Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | 1₹20.4 LAccepted-AOC BEHIND POWER HOUSE WARD NO 6 UDASAR BIKANER RAJASTHAN 334022 | BIKANER | RAJASTHAN | 334022 | 1 | Accepted-AOC LOWEST ACCEPTED BIDDER | |
| 2 | 2₹21.9 L+₹1.2 L (5.56%)Rejected-AOC | 2 | Rejected-AOC LOWEST ACCEPTED BIDDER IS M/S BIDAWAT ENTERPRISES | |
| 3 | 3₹22.0 L+₹1.2 L (5.81%)Rejected-AOC SHIV BARI ROAD NEAR KASUMAL HOTEL BIKANER 334003 RAJASTHAN | BIKANER | BIKANER | RAJASTHAN | 334003 | 3 | Rejected-AOC LOWEST ACCEPTED BIDDER IS M/S BIDAWAT ENTERPRISES |
Tender Value
₹19.4 L
EMD Value
₹38,740
Closing Date
8 Feb 2022, 6:00 pmClosed
Col Avik Saxena, CWE
HQ CWE Bikaner, Mil Stn Bikaner, PIN-334001
Provn of special repair to MRS and Pump House including VCB at Military Station Kanasar
2021_MES_489922_2
CWE BKN TOKEN NO 66 OF 2021-22
Open Tender
Civil Works
Item Rate
150 days
Kanasar
Please refer Tender documents.
7 documents required · 7 mandatory
₹500
GE (P) Kanasar
₹38,740
Yes
25 Feb 2022
20 Jan 2022
10 Feb 2022
20 Jan 2022
8 Feb 2022
27 Jan 2022
20 Jan 2022 - 25 Jan 2022
Amount
M&L for disconnecting the HT 33 KV out door VCB unit capacity ranging from 800 Amp -1600 Amp, overhauling of complete unit, opening the total machanical and electrical mechanism of breaker, checking its contact, baffle plates and other minor parts, cleaning the complete accessories carefully, minor repairs shall be rectified, parts/accessories shall be cleaned, the tank, baffle plates, rotating contact, upper supports, lower supports, drive shall be cleaned, and all other spare parts including rewiring connecting all control / communication wires coming from 33 KV transformer and VCBs, 33 KV current transformer, voltage transformer (CT & PT) including necessary modification in wiring for latest installed relays all as directed and reassembled after repair/replacement of the defective parts complete all as specified and as directed. Notes :- (i) Repair work shall be carried out only by the authorised technician of the concerned OEM. (ii) Spare parts as required for replacement of existing worn out parts shall be measured and paid separately under appropriate items. (iii) Labour for replacement/fixing of the supply only items shall be deemed to be included in the unit rate quoted against this item. (iv) After repairing contractor will test the complete mechanism and trip relay by applying artificial load for overcurrent and earth fault.
Supply only the following spare parts / items / accessories for repair/replacement to VCB under serial item No. 1.00 here-in-before :- Note :- Make & specifications of spare parts / items / accessories shall be as used/recommended by the OEM and as directed..
Master trip relays assembly
Breaker pull rod assembly
Vaccum interrupter bottle assembly for 33 KV outdoor VCB
T & C switch assembly
BLANK
Remote switch assembly
Auxiliary switch assembly
Spring charging motor.
Emergency push button / trip button with connected relays
Charging spring and tripping spring & complete gear box assembly along with bearing.
Push button along with connected tripping coil & closing coil for On/trip of VCB
Manual spring charging mechanism
Limit switch of spring charging mechanism
M&L opening of 33 KV VCB indoor control panel / operating panel for operating 02 Nos 33 KV VCB installed near 33 KV transformer for after opening doing overhauling of complete unit, opening the total machanical and electrical mechanism of different type of trip relay, checking its contact, other minor parts, cleaning the complete accessories carefully, rewiring complete with new wires as per existing including replacing connector, minor parts accessories, connecting all control / communication wires coming from 33 KV transformer and VCBs, 33 KV current transformer, voltage transformer (CT & PT) including necessay modification in wiring for latest installed relays, meters, making doors and locks serviceable for free movement all as directed and reassembled after repair/replacement of the defective parts complete all as specified and as directed. Notes :- (i) Repair work shall be carried out only by the authorised technician of the concerned OEM. (ii) Spare parts as required for replacement of existing worn out parts shall be measured and paid separately under appropriate items. (iii) Labour for replacement/fixing of the supply only items shall be deemed to be included in the unit rate quoted against this item. (iv) Addition / Alteration / cutting and welding work included in the item. No seperate payment shall be mase to the contractor.
Supply only the following spare parts / items / accessories for repair/replacement to VCB under serial item No. 3.00 here-in-before :- Note :- Make & specifications of spare parts / items / accessories shall be as used/recommended by the OEM and as directed..
Master trip relay assembly.
TNC switch assembly.
Electronic earth fault & over current relay having indicator and LED display.
Auxilary relay.
Speed tripping relay.
Push button along with NO/ NC contactors.
Alarm annunciator with digital display along with buzzer having different 24 types options such as Oil temperature, winding temperature, earth falult, over current, oil surge, Bauchholz, DC fail.
Indicator lamp in different colour code LED/Neon type complete (RYB) suitable for HT VCB including wiring with copper conductor cable of suitable size.
Supply and fix in replacement PVC control copper cable multistranded of size 2.5 sqmm 12 core, ISI marked, complete all as specified and as directed.
Supply and fix in replacement PVC control copper cable multistranded of size 2.5 sqmm 4 core, ISI marked, complete all as specified and as directed.
Supply and fixing in replacement bucholz relay suitable for 33/11KV transformer complete all as specified and as directed.
Supply and fixing in replacement oil temperature gauge to be fixed in 33/11 KV transformer complete all as specified and as directed.
Supply and fixing in replacement winding temperature gauge to be fixed in 33/11 KV transformer complete all as specified and as directed.
M&L for cleaning and preperation of old painted surfaces of 33/ 11 KV VCB and painting with two coats of synthetic enamel paint (blue colour) including doors, bottom brackets, stand, inner portion, clamps, channels, etc. and writing MES No. complete all as specified and as directed.
M&L for cleaning and preperation of old painted surface of 33 KV VCB control panel and painting with two coats of synthetic enamel paint (blue colour) including doors, bottom brackets, stand, inner portion, clamps, channels, etc. and writing MES No. complete all as specified and as directed.
M&L for cleaning and preperation of old painted surface of 33 KV capacity Transformer upto 5 MVA with preventing oil leakage and painting with two coats of synthetic enamel paint (blue colour) including overflow tank, cooling fins, wheels, gauge and writing MES No. complete all as specified and as directed.
M&L for cleaning and preperation of old painted surfaces of 10 to 11 meter long steel structure, having four legs made from 40mm x 40mm x 6mm 'L' shape angle, cross arms, brackets, clamps, channels painting with two coats of aluminium paint complete all as specified and as directed.
S&F Lightning arresters HT 11 KV 65 kilo Amp Non linear expulsion type transmission class with standard fittings confirming to IS-3070 (Part-I) 1985, fixed in repairs, complete all as specified & as directed.
S&F Lightning arresters HT 33 KV 65 kilo Amp Non linear expulsion type transmission class with standard fittings confirming to IS-3070 (Part-I) 1985, fixed in repairs, complete all as specified & as directed.
Supply and fixing in relpacement DC power pack for operating 11KV / 33 KV VCB relays having power backup upto 2 Hrs having 1.5 Amps load Max on each VCB complete with incoming 415V AC ±10%, 3 phase, 50 Hz, output power 110V DC with capacity of 40 Amps, FCBC battery charger of MMAX power with 55 cells of 2V/100AH SMF VRLA battery bank (Exide/Amara or makes mentioned in Appendix ‘B’ here-in-after) including connection to all 13 qty VCBs all as directed by Engineer-in-Charge.
S&F Aluminium Conductor Steel Reinforced (ACSR) of any size as directed, stringing for overhead line on HT poles including jointing with and including aluminium binding wire 2 mm dia, jumpers, line tapes, conducting jelly, stretching properly and connecting with suitable PG clamps, etc including dismantling and taking down old existing unserviceable aluminium conductor steel reinforced (ACSR) of any size/type/capacity, complete all as specified and as directed. Notes : (i) The ACSR conductors shall conforming to IS-398 (Part-II) and as specified in SSR Part-I. (ii) The unit rate quoted shall also deemed to include for supply and fixing of binding wire, aluminium tapes, etc which shall not be included in the weight of conductors for payment. (iii) Weight of conductors shall be determined by measuring the horizontal distance between centers of two adjacent poles and compounding the weight of conductors of that size and length and 3% extra shall be added for sag, jointing, jumpers etc. (iv) Weight of the conductors shall be calculated from the nominal weights given in tables in the relevant IS code.
M&L for cable jointing kit for 11 KV (Earthed) grade cable for straight through heat shrink type joint complete with jointing material and accessories suitable for 3 core XLPE armoured aluminium conductor cable of size 50 sqmm to 95 sqmm including dismantling & taking out old unserviceable jointing kit complete all as specified & as directed.
M&L for cable jointing kit for 11 KV (Earthed) grade cable for straight through heat shrink type joint complete with jointing material and accessories suitable for 3 core XLPE armoured aluminium conductor cable of size 120 sqmm to 185 sqmm including dismantling & taking out old unserviceable jointing kit complete all as specified & as directed.
M&L for cable jointing kit for 11 KV (Earthed) grade cable for indoor termination heat shrink type joint complete with jointing material and accessories suitable for 3 core XLPE armoured aluminium conductor cable of size 50 sqmm to 95 sqmm including dismantling & taking out old unserviceable jointing kit complete all as specified & as directed.
M&L for cable jointing kit for 11 KV (Earthed) grade cable for indoor termination heat shrink type joint complete with jointing material and accessories suitable for 3 core XLPE armoured aluminium conductor cable of size 120 sqmm to 185 sqmm including dismantling & taking out old unserviceable jointing kit complete all as specified & as directed.
Supply and fixing in replacement aluminium busbar rectangle shape strip of capacity 11 KV, 800 Amps along with insulators all as directed by Engineer-in-Charge.
M&L for Earthing to Panel / Transformer / GOD switch / equipments etc with & including galvanised mild steel earth plate electrode of size 60 cm x 60 cm x 6 mm thick buried vertically in ground (earth pit not less than 2.25 m below normal ground level) with top edge of the earth plate at a depth not less than 1.5 m below ground level, the earth electrode surrounded by adequate quantity of charcoal dust and salt to a packed thickness of 15 cm on all sides, connected to & including galvanized mild steel strip 32x6 mm as earth lead, including nuts, bolts, check nuts & washers of galvanized iron or steel and riveted/welded to earth plate at one end and other end of strip connected to Panel / transformer / GOD / equipment body / test point with two Nos nuts bolts or welding with steel structure, GI earth strip encased in and including 40mm bore GI light grade pipe with all fittings from upper edges of earth plate upto 7.5 metre above ground level fixed with and including 25x3mm flat iron clamps, bolts, nuts and washer and also including providing watering pipe 20mm bore GI pipe medium grade from earth pit to top of electrode and including funnel, wire mesh, copper lugs etc complete with earth pit in PCC 1:3:6 type C1 using 20mm graded crushed stone aggregate and 40mm thick RCC (1:2:4 type B1) cover complete all as specified and shown in electrical plate No 3 of SSR Part-I including necessary excavation and earthwork in any type of soil, returning, filling in approved soil and disposal of surplus soil to a distance not exc 50m complete all as specified and as directed including dismantling & taking out old existing unserviceable earthing. Note : PCC chamber shall be constructed at least 1.5 mtr away from the earth electrode and pipe for watering shall be provided in slanting manner.
Taking down / taking out carefully without damaging old unserviceable burnt / punctured / faulty aluminium / HT Pilca cable / XLPE cable of any size laid in trenches/ducts, through pipe, under floors or roads/ along poles etc and relaying / refixing the same after rectification of defect including cutting making jointing complete all as specified & as directed. Notes :- (i) Excavation & earth work and cable jointing kit shall be measured & paid for separately. (ii) Old serviceable brick / precast PCC cable cover shall be reused where directed by Engineer-in-charge and rate quoted shall dement to include for the same. (iii) If cable is damaged by the contractor’s workmen during the execution of work, the same shall be provided / repaired by the contractor at his own cost complete to the entire satisfaction of GE.
S&F 6mm thick mild steel Chequered Plates with big rice projections, Square cut or notched (ordinary and counter sunk) forming holes, without any attachment, conforming to Grade E-165 (Fe 290), fixed on cable ducts in required sizes, complete all as specified and as directed.
Supply and fixing back side cover of HT Panel / VCB made from 3 mm thick mild steel sheet in required shape including Nut / bolts, washers, welding work, etc complete all as directed by Engineer-in-Charge.
Demolition of cement concrete (unreinforced) of any description and in any position not otherwise specifically provided for in this Schedule complete all as specified & as directed.
Demolition of reinforced cement concrete of any description and in any position (reinforcement cut as required to facilitate demolition) not otherwise specifically provided for in this Schedule, complete all as specified & as directed. Note : Contractor shall make arrangement to protect tiles, plumbing items, sanitary fittings, etc under the slab, etc by gunny bags with sand or any other suitable arrangement and quoted rates shall deemed to include this aspect.
Demolition of brickwork or stone/boulder masonry, built in cement mortar or cement lime mortar including all quoins, arches, pillars, etc but excluding ashlar facings, dressed stonework and precast concrete articles complete all as specified and as directed.
Taking down cement plaster or cement lime plaster, terrazo etc on PCC/stone surface/brick surfaces including raking out joints hacking for key scrubbing down with water etc, complete all as specified and as directed.
Dismantling floor, hearth or wall tiling including cement mortar bedding (but not backing) and rubbish off the premises, complete all as specified and as directed.
Dismantling of wrought iron or mild steel work of any description and from any position not otherwise provided for in this Schedule (BOQ), complete all as specified and as directed.
Taking down chowkat or frame with shutters (including fittings & fixtures) area not exc 1.5 Sqm each (without taking off the shutters from the frame) of door/window including cutting holes for taking out hold fasts and making good the same including disturbed portion of jambs, cills, etc complete all as specified and as directed.
Taking down chowkat or frame with shutters (including fittings & fixtures) area exc 1.5 Sqm but not exc 4 Sqm each (without taking off the shutters from the frame) of door/window including cutting holes for taking out hold fasts and making good the same including disturbed portion of jambs, cills, etc complete all as specified and as directed.
Excavating in trenches, not exc 1.5 metre wide and not exc 1.5 metre in depth, for foundation, etc. or for shafts, wells, cesspits, manholes, pier holes, etc. laying cables, pipes, etc. not exc 10 Sqm on plan & not exc 1.5m in depth and getting out in soft/loose soil complete all as specified and as directed.
Returning, filling in, including spreading, leveling watering and well ramming in layers not exc 25 cm thick in soft/loose soil complete all as specified and as directed.
Removing excavated soil/material to a distance not exc 50 metre and depositing where directed at a level not exc 1.50 metre above the starting point complete all as specified and as directed.
M&L for cement concrete 1:2:4 type B1, using 20mm graded crushed stone aggregate as in lintels upto 1.5m clear span, cills, steps, seismic and other similar bands, plinth courses, string courses, lacing courses, parapets and railings upto 60 cm in height, copings, kneelers, apex stones, bed plates, roof kerbs, mud stops and the like including weathering, slightly rounded, chamfered angle and throating as directed including use and waste of form work (straight or curved) all exposed surface of concrete finished fair complete all as specified & as directed.
M&L for reinforced cement concrete 1:1½:3 Type A1 (Nominal Mix) using 20mm graded crushed stone aggregate in slabs supported on walls, beams and columns in floors, roofs, shelves and the like complete all as specified & as directed. Note :- Reinforcement & formwork shall be measured and paid for separately.
M&L for reinforced cement concrete 1:1½:3 Type A1 (Nominal Mix) using 20mm graded crushed stone aggregate in chajjas and the like complete all as specified & as directed. Note :- Reinforcement & formwork shall be measured and paid for separately.
M&L for reinforced cement concrete 1:1½:3 Type A1 (Nominal Mix) using 20mm graded crushed stone aggregate in fins, fascias, louvers, parapets, and railings exc. 60cm in height, newels, balustrade and the like complete all as specified & as directed. Note :- Reinforcement & formwork shall be measured and paid for separately.
Supply only integral liquid water proofing compound (ISI marked).
M&L for brick work with old size burnt clay sub-class ‘B’ bricks, straight or curved on plan exc 6.00 metre mean radius, built in cement mortar 1:4 complete all as specified and as directed.
Formwork to faces of walls, retaining walls, abutments, parapets and staircase railings and similar work including attached pillasters, buttresses, etc., vertical or to batter for rough finished flat surfaces of concrete complete all as specified & as directed.
Formwork to soffits of suspended slabs such as roof slabs, floor slabs, landings and similar work, not exc 200mm thick (Horizontal or sloping) for rough finished flat surfaces of concrete complete all as specified & as directed.
Formwork to flat surfaces of chajjas, chullah hoods, troughs and similar items including edges for rough finished surfaces of concrete complete all as specified & as directed.
Formwork to edges of concrete flats, roofs, floors etc and sides of RCC/PCC bands in walls, horizontal or sloping and similar work exc 10cm but not exc 20cm wide for rough finished surfaces of concrete complete all as specified & as directed.
Resecuring or easing & adjusting without taking down shutter of any description not exc 1 sqm each complete all as specified & as directed.
S&F factory made solid PVC door frame of size 50mm x 47mm made out of 5mm plain colour single piece extruded PVC profile reinforced with MS square tube, fixing in opening as per specifications complete all as specified and as directed.
S&F factory made solid panel PVC door shutter 30mm thick (style) consisting of frame made out of MS tubes for top and bottom rails. MS frame shall be covered with plain colour single piece extruded PVC profile ‘C’ channel having a PVC sheet strip of 20mm width stuck inside with solvent cement for styles and plain colour single piece extruded PVC profile for top rail lock rail bottom rail on either side and as gap insert for Top rail and bottom rail paneling of plain colour PVC sheet to fitted on the MS frame welded/sealed to the styles and rails with suitable PVC sheet beading and joined together with solvent cement complete all as specified and as directed..
S&F stainless steel butt hinges of size 100mm medium weight, complete all as specified and as directed.
S&F 150 mm long aluminium anodized barrel tower bolts of extruded section (ISI marked) complete all as specified.
S&F Cast iron or malleable cast iron handles of size 100mm, cast type, stove enamelled black, complete all as specified & as directed.
S&F extruded aluminium alloy handle, 150mm size, fabricated type, anodized (ISI marked) complete all as specified and as directed.
S&F Cast Iron (Malleable or mild steel) Casement stays, size 300mm, with hinged joint and two plates, with studs complete all as specified & as directed.
S&F 300 mm long aluminium alloy, anodized, sliding door bolt with hasp, staple (bolt type) and fixing clips of sheet, cast or extruded sections and fixing bolts and sliding bolts of extruded sections or cast aluminium alloy complete all as specified and as directed.
S&F mild steel framed work such as grills, gratings, etc with ends of bars shouldered and/or riveted, or forged into spikes, framed guard bars, barred iron doors, ladders, framed balusters, framed signed boards, walk ways, railings, framework of water tanks and similar work including welding conforming to Grade E-165 (Fe 290), complete all as specified & as directed.
M&L for mild steel TMT bars 10 mm dia and over cut to length, bent to shape required, including cranking, bending spirally or hooping for columns, hooking ends and binding with mild steel wire (annealed) not less than 0.9 mm dia complete all as specified & as directed.
M&L for mild steel TMT bars 6 to 8 mm dia cut to length, bent to shape required, including cranking, bending spirally or hooping for columns, hooking ends and binding with mild steel wire (annealed) not less than 0.9 mm dia complete all as specified & as directed.
Supply & fixing steel rolling shutters, thickness of laths 1.25 mm, without ball bearing, as specified including top cover, anchoring rod, hasp and staple and one shop coat of primer, erected in position as indicated, complete, gear operated type with bevel gear box and crank handle, complete all as specified and as directed.
S&F Safety lever locks mild steel with 4 levers for rolling shutters complete all as specified and as directed.
S&F Ball bearing for rolling shutters complete all as specified and as directed.
Dismantling posts or struts (wood, steel or R.C.C.) any section, embedded in concrete, brick work, ground masonry, etc., including taking out embedded portion and making good disturbed ground, complete all as specified and as directed.
S&F mild steel work as in hand rails, half round or other stock section or core for wooden hand-rail straight portion, drilled and countersunk for balusters running bars, for doors, balusters, nosing to steps including embeding in concrete and screwing etc. wind ties for roof including securing bolts, posts and struts in fencing including cutting tops to shape as directed, drilling holes, notching for wire, etc., flat iron fillets (for securing wire mesh etc.) including all necessary drilling, bolting or riveting, etc., and similar work conforming to Grade E-165 (Fe 290), complete, all as specified & directed.
S&F in repairs galvanized 2 strand, steel barbed wire 2.24mm dia, barbed with 2mm dia barbs at 75mm spacing and straining and fixing to any type of standard rails, straining bolts, including securing or tying at crossing with and provision of galvanized mild steel wire, staples or steel pins etc complete all as specified & as directed. Note :- Each line of horizontal / vertical / diagonal wire to be measured for the purpose of payment.
M&L for 75 mm thick PCC (1:2:4) type B2 using 40 mm graded crushed stone aggregate as in sub base, leveling course, etc, surface finished fair and even, complete all as specified and as directed.
M&L for 25mm thick PCC (1:2:4) type B0 using 12.5mm graded crushed stone aggregate as in flooring, leveling course, etc, surface finished fair and even, complete all as specified and as directed.
M&L for non skid ceramic tiles (coloured) 7 to 8mm thick (square/rectangular) area of each tile exceeding 0.06 sqm but not exceeding 0.11 sqm as in floors, set and jointed in neat cement slurry and pointed in white or coloured cement to match the shade of tiles over & including 15mm thick screed bed in cement & sand mortar 1:6 complete all as specified and as directed.
M&L for glazed ceramic tiles (coloured) 7mm thick, area of each tile exceeding 0.11 sqm but not exceeding 0.18 sqm (i.e 450mm x 300mm or as directed), on vertical surfaces such as dado, skirting etc., set and jointed in neat cement slurry and pointed in white or coloured cement to match the shade of tiles over & including 10mm thick rendering (as screed bed) in cement & sand mortar 1:4 complete all as specified and as directed.
M&L for factory made 60mm thick machine pressed precast cement concrete coloured designer polished (reflecting type) interlocking paver blocks of Grade M-35 conforming to IS 15658-2006 of shape and size as directed with grey cement and no pigment with coloured top casted in an automatic plant working on vibration and simultaneous hydraulic compression from top, laid over & including 25mm thick sand cushioning, joints of blocks filled with dry sand and compacted with mechanical vibrator complete all as specified & as directed. Note : Shape & colour of paver blocks shall be as approved by the GE.
M&L for 75mm thick PCC 1:3:6 type C1 using 20 mm graded crushed stone aggregate as in plinth protection & similar works surface finished even and smooth without using extra cement complete all as specified. Note :- Plinth protection shall be of width as directed and shall be laid with an outward slope of 1:30 in alternative bays not exceeding 4 meter in length. Joints of 6 mm wide and 10 mm deep shall be provided along the wall and bays and same shall be filled with bitumen mastic (1:3).
M&L for rendering 10mm thick in cement mortar 1:4 on surfaces other than fair face of brick work of walls, finished even & smooth without using extra cement complete all as specified.
M&L for rendering 15mm thick in cement mortar 1:4 on fair faces of brick masonry or concrete surfaces of walls, mixed with integral liquid water proofing compound as per manufacturer’s instructions, finished fair & even, complete all as specified and directed. Note : Supply only integral liquid water proofing compound shall be measured and paid for separately.
M&L for rendering 5mm thick in cement mortar 1:3 on concrete surfaces in ceiling, finished even & smooth without using extra cement complete all as specified.
M&L for preparation of new plastered surfaces of walls and applying two coats of oil emulsion distemper (OBD) of approved shade/tint over a coat of primer over & including 3mm thick white wall care putty complete all as specified & as directed.
M&L for preparation of new plastered surfaces of ceiling and applying two coats of oil emulsion distemper (OBD) of approved shade/tint over a coat of primer over & including 3mm thick white wall care putty complete all as specified & as directed.
M&L for preparation of new plastered/unplastered surfaces of walls and applying two coats of weather proof acrylic emulsion paint (exterior grade) of approved shade/tint in approved pattern over a coat of primer complete all as specified & as directed.
M&L for complete removal of existing treatment including cleaning of mortar drops, smoke soot, moulds, moss, efflorescent salts, trading oil, greasy spots etc and preparation of plastered surfaces and applying two coats of weather proof acrylic emulsion paint (exterior grade) of approved shade/tint in approved pattern over a coat of primer on walls complete all as specified and as directed.
Hacking out old broken glass any thickness, size, quality or description from metal frame including punching or drilling out old glazing pins/spring clips complete all as specified and as directed.
S&F 3mm thick sheet glass ordinary quality and glazing with oil putty in square not exc 0.5 sqm in each pane including painting / oiling to new putty to match with the existing/new surfaces, complete all as specified & as directed.
M&L for preparation of old painted steel and iron surfaces of any description over 10 cm in width or girth and applying one coat of synthetic enamel paint of approved tint all as specified & as directed.
M&L for preparation of new steel and iron surfaces of any description over 10 cm in width or girth and applying two coats of synthetic enamel paint of approved tint over a coat of zinc chrome primer complete all as specified & as directed.
Dismantling carefully and taking up or down existing unserviceable/serviceable steel water tubing and connections of 15mm bore complete all as specified and as directed.
M&L for galvanized steel water tubing medium grade of 15mm bore with & including all fittings, fixed to walls and ceilings or laid in floors, complete all as specified and as directed.
Dismantling carefully and taking up or down existing unserviceable/serviceable steel water tubing and connections of 20mm bore complete all as specified and as directed.
M&L for galvanized steel water tubing medium grade of 20mm bore with & including all fittings, fixed to walls and ceilings or laid in floors, complete all as specified and as directed.
M&L for cutting chases, pinning in, making good to facings as original where required and pointing in cement mortar 1:3 for concealed water tubing and making good, cutting not exc 10 cm girth in brick walls, complete all as specified & as directed.
Disconnecting & taking down the existing unserviceable water tank and Supply and fixing 500 Litre capacity Rotational moulded polyethylene water storage tanks double layered (cylindrical vertical with closed top) ISI marked, hoisted & fixed in position & making necessary arrangements for fixing inlet, outlet & over flow pipe & provision of wash out pipe etc. complete as specified in SSR Part-I and as directed.
S&F in repairs Ball valves, high pressure of PTMT with epoxy coated aluminium rod & high density plastic ball, screwed for iron pipe 20mm bore (minimum weight 210 gms) complete all as specified and as directed.
S&F in repairs vitreous china squatting pan (Orissa pattern) water closet (white) of size 580x440mm with integral foot rests, ‘P’ or ‘S’ trap, including connection to trap and flushing pipe, antisyphonage pipe etc, complete all as specified and as directed.
S&F in repairs PVC valveless symphonic action type low level flushing cistern (ISI marked) of 10 litre capacity including 32 mm dia PVC flush pipe connected to water closet with inlet, ball valve, float and handle complete all as specified & as directed.
S&F in repairs vitreous china wash hand basin, white, flat back of size 630mm x 450mm with & including a pair of cast iron brackets embedded in PCC 1:3:6 type C1 blocks of size 10x7.5x15cm, 32 mm dia PVC waste pipe and 32mm bore chromium plated brass waste fitting with long screwed shanks and fly nuts, flange end bedded in red lead cement & other end fixed, (excluding tap, waste chain & plug), complete all as specified & as directed.
S&F in repairs PVC connection 450 mm long suitable for 15 mm bore GI pipe including PTMT nuts on both sides complete all as specified & as directed.
S&F in repairs 15mm bore pillar tap, cast copper alloy with capstan heads, chromium plated, fancy type, screwed down high pressure, with or without lettered ‘Hot’ or ‘Cold’ with long screwed shanks & fly nuts, screwed for iron pipes, complete all as specified & as directed.
S&F in repairs 15 mm bore bib tap, brass, chromium plated, long body, fancy type with capstan head, screwed down, screwed for iron pipe or for brass ferrule, including CP brass wall flange, complete all as specified & as directed.
S&F in repairs 15mm bore Stop valve, cast copper alloy, fancy type chromium plated, screwed down, high pressure with capstan heads, screwed both ends for iron pipe or for union complete all as specified & as directed.
S&F in repairs 20mm bore Gun metal gate valve (ISI marked) with iron wheel head, screwed both ends for iron pipe, complete all as specified & directed.
S&F in repairs brass chromium plated shower rose 125mm size with swivel joint type including fixing to steel pipe of 15mm bore or union complete all as specified and as directed.
S&F 110mm bore PVC (SWR) pipes single socketed in any length with rubber ring joints / solvent cement joints laid in trenches or in floors, fixed in repairs, complete all as specified & as directed.
S&F 110mm bore PVC (SWR) pipes single socketed in any length with rubber ring joints / solvent cement joints fixed to walls, fixed in repairs, complete all as specified & as directed.
S&F 110mm bore PVC (SWR) bend, complete all as specified & as directed.
S&F 110 mm bore PVC (SWR) junction single (single ‘T’), equal or unequal with access door complete all as specified & as directed.
S&F in repairs PVC (SWR) multi floor trap with PTMT grating including jointing with solvent cement, diameter of outlet 110mm, complete all as specified & as directed.
S&F in repairs PVC (SWR) Gully trap 125/110mm, setting and jointing with solvent cement complete all as specified and as directed.
S&F PVC (SWR) 'S' trap, 110mm bore, complete all as specified and as directed.
Demolition and breaking up 150mm bore SGSW/RCC/AC drain pipes set in cement mortar including PCC haunching and bedding, complete all as specified and as directed.
S&F salt glazed stone ware drain pipes of 150mm bore, Class ‘SP 2’, ISI marked, laid to slope in trenches, jointed in CM (1:1) and tested complete all as specified & as directed.
M&L for PCC 1:4:8 type D2 using 40 mm graded crushed stone aggregate in bedding to SGSW drain pipes, including packing under and haunching against the sides of pipes after they are laid and tested for 150 mm bore pipe complete all as specified and as directed.
ALPHA ENGINEERING COMPANY
M/s Rohit Construction Co.
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .