GE (S) Jaipur
Garrison Engineer (South) Jaipur Military Engineer Services Kalyan Marg, Jaipur302006
REPAIR AND MAINT OF LT OH/UG CIRCUIT AND SWITCH GEARS PANNEL BOARD AND CONNECTED ACCESSORIES AT ZONE-II AREA UNDER GE (S) JAIPUR
2022_MES_563504_1
GE (S)/J-53P OF 2022-23 8763/E8
Open Tender
Civil Works
Item Rate
210 days
Jaipur
Class E and category b(i)
9 documents required · 9 mandatory
₹500
GE (South) Jaipur
₹40,000
Yes
22 Dec 2022
16 Nov 2022
14 Dec 2022
16 Nov 2022
12 Dec 2022
29 Nov 2022
Amount
Excavation in trenches n.exc 1.5 metre wide and n.exc 1.5 metre in depth for foundation etc or for laying of cable etc and getting out in soft/loose soil as specified.
Excavation in trenches for n.exc 1.5 metre wide and exc. 1.5 metre but n. exc 3.0 metre in depth for foundation etc or for laying of cable/poles etc and getting out in soft/loose soil as specified.
Returning, filling in, including spreading, levelling, watering and well ramming in layers n.exc 25 Cm in depth as specified.
Removing of excavated material (soil) to a distance n.exc 50 metre and depositing where directed at a level n.exc 1.50metre above the starting point as specified.
M & L Sand cushioning to under ground cable with river bed fine sand and jently punning down to provide a required cover as specified.
M & L Bricks for protection cover to under ground cable (with old size sub class ‘B’ bricks) with width equal to length of brick laid dry and flat abutting each other with gaps between adjacent brick not exceeding 10mm as directed by Engineer-in-Charge.
M&L for PCC (1:3:6) type C2 with 40 mm stone aggregate for base / foundation / filling/mass concreting complete all as specified
M & L for PCC (1:2:4) type B-1 using 20 mm graded stone aggregate as in coping / pedestal to Pole etc including form work complete as specified
Dismantling and taking down existing LT insulators of any type and size as directed by Engineer-in-Charge.
M&L pre-stressed cement concrete poles, 9.0 metre long with minimum cross section 102 mm x 120 mm at top and minimum cross section 102 mm x 229 mm at bottom, class-11, conforming to IS-1678. complete all as specified and including dismentling of existing pole any type/size complete as specified. Note : PCC & excavation will be measured seperately
M&L stay assembly complete with accessories as shown in electrical plate No. 1 of MES SSR part I, including stay rod of 20 mm dia, MS stay plate 300 mmx500mmx6mm & GI stay wire of 7/8 SWG, bow of suitable length as required including dismentling of old u/s stay assembly complete. Note : PCC & excavation will be measured seperately
M&L cross arms, bracing, supports, clamps and back plates, fabricated from structural steel section including bolts, nuts, washers, welding, bending (cold or hot) drilling holes for bolts any shape or size as indicated or directed and inclusive painting with one primer coat of zinc chromate and two coats of aluminium paint including dismentling of old u/s of existing cross any type/size complete. Note :- MS/GI clamps, bolts, nuts and washers will also be measured under this item.
M&L pin type, porcelain, vitreous brown, white or green insulator 100 mm height and 65 mm dia, 1100 volts grade including one galvanised MS spindle, two GI washers and one GI nut complete conforming to IS complete as specified.
M&L shackle type, porcelain, vitreous, brown, white or green insulator 1100 volts grade of 90 mm dia and 75 mm height including galvanised MS strap of 31 mm x 3 mm size, 12 mm dia insulator bolts, washers and nuts, complete, conforming to IS complete as specified.
M&L for aluminium conductor steel reinforced (ACSR) straining properly on insulator and binding with aluminium binding/ Clamps, for running lines or jumpers etc.of any type and sizes complete all as specified and directed by Engineer-in-charge including dismantling and taking down of existing ACSR conductor of any size from pole . Note:- Measurement and payment shall be made by measuring horizontal distance between centre of two adjacent poles and adding 3% extra for sag, joints etc.
Straining only existing ACSR of any size/span on existing poles, insulators using proper tensioners and binding with aluminium binding/ Clamps complete as directed by Engineer-in-Charge. (each length of single conductor measured separately) Note:- Measurement and payment shall be made by measuring horizontal distance between centre of two adjacent poles and adding 3% extra for sag, joints etc.
Supply and lay tube GI light grade of 40 mm bore in trenches/ road crossings/ floor/poles/walls etc. with all fittings for protection of cable
All as per item No 17.00 but 50 mm bore
All as per item No 17.00 but 80 mm bore
Labour for boring under road/drain by manual/machine method for inserting GI tubing up to 80 mm dia for cable protection all as specified and directed by EIC.
M&L earthing with galvanised steel earth plate electrode 60cm x 60cm x 6 mm thick, with earth strip 25 mm x 4 mm protected by galvanised iron or steel pipe 40 mm bore light grade with Watering pipe 20 mm bore GI medium grade. The rate of earthing shall be inclusive of necessary earth work in any type of soil, charcoal, salt, funnel, PCC pit and RCC cover with handle complete as per electrical plate No. 3 of MES SSR Part-I. Note 1 : Following items deemed to be included in quoted rate (a) Earth electrode (b) Main earthing lead from earth elctrode to test point and further to equipment to be earthed upto 7.5 meter (c) Material and labour for connecting earth electrode and earthing lead as specified (d) Adequate quantity of charcoal dust and common salt as per direction (e) All labour including testing of earthnetwork. (f) Excavation and earth work or driling holes for electrode (g) P.C.C pit and C.I cover (h) Funnel with watering pipe, wire mesh and copper lugs etc as specified (j) G.I protection pipe of size ordered specified for protoction of earthing lead from mechanical injury or tempering. Note 2. On testing after completion if the desired earth resistance is not obtained the earth will b e redone at no extra cost.
Supply, laying, connecting, and commissioning LT under ground cable XLPE insulated, screened PVC bedded, galvanised steel strip armoured, heavy duty with multi stranded aluminium conductor, 1100 volts grade (ISI marked) laid in trenches, ducts, pipes or fixed on pole etc of size 120 Sqmm, 3.5 Core including distmantling & taking down of u/s old cable complete as specified.
All as per item No 22.00 but 95 Sqmm, 3.5 Core
All as per item No 22.00 but 70 Sqmm, 3.5 Core
All as per item No 22.00 but 50 Sqmm, 3.5 Core
All as per item No 22.00 but 35 Sqmm, 3.5 Core
All as per item No 22.00 but 25 Sqmm, 4 Core
All as per item No 22.00 but 16 Sqmm, 4 Core
All as per item No 22.00 but 16 Sqmm, 2 Core
M&L for preparation of old painted steel surface of LT Panel of any type and M&L for painting the same with two coats of synthetic enamel paint by spray of approved colour complete all as specified and directed by Engineer-in-Charge.
Supply and fix heat shrinkable straight through jointing kit complete with accessories suitable for XLPE armoured aluminium conductor cable 1.1 KV grade of size 10 - 35 Sqmm 3.5 Core complete as specified.
All as per item No 31.00 but 50-70 Sqmm, 3.5 Core
All as per item No 31.00 but 95-150 Sqmm, 3.5 Core
All as per item No 31.00 but 185 Sqmm, 3.5 Core
All as per item No 31.00 but 400 Sqmm, 3.5 Core
All as per item No 31.00 but 600 Sqmm, 3.5 Core
Supply and fix heat shrinkable end termination jointing kit complete with accessories suitable for XLPE armoured aluminium conductor cable 1.1 KV grade of size 10 - 35 Sqmm 3.5 Core complete as specified.
All as per item No 37.00 but 50-70 Sqmm, 3.5 Core
All as per item No 37.00 but 95-150 Sqmm, 3.5 Core
All as per item No 37.00 but 185 Sqmm, 3.5 Core
All as per item No 37.00 but 400 Sqmm, 3.5 Core
Disconnecting & taking out the existing Unserviceable MCCB from panel and S&F new MCCB 63 amp, 27 KA breaking cap of suitable frame size, 4 Pole, 415 V, 50 Hz, 3 phase, adjustable type including extension terminals and Ics=100%Icu connecting using suitable fasteners, modification/fabrication if any complete all as required at site, as specified and directed.
All as per item No 42.00 but 100 Amp, 27 KA
All as per item No 42.00 but 125 Amp, 27 KA
All as per item No 42.00 but 160 Amp, 36 KA
All as per item No 42.00 but 200 Amp, 36 KA
All as per item No 42.00 but 250 Amp, 36 KA
All as per item No 42.00 but 400 Amp, 50 KA
S&F in repairs of Danger notice plate of 1.6 mm thick mild steel sheet 20x15 cm size, vitreous enamelled white with letters, figures and conventional skull and bones in signal red colour and fixed with suitable MS clamps, bolts and nuts including taking down complete all as specified and directed.
Disconnecting & taking out the existing Unserviceable LT panel and S&F new out door (Kiosk type) type LT panel, weather & vermin proof MS sheet housing 3.15 mm thick, powder coated over a coat of primer, double door, front & rear openable type, mounted on 40x40x6 mm angle iron frame, floor mounted type with one MCCB, 4 pole, 200 Amp, 35/36 KA, 415 volts, thermal release, adjustable type (Ics=100%Icu) as incomer and provision of 4 outgoing MCCBs, 4 pole, 415 Volts, 200 Amps & Aluminium bus bar 400 Amp of length not less than 60 cm, 4 pole duly drilled with holes for cable connections, after due approval of panel drawing including PCC pedestals of suitable size, removal of old unsv panel, making good the area complete all as specified and directed by Engr-in-charge.
S&F Bus bar electrolytic grade aluminium of 25×6 mm, mounted on insulators including drilling holes including disconnection & reconnection of cables from existing panel complete all as specified and directed.
S & F On-load change over switch, 4 pole, 415 volts, 100 amp suitable for existing panel including taking down the unsv c/o switch, disconnecting and reconnecting all electrical connections, modification/fabrication if any complete all as specified and directed.
All as per item No 55.00 but 200 Amp
S&F in repair LED indicating lamp (Set of three lamps, RYB), 240 volts AC including necessary wiring (Set of three) complete.
S&F in repair Red luminous push button complete all as specified and directed by Engr in Charge.
S&F in repair Green luminous push button complete all as specified and directed by Engr in Charge.
M&L for cutting/removing damaged Hinge of any size and welding/ fabricating same with best quality replacement spare in the existing panel including making good of existing surface and smooth functioning as specified.
S&F in repairs MCB TPN 20 Amps, 10 KA breaking capacity complete all as specified and directed by Engr in Charge.
All as per item No 61.00 but 40 Amp
All as per item No 61.00 but 63 Amp
S&F in repair auxilary contactor of any suitable type complete all as specified and directed by Engr in Charge.
M&L for fault finding in U/G cable using fault locating machine on requirement for LT/HT cables of any type/size complete all as specified and directed by Engr-in charge. Note : One number of fault as located/ found shall be measured as one Job/Unit for payment.
S&F cable route indicator, cast iron 10 cm dia with 25x25x4 mm angle iron 0.8 m along the LT/HT cable trench including painting and grouting in ground in PCC 1:2:4 type B1 using 20 mm graded aggregate complete all as specified and directed by Engr in Charge.
Laying only LT UG cable 150 sqmm x 3.5 core to 300 sqmm x 3.5 core complete including taking out old u/s cable from trenches/pole complete. Note : (i) Cable shall be issued under Sch 'B' free for fixing/laying. (iii) Excavation /earth work will be measured & paid seperately under relevant item and no change in existing alligment of cable with prior written approval of GE.
Material & Labour for preparation of old painted surface of LT RCC pole (up to 6.10 metre height above coping), applying two coat cement base paint, making of strip of 20 cm width (Black and white in alternate band) upto 1400 mm height with one coat synthetic enamel paint, rewriting pole Nos by painter with synthetic enamel paint, and painting the existing MS clamp with one coat aluminum paint complete as directed.
Material & Labour for preparation of old painted surface of Steel tubeler pole 9 metre height of street light, applying two coat of synthetic aluminium paint, making of strip of 20 cm width (Black and white in alternate band) upto 1400 mm height with synthetic enamel paint, rewriting pole No by painter with enamel paint complete as directed.
M&L for shifting of LT Panel from one location (within the electrical zone) to another location including making all electrical connections as well as suitable size PCC foundation (1:3:6) type C2 completely as specified and directed by Engr-in-Charge. Note:-Excavation & related earth work shall be inclusive of quoted rates.
Trimming of tree/tree branches/shurbs in vicinity of electric supply line (any Nos of conductor) pole/street light pole/solar modules all arounds 3.0 m clearance each direction (verticale/horigontal) in between poles (each span approx not less than 30.0 m length ) & depositing at places n exc 50m all as directed by Engineer-in-Charge.
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .