Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹60.5 LAccepted-AOC | ₹60.5 L | L1 | Accepted-AOC due to urgentnature |
| 2 | Rejected-Technical | - | - | Rejected-Technical solvency certificate not enclosed , Refer TEC report |
| 3 | Rejected-Technical | - | - | Rejected-Technical Document not submitted as per required |
| 4 | Rejected-Technical 1 3 37 CP CHAMBERS 2ND FLOOR STREET NO 5 HABSIGUADA HYDERABAD 500 007 | HYDERABAD | HYDERABAD | TELANGANA | 500007 | - | - | Rejected-Technical Turn over not found as per required , Refer TEC report |
| 5 | Rejected-Technical | - | - | Rejected-Technical Turn over not as for Form-B . Refer TEC Report |
Tender Value
Refer Docs
EMD Value
₹1.2 L
Closing Date
11 Feb 2021, 3:00 pmClosed
Director
Aiims Patna
Supply installation validation of BSL-2 Lab with a minimum pressure of 12 PA Including testing of AHU, Control panel, split Ac , PUF insulation on wall , Damper, Insulated gate, table vinyl flooring , wiring of electrical wire etc
2021_AMSPA_612703_1
AIIMS/Pat/SE/Ac/Cobas6800
Open Tender
Miscellaneous Works
Works
21 days
Aiims Patna
Please refer tender documents
4 documents required · 4 mandatory
₹1,500
Aiims Patna
₹1.2 L
Yes
18 Dec 2021
28 Jan 2021
12 Feb 2021
28 Jan 2021
11 Feb 2021
30 Jan 2021
29 Jan 2021 - 30 Jan 2021
Supply AHU : Capacity: more than 3000 CFM , Double skin AHU complete with mixing box, Cooling coil, fan, volume control dampers for Supply of fresh air, fresh air filter, Static Pressure (mm wg) - 100 , Construction – 28 mm PUF Moulded Double Skin Detachable Panels , Structural - Extruded Spl Alloy Al Profiles filled with PUF , Panel - External Skin - 0.6 mm Pre plasticised Sheet , Panel - Internal Skin - 0.6 mm Plain GI Sheet , Insulation Material/thickness - 25mm Thick PUF with minimum 40kg/m3 density , Fan Type - DIDW Backward Curve Centrifugal Fan , Fan Wheel size & No. of Fans - RDH 315R #1 , Fan Speed in RPM – 2381, Critical Fan Speed in RPM – 3100 , Fan Outlet Velocity in mps - 8.68 , Motor Drive Arrangement - Taper Lock Pulleys for Fan & Motor Both ,Type of Balancing/Test Procedure - Statically & Dynamically/AMCA Tested , Type of Vibration Isolators - Rubberized Mounts , Filters Provision - Pre Filters & HEPA filters , Coil Type - Cooling Coil , Coil Surface Area - Sq. ft - 6.11 , No.of. Coil Rows- 6 , Face Velocity Across the coil - 491 , Coil Specification - 1/2 " OD 27SWG Copper & 36 SWG AI Fin at FPI , Canvass - SRF make Flexible Fire Retardant Canvass, Hardware - Galvanized, Operation Wt (Kgs) - Aprox – 240, Noise level less than 60 db at 1mtr from source.
Exhaust AHU Capacity: more than 3500 CFM , Double skin AHU complete with mixing box, volume control dampers for return, fresh air ,Static Pressure (mm wg) - 100 , Construction - 28mm PUF Moulded Double Skin Detachable Panels , Structural - Extruded Spl Alloy Al Profiles filled with PUF , Panel - External Skin - 0.6 mm Pre plasticised Sheet ➢ Panel - Internal Skin - 0.6 mm Plain GI Sheet ➢ Insulation Material/thickness - 25mm Thick PUF with 45kg/m3 density ,Fan Type - DIDW Backward Curve Centrifugal Fan , Fan Wheel size & No. of Fans - RDH 315R #1 , Fan Speed in RPM - 2381 , Critical Fan Speed in RPM – 3100 ,Fan Outlet Velocity in mps - 8.68 , Motor , Drive Arrangement - Taper Lock Pulleys for Fan & Motor Both , Type of Balancing/Test Procedure - Statically & Dynamically/AMCA Tested , Type of Vibration Isolators - Rubberized Mounts , Filters Provision - Pre Filters, HEPA filters Hardware etc
AHU Control Panel
Ducting: Ventilation ducting will be made out of minimum 24 gauge GI sheet, exhaust duct from the lab to the AHU will be 24 Gauge GI Duct. All the ventilation ducting including return air riser will be leak proof. with Insulation material with Nit Rile foam/cross linked Polyethylene material (Aluminium Foil insulation)
Condensing unit: Supply and Installation of Condensing unit with 11 Tr(5.5 tr x 2) capacity Including, Gas, Copper tubing, Drier & expansions valves etc
Dampers : Galvanised steel Volume controlled damper, Opposed / parallel Blade Dampers are used to carry out a rough air system balance with closer control being carried out at the individual grilles or diffusers.
Supply & Return air grills Supplying & fixing of powder coated extruded aluminium Supply Air Grills with aluminium volume control dampers as per specifications.
Supply, installation, testing & commissioning of thermal insulated flexible duct of following sizes duly supported at regular interval as per site requirement etc. complete as required as per specifications.
Ceiling Panel: Modular ceiling: Modular ceiling will be made for Clean Room application, pre-engineered 50 mm thick PUF panels with PCGI Sheets with PUF insulation of minimum 38- 40 kg/m3. Both surfaces should be power coated 0.6 mm thick PCGI sheet and will be installed along the outer walls, partitions and false ceiling to create an impervious shell, which is fully sealed.
Modular wall: Modular wall will be made for Clean Room application, pre-engineered 50 mm thick PUF panels with PCGI Sheets with PUF insulation of minimum 38-40 kg/m3. Both surfaces should be power coated 0.8 mm thick PCGI sheet and will be installed along the outer walls, partitions and false ceiling to create an impervious shell, which is fully sealed
Covings: Extruded aluminum anodized R75 clip-on type (Male & Female connectors) covings for entire wall to floor, wall to wall & wall to ceiling joints. Extruded aluminum double cove integrated with top track of the partition panels. Corner internal & external cove joining pieces in aluminum anodized finish. Having similar construction and finish as the walls and properly sealed with silicon sealant with wall & ceiling
Modular Clean room Door Flush Door finishes shall be 50 mm thick 1.2mm thick PCGI sheet suitable to fix on 50 mm thick wall panel with provisions for double glazing glass for all door and hardware like push plate.PUF Panels will be with PCGI Sheets, powder coated on both sides and PUF insulation of minimum 38-40 kg/m3. Concealed hardware for fixing of door frames, door closure, SS hinges, SS Door handle, SS ball bearing butt hinges, automatic drop seal, concealed tower bolt for the double door, both sides lock and key arrangement etc Size: (Single door)915 x 2100 mm Size : Double door(1500 x2100)
Differential Pressure Gauge Supply, Installation of Magnahelic Pressure gauges 0 – 10 mm for monitoring differential room pressures
Vinyl flooring make Armstrong
Vinyl coving
Door interlocking system
Static Pass box: MOC: SS 304 Size: 2’ x 2’ x 2’, Door, Interlocking system, UV light, Fluorescent Lamp etc
Electricals: Required electrical arrangements(3 phase and single phase) for the purpose of energizing the BSL-2 Laboratory facility All the electrical fittings and fixtures in the laboratories areas shall be suitable for clean room application and shall be sealed (all conduits, outlets shall be sealed with silicon sealant), leak proof and capable to withstand chemical exposures during fumigation 3 phase power plug - 3 no's 6/16Amp power Plug--25 no's
Input to UPS (from Distribution panel ) :- 63 Ampere 4 Pole MCB (to provide 3 phase input supply to UPS,RYBN+E format) near UPS installation location.- 1 no's 10 mm² wire (for 3phase supply, RYBN+E format) from - Distribution panel to the 63 Amp 4 Pole MCB and from – 63 Amp, 4 Pole MCB to UPS input.
Output from UPS (will go to c6800 ) :- 32 Ampere 4 Pole MCB, Two (2) Quantity 16 Ampere Double Pole MCB along with earth to be provided near c6800.- 1 no's 10 mm² wire (for 3phase supply, RYBN+E format) from UPS to these 3 MCB’s (1 qty 32Amp & 2 Qty 16Amp) Output wire (6 mm²) of around 4 meter length from these 3 MCB’s are to be provided, at end of which industrial connectors will be connected by UPS Engineer.
Miscellaneous works - for items required, if any, as per site require while execution of work.
PCR hood, size: 4 feet, MOC: CRCA Powder coated
LAN Port near c6800 at the back wall (High Speed Internet + Provision for Remote UI)
Supply and Installation of 1 TR Split AC
Supply and Installation of 2 TR Split AC
Shed work for AHU,AC
1 ft x 1 ft down light
Laying and fixing of one number PVC insulated and PVC sheathed I XLPE power cable of 1.1 kV grade of following size on wall surface as required. Upto 35 sq. mm (clamped with 1mm thick saddle)
Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed I XLPE aluminium conductor cable of 1.1 kV grade as required. 3.5C X 50 sq. mm (35mm)
Supplying, installation, testing & commisioning of following capacity Plug In/ tap off box on the existing Air Insulated Compact Type bus trunking/ rising mains for use on 3 phase 4 wire 415 V, 50Hz A.C. supply made with 1.6mm thick sheet steel enclosure (IP54) duly powder coated with provision of MCCB (but without MCCB) complete etc. as required 125 A, (lsc=15 kA for 1 second)
3.5 x 50 sq. mm AL Armoured XLPE Cable (Make - Havells /Polycab/ Finolex)
CAMC of Above entire setup including all spares & consumables required for 1st year after DLP
CAMC of Above entire setup including all spares & consumables required for 2nd year after DLP
CAMC of Above entire setup including all spares & consumables required for 3rd year after DLP
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .