based temperature and Humidity monitoring system) (MAKE: CIMCON) of air conditioning plant installed at MES office at WSA Air force station Chabua by one factory trained Technician/Software Engineer. The scope of work includes carrying out complete maintenance/ servicing/ repairs as required of all the above sub systems viz. RTU based control panels (with all the accessories), RTD sensors, Humidity sensors, communication MODEM (with all its accessories) Humidity indicator, Temperature indicator, SCADA system etc. (with all its accessories), breakdown maintenance as and when required complete all as specified and directed by Engr-In-Charge. More over details of servicing are as under. (a) Servicing iRTU Panel i/e cleaning, checking for wear and tear, checking electrical termination, testing, as directed by Engr-In-Charge (once every month) and breakdown maintenance as and when required. (b) Servicing Temp. sensor i.e.. cleaning, checking for wear and tear, checking electrical termination ,testing, as directed by Engr-In-Charge (once every month) and breakdown maintenance as and when required. (c) Servicing Humidity transmitter i.e.. cleaning, checking for wear and tear, checking electrical termination, testing, as directed by Engr-In-Charge (once every month) and breakdown maintenance as and when required. (d) Servicing Humidity and temperature indicator i.e.. cleaning, checking for wear and tear, checking electrical termination, testing, as directed by Engr-In-Charge (once every month) and breakdown maintenance as and when required. Note:- (i) Cost of new components shall be paid for separately under relevant items
Supply & Fix in repair of 12V/7 AH Battery complete all as specified and as directed. Make: EXIDE/AMAR RAJA/AMCO/AMARON
Supply and Install, wireless modem suitable for GSM/GPRS based communication system, dual band GSM900 and GSM1800, compliant to GSM phase 2/2+ Class 4 (2W@ 900 MHz) Class 1 (1W@ 1800/1900MHz), control via AT commands (GSM 07.07 ,07.05 and enhanced AT Commands), with SIM application toolkit, complete all as specified and directed. Make: Visiontek (Linkwell Telesystems Pvt. Ltd.)/Safetek/ Siemens/L&T/Schneider/ Motorola/Cimcon
Supply and Install, Resistant Temperature Detector (RTD) Sensor with Transmitter (Signal Converter), three wire system, range 0°C to 200°C, accuracy Class ‘B’ (Tolerance as per IEC 751), suitable for measurement of room temperature (Inside the Room and Duct), complete all as specified and directed. Make: L&T/ Seimens/ Schneider/Baumer/ Radix/ Masibus/Wika
Supply and Install, surface mounted, humidity sensor with transmitter (Signal Converter), working range 0°C to 50°C & 0-100%RH, transmitter output 4-20mA (two wire), accuracy at 25°C ± 2% RH (0 to 90%) ; ± 3% RH (90 to 100%), suitable for measurement of Humidity inside room, complete all as specified and directed. Make: L&T/Seimens/Schneider/ Masibus/Wika / Baumer / Radix
Supply and Install, Process Indicator of minimum size 48x48 mm, with retransmission output for monitoring of temperature and humidity, complete all as specified and directed. Make: Multispan/Radix/Masibus
Supply and Install in repair UPS, 360 Watts /600 VA, Input 230V, Output 230V 600VA with minimum 15 minutes Backup, complete all as specified and directed. MAKE: APC Model No. BX600CI-IN or equivalent Model in Microtek/Su Kam/Luminious
Supply and Install, Programming, Testing and Commissioning of Supervisory Control and Data Accusition (SCADA) software development Version with required tags for Central Monitoring and control through wireless communication for Master Control Station, including programming liberty generation, soft keys etc.for graphical display of parameters for control and multilevel password protection, complete all as specified and directed. Make: MC WorX/GE FANUC/ROCKWELL AUTOMATION/L&T/Seimens/Schneider/ CIMCON/Safetek/Powertek
Supply Only, GSM SIM Card with prepaid Rental and SMS charges for data usage only without talk time, inclusive of all taxes and charges of service operator, for a period of 8 (eight) months for 02 (Two) Nos sim cards complete all as specified.
SUPPLY and install/renew COMPUTER ANTI VIRUS SOFTWARE complete all as specified and directed.
Supply of RTU logic up gradation and development for central monitoring through wireless communication at master control station which includes the development of logic for false alarm which comes from addressable fire alarm control panel complete all as specified and directed.
Supply and Fixing in repair or replacement of Indoor addressable detectors complying with and type certified to EN-54 Addressable type multisensor detector with heat and smoke combination photoelectric / optical with base with self built intelligence complete all as specified and as directed. Make:- GST/COOPER/BOSCH/SEIMENS
Supply only of electronically addressable intelligent resettable type manual call point with mounting base complying with EN 54 standard and LPCB approved with the specifications as appended below:- a) Power- 24V, ≤ 0.6 mA (Standby Current) ≤1.8mA (Alarm Current) b) Class A , c) Initiating Mode- Pressing the action plate manually Resuming Mode-Manually Resumed by a special Key, d) Ingress Protection IP-43 & Material-ABS Make:- GST/COOPER/BOSCH/SEIMENS
Supply only of the annunciating device Remote response indicator complete all as specified and directed. Make:- GST/BOSCH/SEIMENS
Supply only of fire alarm sounder/sirens electronic type horizontal single stage continuous normal operation for at least 50 minutes with sound level 65db to 120db measured at 1.5 m with sound output variation of +5db 500m range complete all as specified and directed. Make:- GST/COOPER/BOSCH/SEIMENS
Supply, Install, Testing & Commissioning of Wireless modem suitable for GSM based communication system to be mounted in RTU enclosure shall be installed at all proposed buildings complete all as specified and directed. Make:- CIMCON/MOTOROLA/SIMOCO/SEIMENS
Supply only of Amplifiers suitable 30-60 Watts, 230 VAC 50 Hz complete all as specified and directed. Make: AHUJA/BOSCH/PHILLIPS
Supply and Fixing wall mounted loudspeaker 10 watt 230V AC, 50Hz of sturdy design weather proof type re-entrant horn type loudspeaker for operating under rough conditions complete all as specified and directed. Make: AHUJA/BOSCH/PHILLIPS
Supply only of the indoor detector complying with and type certified to EN - 54 Addressable type flame detectors with UV and IR detection capacity (add up cost of module to be a complete set, the type of module shall be relay type module) with self built intelligence complete all as specified and directed. Make: SIEMENS/AGNI/GST/HONEYWELL
Supply only of Zone Monitor Module compatible with Fire Alarm Control Panel complete all as specified and as directed. Make: GST/COOPER/BOSCH/SEIMENS
Supply only of optical beam detector Transmitter and receiver type including testing complete all as specified and directed. Make: GST/COOPER/GODREJ/AGNI
Supply only 24 V DC Power Supply Unit of RTU complete all as specified and as directed. Make: CIMCON/SIEMENS/ABB
Supply only 12/5 V DC Power Supply Unit of RTU complete all as specified and as directed. Make: CIMCON/SIEMENS/ABB
Supply only CPU card of RTU complete all as specified and as directed. Make: CIMCON/SIEMENS/ABB
Supply only Analog and Digital I/O Card of RTU complete all as specified and as directed. Make: CIMCON/SIEMENS/ABB
Supply only DI/AI Termination PCB of RTU complete all as specified and as directed. Make: CIMCON/SIEMENS/ABB
Supply only of Display and Keyboard of RTU complete all as specified and as directed. Make: CIMCON/SIEMENS/ABB
Supply only of MCB 6A SP complete all as specified and as directed. Make: LEGRAND/HAVELLS INDIA LTD/HAGER/ INDOASIAN/C & S ELECTRIC LTD/ABB/L & T/SCHNIEDER/GE
Supply only of LEDs (Red/Green) for RTU Panel complete all as specified and as directed. Make: SAFETEK/CIMCON/POWERTEK
Supply only of Relay card : 8 relay 1 c/o for RTU panel complete all as specified and as directed. Make: SAFETEK/CIMCON/POWERTEK
Supply only of Isolation transformer—300 VA for RTU panel complete all as specified and as directed. Make: SAFETEK/CIMCON/POWERTEK
Supply only of PUSH BUTTON WITH NO CONTACT (BLACK) complete all as specified and as directed.
Supply only of GST200-2 Main Board F2.908.826a for FACP complete all as specified and as directed.
Supply only of LCD Screen CGM12864 for FACP complete all as specified and as directed.
Supply only of GST200 Rubber Keypad F7.843.249 for FACP complete all as specified and as directed.
Supply only of GST200 Loop Interface Board F2.908.828 (RoHS) for FACP complete all as specified and as directed.
Supply only of GST200 Power Supply Unit F2.932.069 (20100682) for FACP complete all as specified and as directed.
Supply only of Transformer 220V/27V-100W-R for FACP complete all as specified and as directed.
Supply only of PRN-6 printer, for FACP complete all as specified and as directed.
Supply only of two core copper conductor of size 1.5sqmm FRLS flexible shielded cable complete all as specified and directed. Make: HAVELLS INDIA LTD/INDIA LTD INDO AMERICAN ELECTRICALS FINOLEX/ NICCO/KEI/POLYCAB/RR KABLE LTD
Schedule of Credit
J D construction
M/s PRABIR ENTERPRISE
M/S S. P. ENTERPRISE
S K ENTERPRISE
R K CHAKRABORTY AND CO
ms singh construction
M/S DURGA CONSTRUCTION & CO
stage.html
html • 0.06 MB
tech_eval.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .