Loading…
Tenderkart now works inside Claude and ChatGPT: search and analyse tenders right from your chat
Loading…
Tender ID
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹18.2 LAccepted-AOC | L1 | Accepted-AOC Being L1 | |
| 2 | L2₹18.6 L+₹35,367.50 (1.94%)Rejected-Finance | L2 | Rejected-Finance L1 being accepted | |
| 3 | L3₹18.8 L+₹63,865 (3.51%)Rejected-Finance | L3 | Rejected-Finance L1 being accepted | |
| 4 | L4₹18.9 L+₹72,393 (3.98%)Rejected-Finance | L4 | Rejected-Finance L1 being accepted | |
| 5 | L5₹19.0 L+₹75,005 (4.12%)Rejected-Finance | L5 | Rejected-Finance L1 being accepted |
Tender Value
₹18.5 L
EMD Value
₹37,000
Closing Date
3 Jan 2022, 6:00 pmClosed
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
GE 867 EWS
GE 867 EWS C/O 99 APO PIN 913867
REPAIRS TO LT DISTRIBUTION SYSTEM AND ALLIED WORKS AT RHENOCK AND RONGLI UNDER GE 867 EWS
2021_MES_490248_2
CA NO GE/867/TOKEN/ 61 OF 2021-2022
Open Tender
Electrical and Maintenance Works
Item Rate
270 days
Rhenock
Refer tender documents
8 documents required · 8 mandatory
₹500
GE 867 EWS
₹37,000
Yes
14 Jan 2022
20 Dec 2021
4 Jan 2022
20 Dec 2021
3 Jan 2022
28 Dec 2021
20 Dec 2021 - 25 Dec 2021
60 days
Amount
Excavating in trenches, not exceeding 1.5m wide and not exceeding 1.5 in depth for taking out /laying of cable etc., and getting out in soft/loose soil.complete all as specified and directed by Engineer-in-Charge.
Excavating in trenches, not exceeding 1.5m wide and exceeding 1.5m and not exceeding 3m in depth for taking out /laying of cable etc., and getting out in hard/dense soil.complete all as specified and directed by Engineer-in-Charge.
Returning, filling in soil, including spreading leveling, watering and wall ramming in laying not exceeding 25 cm thick complete all as specified and directed by Engineer-in-Charge.
Removing excavated soil to a distance n.exe 50m and depositing where directed at alevel n.exe 1.5m above the starting point complete all as directed by Engineer - in -Charge.
Supply and spreading of dry sand in trenches for cable coushioning and punned down complete all as specified and directed by Engineer-in-Charge. Note:- Punned thickness only shall be measured for payment purpose.
M&L for common burnt bricks, sub class 'B', of size 250 x 125 x 75 mm laid in trenches for cable protection complete all as specified and directed by Engineer-in-charge.
Supply and laying in trenches, fixed to wall or drawn through pipe etc., XLPE Insulated screened PVC bedded, galvanized steel strip or wire armored, electric power cables (heavy duty) 1100 Volts grade with stranded aluminium conductor of size 120 sqmm 3.5 core and connecting with necessary lugs including taking out exising unserviceable cable complete all as specified and directed by Engineer-in-Charge.
Supply and laying in trenches, fixed to wall or drawn through pipe etc., XLPE Insulated screened PVC bedded, galvanized steel strip or wire armored, electric power cables (heavy duty) 1100 Volts grade with stranded aluminium conductor of size 70 sqmm 3.5 core and connecting with necessary lugs including taking out exising unserviceable cable complete all as specified and directed by Engineer-in-Charge.
Supply and laying in trenches, fixed to wall or drawn through pipe etc., XLPE Insulated screened PVC bedded, galvanized steel strip or wire armored, electric power cables (heavy duty) 1100 Volts grade with stranded aluminium conductor of size 50 sqmm 3.5 core and connecting with necessary lugs including taking out exising unserviceable cable complete all as specified and directed by Engineer-in-Charge.
Supply and laying in trenches, fixed to wall or drawn through pipe etc., XLPE Insulated screened PVC bedded, galvanized steel strip or wire armored, electric power cables (heavy duty) 1100 Volts grade with stranded aluminium conductor of size 35 sqmm 3.5 core and connecting with necessary lugs including taking out exising unserviceable cable complete all as specified and directed by Engineer-in-Charge.
Supply and laying in trenches, fixed to wall or drawn through pipe etc., XLPE Insulated screened PVC bedded, galvanized steel strip or wire armored, electric power cables (heavy duty) 1100 Volts grade with stranded aluminium conductor of size 25 sqmm 3.5/4 core and connecting with necessary lugs including taking out exising unserviceable cable complete all as specified and directed by Engineer-in-Charge.
Supply and laying in trenches, fixed to wall or drawn through pipe etc., XLPE Insulated screened PVC bedded, galvanized steel strip or wire armored, electric power cables (heavy duty) 1100 Volts grade with stranded aluminium conductor of size 16 sqmm 4 core and connecting with necessary lugs including taking out exising unserviceable cable complete all as specified and directed by Engineer-in-Charge.
Supply and laying in trenches, fixed to wall or drawn through pipe etc., XLPE Insulated screened PVC bedded, galvanized steel strip or wire armored, electric power cables (heavy duty) 1100 Volts grade with stranded aluminium conductor of size 16 sqmm 2 core and connecting with necessary lugs including taking out exising unserviceable cable complete all as specified and directed by Engineer-in-Charge.
Supply and laying in trenches, fixed to wall or drawn through pipe etc., XLPE Insulated screened PVC bedded, galvanized steel strip or wire armored, electric power cables (heavy duty) 1100 Volts grade with solid aluminium conductor of size 10 sqmm 2 core and connecting with necessary lugs including taking out exising unserviceable cable complete all as specified and directed by Engineer-in-Charge. Note for Item No. 7 to 14:- Excavation, earth work, brick protection, protection pipe and sand coushioning shall be measured and paid separately. Make of cable shall be CCI / Gloster / ICC / Unistar / NICCO / Asian (RPG) / Havells / Polycab/PRG/Universal/Plaza/Crystal cables/Terracom/ Rallison/Mescab/Jeypore/KEI
Material and labour for 80 mm dia bore GI tubing Light grade, laid under roads/ floor, or fixed to wall or along the pole with suitable size M.S.flat iron clamps, nuts, bolts and washers for cable protection including taking down/out existing pipe complete all as specified and directed by Egineer-in-Charge.
Material and labour for 40 mm dia bore GI tubing Light grade, laid under roads/ floor, or fixed to wall or along the pole with suitable size M.S.flat iron clamps, nuts, bolts and washers for cable protection including taking down/out existing pipe complete all as specified and directed by Egineer-in-Charge.
Material and labour for 25 mm dia bore GI tubing Light grade, laid under roads/ floor, or fixed to wall or along the pole with suitable size M.S.flat iron clamps, nuts, bolts and washers for cable protection including taking down/out existing pipe complete all as specified and directed by Egineer-in-Charge. Make for iItem No. 15 to 17: TATA/ZENITH/JINDAL.
S & F pin type insulator, porcelain, vitreous white/ brown or green including one galvanised mild steel spindle two GI washer and one GI nut 100mm height, 65mm dia for 1100 Volt grade including taking down existing insulator complete all as specified and directed by Engineer-in-Charge.
S & F Schakle type insulator, porcelain, vitreous white/ brown or green including galvanised mild steel straps of size 31 x 5 mm, washers insulator bolt of 14 mm dia and nuts complete of size 100 mm hight and 115mm dia of working pressure 1100 volts grade including taking down existing insulator complete all as specified and directed by Engineer-in-Charge. Make for iItem No. 18 & 19: (i) Jaipuria (ii) Jayshree (iii) Maysore Electric Industries (iv) Oblum
S&F cable route marker of size 100 mm x 100 mm x 5mm thick with GI plate with inspection threon bolted / welded to 35 mm x 35mm x6 mm angle iron 60 cm long and fixing the same in ground as required for LT cable all as specified and directed by Engineer-incharge.
S&F Busbar Chambers 8 way 100 Amps outdoor type (IP 65/66) pole mounted including provision of fixing on pole by means of suitable size of clamps with nut and bolts including necessary connection including taking down existing bus bar chamber complete all as specified and as directed by Engr-in-charge. Make: Havells cat part No IHBC010004 or equivalent model of SMC/Hencel.
Cutting and trimming tree branches any girth and any size and any number, touching to over head line and clearing the distance 2.5 mtrs both side of LT/HT over head conductors of span not exceeding 60m between poles and removing cut branches to a distance not exceeding 50m complete all as specified and directed by Engineer-in-Charge.
M&L for Plain cement concrete 1:3:6 mix type C2 (using 40 mm graded stone aggregate) in foundations, filling and mass-concrete etc., all as specified and directed by Engineer-in-Charge.
M & L Plain cement concrete 1:2:4 type B1 (using 20 mm graded stone aggregate) as in coping including necessary formwork, weathering, slightly rounded or chamfered andgles, finishing of exposed surfaces of concrete to even and smooth without using extra cement all as specified and directed by Engr-in-charge.
Supply and fix 32 x 6mm galvanised iron strip as earth continuity conductor or main earth lead fixed to wall on batten or recess or chases or buried in ground or drawn in conduit pipe or fixed to poles or any other indicated situation for loop earthing etc., as required including taking down existing earth strip complete all as specified and directed by Engineer-in-Charge.
Supply and stringing of aluminium conductor steel reinforced (ACSR) of any size as in overhead lines including binding wires of suitable sizes and suitable conductors / parallel groove clamp Etc. other jointing materials for over head lines including taking down existing ACSR conductors complete all as specified and directed by Engineer-in-Charge.
Earhing complete with galvanized steel earth plate electrode 600X600X6 mm buried directly in ground (earth pit not less than 2.25 m deep below ground level) with top edge of the plate not less than 1.5m below ground level, connected to GI earth strip of size 32x6mm, by means of galvanized iron or steel bolts, nuts, check nuts and washers, and conneced to equipments as directed, including funnel with GI med grade watering pipe 20 mm bore, wire mesh charcoal or coke and common salt in alternate layers, of 15 cm compacted thickness all around the earth electrode, with concrete pit in PCC 1:3:6 type C-1 , 50 mm thick pre cast RCC 1:2:4 type B1 cover slab reinforced with 8 mm dia reinforced bar 15 cm C/C and suitable handle of 10 mm dia round bar, 40 mm GI medium grade pipe for earth lead protection including necessary excavation earth work in soft/loose soil and disposal of spoil to a distance n.exc. 50 m and necessary testing complete all as shown on electrical plate No. 3 of MES SSR Part-I including taking out existing earth plate etc., complete all as specified and as directed by Engineer-in-Charge. NOTE: Rate quoted shall be deemed to include for earth lead and protection pipe upto 7.5m.
Earthing complete with galvanized steel earth plate electrode 600 x 600 x 6 mm buried directly in ground ( earth pit not less than 2.25 m deep bellow ground level ) with top edge of the plate not less than 1.5 m below normal ground level, connected to GI earth lead wire 4 mm dia. by means of galvanized iron or steel bolts , nuts , check nuts and washers, and connected to equipments as directed , including funnel with GI medium grade watering pipe 20 mm bore , wire mesh , charcoal or coke and common salt in alternate layers of 15 cm compacted thickness all around the earth electrode , with concrete pit in PCC 1:3:6 type C-1 , 50 mm thick pre cast RCC 1 : 2 : 4 type B-1 cover slab reinforced with 8 mm dia deformed bar 15 cm C/C and suitable handle of 10 mm dia round bar, 15 mm GI medium grade pipe for earth lead protection including necessary excavation earth work in soft/loose soil and disposal of spoil to a distance n.exc. 50 m and necessary testing complete all as shown on electrical plate No. 3 of MES SSR Part-I including taking out existing earth plate etc., complete all as specified and as directed by Engineer-in-Charge. NOTE: Rate quoted shall be deemed to include for earth lead and protection pipe upto 7.5m.
M&L for galvanised steel wire 3.15 or 4mm dia as earth continuity conductor including binding and connecting to earth test point etc., including taking down existing earth wire complete all as specified and directed by Engineer-in-Charge.
M&L for galvanised stay strand 7/4mm as stay wire including binding etc., including taking down existing stay wire complete all as specified and directed by Engineer-in-Charge.
M&L for cross arms , bracings, supports, clamps and back plate fabricated from structural sections including nuts, bolts, and washer bending hot or cold , drilling holes for bolts of any size and painting with two coats of aluminum paint over one coat of red oxide primer including preparation of surfaces, including taking down existing cross arms etc., complete all as specified and directed by the Enginee-in-Charge.
M&L for Stay assembly with 20mm dia rod complete with accessories as shown in electrical plate No. 1 including taking out existing stay assembly, insulator complete all as specified and directed by the Enginee-in-Charge. Note: Loop type insulator, stay clamps, stay wire, excavation and concrete shall be measured and paid separately.
S & F loop type insulator, porcelain, vitreous white/ brown or green of size 90 x 140mm with clearence of hole 25.5 mm including taking down existing insulator complete all as specified and directed by Engineer-in-Charge.
M&L for applying one coat aluminium paint on 9 mtr long steel tubler pole in position after prepretion of surface of steel tubler pole including all fitted cross arms, clamps and nut, bolts etc., including painting of black and yellow paint strips of 05 Nos of 30 cm wide strips or as ordered by engineer-in-charge on poles up to 1.5 mtr high above coping level including numbering of size 70mmx40mm by using stencil to the pole with black synthetic enamel paint ( 1st grade ) 1.5 mtr above the ground level all as specified and as directed by Engineer-in-Charge.
Restringing of existing LT overhead line for removing exessive sag including removing the existing binding wire and rebinding with new binding wire after tightning of overhead lines including disconnecting existing jumper and connections and reconnecting after tightning of conductor incl replacement of all jumpers all as directed by Engr -incharge. Notes: - (a) Single wire run of conductor in LT lines shall be measured as one lenght for payment purpose. (b) ACSR conductor shall be measured and paid separately.
Repairing of LT panel by means of replacing the hinge and locking arrangement of the existing panel, tightening the cable with bus bar by means of suitable lugs all as specified and as directed by Engr-in-charge.
S&F of MCCB of Four Pole, 415V, AC 50 Hz, 36KA breaking capacity 160 Amps with thermal magnetic protection and thermal adjustment range 80 to 100% Icu=Ics=100% including taking down old unserviceable MCCB complete all as specified and directed by Engineer-in-Charge.
S&F of MCCB of Four Pole, 415V, AC 50 Hz, 25KA breaking capacity 100 Amps with thermal magnetic protection and thermal adjustment range 80 to 100% Icu=Ics=100% including taking down old unserviceable MCCB complete all as specified and directed by Engineer-in-Charge. Make for Item No. 37 & 38: LEGRAND/SIEMENS/SCHNEIDER/L&T
Material and labour for spray painting to outdoor/Indoor type double door LT panels/Fedder pillar box incl angle iron stand with synthetic enamel paint after cleaning the surface thouroughly with scrapper including protecting/cleaning of cables, wiring and other non painted parts complete all as specified and as directed by Engr-in-charge.
Supply and fix cable jointing kit in repairs of existing LT 1.1 KV grade cable disconnecting from site (by means of disconnecting from pole/panel/trench) for outdoor termination Straight through tubular sleeve version type joint kit complete with jointing materials and accessories suitable for 3.5 core XLPE armoured aluminium conductor cable of size 70 Sqmm to 120 Sqmm complete all as specified and as directed by Engr-in-charge.
Supply and fix cable jointing kit in repairs of existing LT 1.1 KV grade cable disconnecting from site (by means of disconnecting from pole/panel/trench) for outdoor termination Straight through tubular sleeve version type joint kit complete with jointing materials and accessories suitable for 3.5 core XLPE armoured aluminium conductor cable of size 25 Sqmm to 50 Sqmm complete all as specified and as directed by Engr-in-charge.
Supply and fix cable jointing kit in repairs of existing LT 1.1 KV grade cable disconnecting from site (by means of disconnecting from pole/panel/trench) for outdoor termination Straight through tubular sleeve version type joint kit complete with jointing materials and accessories suitable for 4 core XLPE armoured aluminium conductor cable of size 16 Sqmm complete all as specified and as directed by Engr-in-charge.
Supply and fix cable jointing kit in repairs of existing LT 1.1 KV grade cable disconnecting from site (by means of disconnecting from pole/panel/trench) for outdoor termination Straight through tubular sleeve version type joint kit complete with jointing materials and accessories suitable for 2 core XLPE armoured aluminium conductor cable of size 16 Sqmm complete all as specified and as directed by Engr-in-charge. Make item No. 40 to 43: RAYCHEM/ 3M / M-SEAL/ DENSON
Dismantling/taking up or down roof conductor/down conductor of aluminium strip of any size/condition with insulators from the Bldg for replacement of insulator/conductor etc., and segregating serviceable conductor & insulators for re-use at site and removal of unserviceable conductor and insulators from site of work all as specified and as directed.
Fixing only serviceable roof conductor/down conductor any type/size retrieved under item No. 46 above on roof wall on porcelain or epoxy spacer insulator (insulator measured and paid separately under relevant item) all as specified and as directed. Note :- Rates quoted by the contractor shall be deemed to be included for cutting, jointing pieces of strip with nut bolt etc.
Supply and fixing aluminum strip 25 x 3.15 mm complete with saddles and fixing screws for roof / down conductor on porcelain/epoxy spacer insulatoror fixed on GI Pipe all as specified and as directed. (Spacer insulator measured and paid separately under relevant items) . Note :- Rates quoted by the contractor shall be deemed to be included for cutting, jointing pieces of strip with nut bolt etc.
S&F porcelain/epoxy white / brown / green spacer insulator with one GI stud bolt with nut and washer with necessary drilling for bolt hole for holding / fixing roof conductor / down conductor of lightning conductor complete all as specified and as directed
Fixing only porcelain/epoxy white / brown / green spacer insulator retrieved under item No. 46 above with one GI stud bolt with nut and washer for holding / fixing roof conductor / down conductor of lightning conductor complete all as specified and as directed
Supply and fixing GI light grade pipe of 15mm dia for fixing air termination rod and earth strip on roof including dismantling of old worn out GI pipe all as specified and as directed. Make : JINDAL/ZENITH/TATA
Supply and fix single pointed air termination aluminium rod 12-mm dia 300 mm long with fixing arrangement including dismantling of old unserviceable/ deshaped conductor and removed from site of work complete all as specified and as directed
Taking down existing single pointed air termination aluminium rod 12-mm dia 300 mm long and refixing with fixing arrangement complete all as specified and as directed
Supply & Fixing Test Point Terminal Block made of gum metal or phophorus bronze size( 75 x75x25) mm drilled and screwed including 3 Nos 8 mm dia 25 mm long hex head Screw complete including taking down existing test terminal back complete all as specified and directed by Engineer-in-Charge.
S& F in replacement of Danger notice plate of 1.6mm thick mild steel sheet, vitreous enamelled white, with letters, figures and conventional skull and bones in signal red colour and fixed with M.S. clamps, bolts and nuts of approved size, for LT, 20x15cm size complete all as directed by Engr-in-charge.
M & L for DK Thermoplastic cable junction boxes IP 65 of size 270x225x135mm of metric knockouts for cable entry, weather proof for outdoor installation with and including glands and with 4 terminals for terminating one incoming and outgoing UG cable of size 10/16 sqmm 2/4 core and fixed to the PSC/Steel Poles by means of suitable size of clamps with nut and bolts complete including taking down existing existing junction box all as specified and directed by Engineer-in-Charge. NOTE: Make of Junction box shall be Sintex/Hensel or equivalent as approved by GE.
M&L for preparation of new or previously untreated surfaces of steel and iron surfaces of any description, not otherwise described, over 10 cm width or girth and applying two coats of synthetic enamel paint over one coat of red oxide zinc chrome primer all as specified and directed by Engineer-in-Charge.
M&L for preparation of old treated surfaces of steel and iron surfaces of any description, not otherwise described, exceeding 10 cm width or girth and applying one coat of synthetic enamel paint all as specified and directed by Engineer-in-Charge.
M&L for preparation of new or previously untreated surfaces of steel and iron surfaces of any description, not otherwise described, not exceeding 10 cm width or girth and applying two coats of synthetic enamel paint over one coat of red oxide zinc chrome primer all as specified and directed by Engineer-in-Charge. Make for Item No. 55 to 57: ASIAN/ SHALIMAR/ BERGER/ JENSON & NICHOLSON/ IEL/ NEROLAC
Supplying and spreading 40mm graded stone aggregate around the structure yard area complete all as specified and directed by Engineer-in-Charge.
S&F Fe 410-W (Gde-E- 250) quality-A rolled mild steel plates (plain or chequered), as in base plates etc., square cut or notched (ordinary and counter sunk) forming holes, with riveted, bolted or welded attachment complete all as specified and directed by Engineer-in-charge.
S&F Fe-290 Gde E-165 mild steel angle or other sections as in posts and struts in fencing etc., and similar work including cutting tops to shape as directed,drilling holes, notching for wire, including all necessary drilling holes for bolting or riveting, etc., including taking down existing fencing posts complete all as specified and directed by Engineer-in-charge.
S&F MS galvanised chain link fencing fixed to any type of standards, rails, posts, straining bolts etc., including provision of binding wire including dismantling of old fencing wire mesh any type complete all as specified and directed by Engineer-in-charge.
S&F Mild steel bar round bars 6 to 8 mm dia in fencing, cut to length, bent to shape required including cranking, bending, hooking ends and binding etc. as in line bars of fencing conforming to grade I, IS-432 (Part I) all as specified and directed.
S&F Fe-290 Gde E-165 mild steel flat or other sections as in fillets etc., and similar work including all necessary drilling holes for bolting or riveting, etc., complete all as specified and directed by Engineer-in-charge.
S&F mild steel machine made screw bolts not exceeding 5cm long 11 to 15 mm (diameter of neck) with hexagonal or square heads at one end and screwed the other, screwed end fitted with washers and one hexagonal or square nut, complete all as specified and directed.
S&F for galvanised, 2 strand, steel barbed wire 2.24mm dia barbed with 2mm dia barbs at 75mm spacing and straining and fixing to any type of standard rails straining bolts, incl securing or tying at crossings with and provision of galvanised mild steel wire, staples or steel pins, etc., including dismantling old rusted barbed wire any type all as specified and directed.
M&L for preparation of old plastered surfaces of walls and applying one coat of cement based paint complete all as specified and directed by Engineer-in-Charge. Make: INDOCEM/ SUPERSNOWCEM/ AQUACEM/ DURACEM
M&L for preparation of newly plastered surfaces of walls and applying two coats of cement based paint over one coat of primer complete all as specified and directed by Engineer-in-Charge. Make: INDOCEM/ SUPERSNOWCEM/ AQUACEM/ DURACEM
Sub Total of Schedule 'A'
Schedule of Credit (Minus) Rs. 38,815.00 B/F from Ser page No. 29 NOTE: Bidder shall insert credit amount as rate Rs. 38,815.00 in Green field under Col-M. If bidder does not insert the amount the same will be deducted from total amount of Schedule 'A' and accordingly total amount of tender will be considered in deciding the lowest tender.
Sub Total of Schedule of Credit
MANOJ JINDAL
JAYSHREE CONCERN
SANJAY SAW MILL
MS MAYA PRAKASH GOEL AND SONS
DEEP CHANDRA JOSHI
G K SUTHAR
MS BRAHMA CONSTRUCTION
stage.html
html • 0.06 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .