Loading…
Loading…
Tender ID
Tender Value
₹8.4 L
EMD Value
₹87,000
Closing Date
28 Mar 2026, 12:00 pmClosed
Superintending Engineer
Superintending Engineer (E/M) 44th E/M Circle, PWD, Varanasi
Janpad fatehpur isthit nirikshan bhawan fatehpur me 100 KVA CPCB-4 Generator ki apurti evum isthapana ka karya
2026_CEEMP_1126154_1
344/Nivida Suchna(Fatehpur)-44/2025-26, Dt. 26-02-2026
Open Tender
Electrical Works
Fixed-rate
90 days
Fatehpur
Please refer Tender documents.
3 documents required · 3 mandatory
₹677
Executive Engineer, Mechanical Division. PWD
₹87,000
Fatehpur
23 Mar 2026
17 Mar 2026
28 Mar 2026
17 Mar 2026
28 Mar 2026
17 Mar 2026
20 Mar 2026
Supplying, Installation, Testing & Commissioning of ‘Silent Type Diesel Generating set as per CPCB IV + or better norms along with having Prime Power Rating of KVA as below, 415 volts at 1500 RPM, 0.8 lagging power factor at 415 V suitable for 50 Hz, 3 phase system & for 0.85 Load Factor, including testing at factory and site with fuel, load for test and other necessary arrangements Complete as per CPWD specifications, should have QR code which should contain drawing, test report OEM manual,Geo- Tag of manufacturing location, rating plate as per relevant IS Code etc. and consisting of the followings:
Diesel Engine: Tourbocharged Diesel engine 4 stroke water cooled, multi cylinder, dynamically balanced fly wheel, electric start of suitable BHP at 1500 RPM suitable for above output of alternator at 40 0C, 50% RH & at 1000 Meter MSL , capable of taking 10% over loading for one hour after 12 hours of continuous operation. The engine will be with Electronic governor, Dry type Air filter with service indicator, first filling of engine fuel (after commissioning) lubricating Oil, Coolant and other consuma bles complete with all the required accessories, the Electronic governor shall be as per ISO 8528. The engine shall comply to the latest CPCB norms (CPCB IV + or better) and Conforming to BS 5514, BS 649, IS 10000, IS 10002, IS 13018 and as per CPWD specifications.
Engine mounted Instrument Panel fitted with and having digital dis Plate for following: (i) Start-stop switch with key (ii) Water temperature indication (iii) Lubrication oil pressure indication (iv) Lubrication oil temperature indication (v) Battery charging indication and Voltage indication (vi) RPM indication (vii) Over speed indication (viii) Low lubricantion Oil trip indication (ix) Engine Running Hours indication (x) Fuel Level
Alternator: Synchronous alternator rated of appropriate KVA, 415 volts at 1500 RPM, 3 phase 50 Hz, AC supply with 0.8 lagging power factor at 40 0C, 50% RH & at 1000 Meter MSL. The alternator shall be having Screen Protected Drip Proof (SPDP) enclosure IP23, brushless, continuous duty, dynamically balanced rotor, capable of taking 10% over loading for one hour after 12 hours of continuous operation, self cooled,self-excited and self-regulated through AVR conforming to IS13364(Part 2)/IS: 4722/BS 2613 suitable for tropical conditions and with class- H insulation.
Base Frame & Foundation: Both the engine and alternator shall be mounted on suitable base frame made of MS channel with necessary reinforcement which shall be installed on suitable cement concrete foundation and vibration isolation arrangement as per recommendations of manufacturer.
FUEL TANK: Daily service fuel tank of suitable liters capacity as per CPWD Specifications, fabricated out of 3 mm thick M.S. sheet complete with all standard accessories and fuel piping between fuel tank and diesel engine with MS class ‘C’ pipes of suitable dia. Complete with valves, level indications & ccessories as required as per specifications.
Starting System: 12V/24V DC starting system comprising of starter motors: voltage regulator and arrangement for initial excitation complete with suitable numbers of batteries (180 AH capacity lead acid SMF type) as required as per specifications. The battery shall be housed inside the acoustic enclosure of DG Set.
Acoustic and weather proof enclosure with arrangement for fresh air intake for cooling of the engine & alternator, extraction, discharging hot air in to the atmosphere and the temperature rise inside the enclosure, noise level outside enclosure. The acoustic enclosure should be suitable for cableconnection/connection through bus-trunking. Such arrangements on acoustic enclosure should be water proof & dust-proof conforming to IP-65 protection. The enclosure shall be as per CPCB IV + or better norms etc. and as per CPWD specifications.
AMF Panel: Free standing floor mounted IP 42 automatic mains failure control panel including auto by-pass, suitable for KVA as below for silent type DG set complete with relays, timers, set of CTs for metering & protection and energy analyser to indicate currents, phase and line voltages, frequency, power factor, KWH, Kilo Volt Ampere Reative Hour (KVARH), KVA (Phase & Total), KW & provision for overload, short circuit, restricted earth fault, under frequency, power (aluminium) and control (copper ) cabling of suitable size upto 15 meter between AMF panel, LT Panel and DG Set including connection interconnection etc. as required, all complete and inter locking and communication/ Ethernet /RS485/SNMP port open protocol for BMS integration including suitable software, the panel shall be of DG Set OEM make etc. as per approved by Engineering in charge and including the following:
100 KVA. DSR (E/M) 2025 Ref. No. 29.1.7
Earthing with copper earth plate 600mm X 600mm X 3mm thick including accessories and providing masonry enclosure with cover plate having locking arrangement and watering pipe to 2.7 m long etc. with charcoal/coke and salt as required. DSR (E/M) 2025 Ref. No. 5.6
Providing and fixing 25mm X 5mm copper strip on surface or in recess for connections etc. As per required. DSR (E/M) 2025 Ref. No. 5.8
Supply and fixing of brass nickle plated compression gland for PVC insulated & armoured served sheathed, underground cable including rubber ring etc. complete in all respect. The armouring of the cable shall be properly connected with the earth as per direction of Engineer- Incharge. (a)120 Sq mm 3-1/2 core. DSR (E/M) 2025 Ref. No. 11.1.25
Supply and laying of fillowing size aluminium conductor PVC insulated armoured served sheathed cables 1100 Volts grade on wall surface a directed by Engineer-in-charge complete in all respect including Excavation & Re-filling. The armouring of the cable shall be properly connected with earth conductor by clamps etc:- 120 Sq mm 3-1/2 core. P.S. No. 20a.1.15
Supplying and making end termination with brass compression gland and aluminium lugs for followingsize of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required.
(a) 4 X 16 sq. mm (28mm) DSR (E/M) 2025 Ref. No. 11.1.33
(b) 3½ X 70 sq. mm (38mm) DSR (E/M) 2025 Ref. No. 11.1.23
Structural steel work riveted, bolted or welded in built up sections, trusses and framed work, including cutting, hoisting, fixing in position and applying a priming coat of approved steel rimer all complete. Civil DSR 2023 10.2
Providing corrugated G.S. sheet roofing including vertical / curved surface fixed with polymer coated J or L hooks, bolts and nuts 8 mm diameter with bitumen and G.I. limpet washers or with G.I. limpet washers filled with white lead, including a coat of approved steel primer and two coats of approved paint on overlapping of sheets complete (up to any pitch in horizontal/ vertical or curved surfaces), excluding the cost of purlins, rafters and trusses and including cutting to size and shape wherever required. (a) 1.00 mm thick with zinc coating not less than 275 gm/m². Civil DSR 2023 12.1.1
stage.html
html • 0.01 MB
tech_bid_open.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 0.52 MB
Tendernotice_2.pdf
PDF • 1.07 MB
BOQ_2099878.xls
BOQ • 0.26 MB
545100KVA.pdf
PDF • 0.27 MB
525KVA100.pdf
PDF • 0.24 MB
455A100DGSET.pdf
PDF • 0.26 MB
455A100DGSET.pdf
PDF • 0.26 MB
465ADGSET100.pdf
PDF • 0.24 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .