Loading…
Loading…
Tender ID
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
Tender Value
₹55.3 L
EMD Value
₹1.1 L
Closing Date
4 Feb 2026, 6:00 pmClosed
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
HQ CWE Agra
112, Taj Road, Agra Cantt
SPL REPAIR / REPLACEMENT OF BER TRANSFORMERS 11/0.433 KV AND ALLIED WORKS AT FATEHGARH CANTT
2026_MES_747032_1
86266/E8
Open Tender
Electrical and Maintenance Works
Item Rate
180 days
Fatehgarh
MES contractors enlisted for Class C and above and category b(ii) for unenlisted contractors meeting the enlistment criteria corresponding to value class and category of work
8 documents required · 8 mandatory
₹1,000
AGE (I) Fatehgarh
₹1.1 L
2 Jan 2026
2 Jan 2026
11 Feb 2026
2 Jan 2026
4 Feb 2026
16 Jan 2026
2 Jan 2026 - 9 Jan 2026
Supply, fixing, testing and commissioning Transformer step down 11/0.433 KVA complete outdoor/indoor copper wound of capacity 160 KVA complete all as specified and directed. Supplying, Installing, Connecting, Commissioning and Testing of Transformer, Step Down, Outdoor Type, 11 KV / 433 V [at No load], AC, 3 Phase, 50 Hz, of 160 KVA capacity,Copper Wound, Oil immersed, CRGO Core type Naturally cooled, Built-up with class "A" insulation, having Primary Voltage [HT] 11 KV and Secondary Voltage [LT] of 433 Volts, Delta connected on 11 KV Side & Star connected on 433 Volts side, designed & constructed with particular reference to Tropical Condition, conforming to IS – 1180 [Part-I], energy efficient level III with latest amendment complete all as specified and as directed and comprising of the following Specification and Fittings:(Continuous Rating : 160 KVA, No-Load Voltage Ratio : 11 KV / 433 V , Tapping on HV [%] : ± 7.5, ± 5, ± 2.5, Phase & Frequency : 3 Phase & 50 Hz, Connection : Delta Star, Vector Group : DYN 11, Cooling : ONAN, Type : Outdoor) Make: ABB, Crompton Greaves and M/s. Indian Transformers and Electricals Pvt Ltd, Gurgaon. Fittings:[a] Externally hand operated Off–Circuit Tap Switch with position indicator and locking device.[b] Conservator with Oil Gauge, filling hole with plug & drain hole with plug, [c] Undercarriage with four plain rollers, [d] Oil filling hole cum air release plug, [e] Drain Valve cum Sampling Valve, [f] Top Filter Valve with Plug, [g] Rating Plate with Diagram Plate,[h] Lifting lugs for Transformer,[j] Lifting lugs for Core,[k] Earthing Terminals, [l] Thermometer Pockets, [m] Silica Gel Breather,[n] Explosion Vent, [o] 150mm size Oil Temperature indicator, dial type with alarm and trip contacts,[p] 150mm size Winding Temperature indicator, dial type with alarm and trip contacts,[q] Buchholz Relay with 2 Shut-Off Valves,[r] Marshalling Box with Double Window, [s] OCTC.
Note: [a] The Transformers shall also be provided with following Terminal Arrangement & Fittings and rate quoted against respective item is deemed to be included for the same:Terminal Arrangement: [i] HV & LV Side: Cable Box, [ii] Quad furcating cable box with five compression glands for PVC Cable and One additional neutral terminal shall be brought out separately for earthing purpose on LV Side. [iii] First filling of new and unused Transformer Oil [IS – 335 Marked], filtered and tested up to 60KV dielectric strength at 2.5mm air gap between testing electrodes. Certification of dielectric strength shall be submitted by the Contractor after filling the oil. Transformer Oil shall be got tested. [iv] Apart from routine tests mentioned in these tender documents and relevant IS, pre-commissioning inspection of Transformer shall be carried out by Senior Electrical Inspector / Electrical Inspector. [b] All necessary arrangements with devices for measuring the temperature of core winding and oil, [c] Provision of Brick Masonry Platform for Transformer with Brickwork with old size Bricks in Cement Mortar 1:6 including excavation and earth work in any type of soil, PCC foundation with 100mm thick PCC 1:4:8, Type D2 using 40mm graded aggregate, PCC flooring with 40 mm thick PCC, 1:2:4, Type B1, using 20mm graded aggregate, over a sub base of 75mm thick PCC 1:4:8, Type D2, using 40mm graded aggregate over approved earth filling and rendering in CM 1:4, 20 mm thick over brick walls and applying three coats of white wash etc complete all as specified and as directed.
Supplying, Installing, Connecting, Commissioning and Testing of Transformer, Step Down, Outdoor Type, 11 KV / 433 V [at No load], AC, 3 Phase, 50 Hz, of 250 KVA capacity,Copper Wound, Oil immersed, CRGO Core type Naturally cooled, Built-up with class "A" insulation, having Primary Voltage [HT] 11 KV and Secondary Voltage [LT] of 433 Volts, Delta connected on 11 KV Side & Star connected on 433 Volts side, designed & constructed with particular reference to Tropical Condition, conforming to IS – 1180 [Part-I], energy efficient level III with latest amendment complete all as specified and as directed and comprising of the following Specification and Fittings:(Continuous Rating : 250 KVA, No-Load Voltage Ratio : 11 KV / 433 V , Tapping on HV [%] : ± 7.5, ± 5, ± 2.5, Phase & Frequency : 3 Phase & 50 Hz, Connection : Delta Star, Vector Group : DYN 11, Cooling : ONAN, Type : Outdoor) Make: Make: ABB, Crompton Greaves and M/s. Indian Transformers and Electricals Pvt Ltd, Gurgaon. Fittings:[a] Externally hand operated Off–Circuit Tap Switch with position indicator and locking device.[b] Conservator with Oil Gauge, filling hole with plug & drain hole with plug, [c] Undercarriage with four plain rollers, [d] Oil filling hole cum air release plug, [e] Drain Valve cum Sampling Valve, [f] Top Filter Valve with Plug, [g] Rating Plate with Diagram Plate,[h] Lifting lugs for Transformer,[j] Lifting lugs for Core,[k] Earthing Terminals, [l] Thermometer Pockets, [m] Silica Gel Breather,[n] Explosion Vent, [o] 150mm size Oil Temperature indicator, dial type with alarm and trip contacts,[p] 150mm size Winding Temperature indicator, dial type with alarm and trip contacts,[q] Buchholz Relay with 2 Shut-Off Valves,[r] Marshalling Box with Double Window, [s] OCTC.
Note: [a] The Transformers shall also be provided with following Terminal Arrangement & Fittings and rate quoted against respective item is deemed to be included for the same:Terminal Arrangement: [i] HV & LV Side: Cable Box, [ii] Quad furcating cable box with five compression glands for PVC Cable and One additional neutral terminal shall be brought out separately for earthing purpose on LV Side. [iii] First filling of new and unused Transformer Oil [IS – 335 Marked], filtered and tested up to 60KV dielectric strength at 2.5mm air gap between testing electrodes. Certification of dielectric strength shall be submitted by the Contractor after filling the oil. Transformer Oil shall be got tested. [iv] Apart from routine tests mentioned in these tender documents and relevant IS, pre-commissioning inspection of Transformer shall be carried out by Senior Electrical Inspector / Electrical Inspector., [b] All necessary arrangements with devices for measuring the temperature of core winding and oil, [c] Provision of Brick Masonry Platform for Transformer with Brickwork with old size Bricks in Cement Mortar 1:6 including excavation and earth work in any type of soil, PCC foundation with 100mm thick PCC 1:4:8, Type D2 using 40mm graded aggregate, PCC flooring with 40 mm thick PCC, 1:2:4, Type B1, using 20mm graded aggregate, over a sub base of 75mm thick PCC 1:4:8, Type D2, using 40mm graded aggregate over approved earth filling and rendering in CM 1:4, 20 mm thick over brick walls and applying three coats of white wash etc complete all as specified and as directed.
Supplying, Installing, Connecting, Commissioning and Testing of Transformer, Step Down, Outdoor Type, 11 KV / 433 V [at No load], AC, 3 Phase, 50 Hz, of 315 KVA capacity,Copper Wound, Oil immersed, CRGO Core type Naturally cooled, Built-up with class "A" insulation, having Primary Voltage [HT] 11 KV and Secondary Voltage [LT] of 433 Volts, Delta connected on 11 KV Side & Star connected on 433 Volts side, designed & constructed with particular reference to Tropical Condition, conforming to IS – 1180 [Part-I], energy efficient level III with latest amendment complete all as specified and as directed and comprising of the following Specification and Fittings:(Continuous Rating : 250 KVA, No-Load Voltage Ratio : 11 KV / 433 V , Tapping on HV [%] : ± 7.5, ± 5, ± 2.5, Phase & Frequency : 3 Phase & 50 Hz, Connection : Delta Star, Vector Group : DYN 11, Cooling : ONAN, Type : Outdoor) Make: Make: ABB, Crompton Greaves and M/s. Indian Transformers and Electricals Pvt Ltd, Gurgaon. Fittings:[a] Externally hand operated Off–Circuit Tap Switch with position indicator and locking device.[b] Conservator with Oil Gauge, filling hole with plug & drain hole with plug, [c] Undercarriage with four plain rollers, [d] Oil filling hole cum air release plug, [e] Drain Valve cum Sampling Valve, [f] Top Filter Valve with Plug, [g] Rating Plate with Diagram Plate,[h] Lifting lugs for Transformer,[j] Lifting lugs for Core,[k] Earthing Terminals, [l] Thermometer Pockets, [m] Silica Gel Breather,[n] Explosion Vent, [o] Double Float Buchholz with alarm and trip contacts including control cable of copper conductor of size & length from Marshalling Box to Relay of VCB, [p] 150mm size Oil Temperature indicator, dial type with alarm and trip contacts,[q] 150mm size Winding Temperature indicator, dial type with alarm and trip contacts,[r] Buchholz Relay with 2 Shut-Off Valves,[s] Marshalling Box with Double Window, [t] OCTC.
Note: [a] The Transformers shall also be provided with following Terminal Arrangement & Fittings and rate quoted against respective item is deemed to be included for the same:Terminal Arrangement:[i] HV & LV Side: Cable Box,[ii] Quad furcating cable box with five compression glands for PVC Cable and One additional neutral terminal shall be brought out separately for earthing purpose on LV Side.[iii] First filling of new and unused Transformer Oil [IS – 335 Marked], filtered and tested up to 60KV dielectric strength at 2.5mm air gap between testing electrodes. Certification of dielectric strength shall be submitted by the Contractor after filling the oil. Transformer Oil shall be got tested.[iv] Apart from routine tests mentioned in these tender documents and relevant IS, pre-commissioning inspection of Transformer shall be carried out by Senior Electrical Inspector / Electrical Inspector., [b] All necessary arrangements with devices for measuring the temperature of core winding and oil, complete all as specified and as directed.
Supplying, Installing, Connecting, Commissioning and Testing of Transformer, Step Down, Outdoor Type, 11 KV / 433 V [at No load], AC, 3 Phase, 50 Hz, of 400 KVA capacity,Copper Wound, Oil immersed, CRGO Core type Naturally cooled, Built-up with class "A" insulation, having Primary Voltage [HT] 11 KV and Secondary Voltage [LT] of 433 Volts, Delta connected on 11 KV Side & Star connected on 433 Volts side, designed & constructed with particular reference to Tropical Condition, conforming to IS – 1180 [Part-I], energy efficient level III with latest amendment complete all as specified and as directed and comprising of the following Specification and Fittings:(Continuous Rating : 250 KVA, No-Load Voltage Ratio : 11 KV / 433 V , Tapping on HV [%] : ± 7.5, ± 5, ± 2.5, Phase & Frequency : 3 Phase & 50 Hz, Connection : Delta Star, Vector Group : DYN 11, Cooling : ONAN, Type : Outdoor) Make:Make: ABB, Crompton Greaves and M/s. Indian Transformers and Electricals Pvt Ltd, Gurgaon. Fittings:[a] Externally hand operated Off–Circuit Tap Switch with position indicator and locking device.[b] Conservator with Oil Gauge, filling hole with plug & drain hole with plug, [c] Undercarriage with four plain rollers, [d] Oil filling hole cum air release plug, [e] Drain Valve cum Sampling Valve, [f] Top Filter Valve with Plug, [g] Rating Plate with Diagram Plate,[h] Lifting lugs for Transformer,[j] Lifting lugs for Core,[k] Earthing Terminals, [l] Thermometer Pockets, [m] Silica Gel Breather,[n] Explosion Vent, [o] Double Float Buchholz with alarm and trip contacts including control cable of copper conductor of size & length from Marshalling Box to Relay of VCB, [p] 150mm size Oil Temperature indicator, dial type with alarm and trip contacts,[q] 150mm size Winding Temperature indicator, dial type with alarm and trip contacts,[r] Buchholz Relay with 2 Shut-Off Valves,[s] Marshalling Box with Double Window, [t] OCTC.
Note: [a] The Transformers shall also be provided with following Terminal Arrangement & Fittings and rate quoted against respective item is deemed to be included for the same:Terminal Arrangement:[i] HV & LV Side: Cable Box,[ii] Quad furcating cable box with five compression glands for PVC Cable and One additional neutral terminal shall be brought out separately for earthing purpose on LV Side.[iii] First filling of new and unused Transformer Oil [IS – 335 Marked], filtered and tested up to 60KV dielectric strength at 2.5mm air gap between testing electrodes. Certification of dielectric strength shall be submitted by the Contractor after filling the oil. Transformer Oil shall be got tested.[iv] Apart from routine tests mentioned in these tender documents and relevant IS, pre-commissioning inspection of Transformer shall be carried out by Senior Electrical Inspector / Electrical Inspector., [b] All necessary arrangements with devices for measuring the temperature of core winding and oil, complete all as specified and as directed. Note for item No.1 to 4 :- Old transformer shall be dismentalled & deposited to MES Yard by contractor. Rates are deemed to be included in quoted rate.
M&L for earthing complete with galvanised steel earth plate electrode 600 x 600 x 6 mm thick, burried directly into the ground (earth pit not less than 2.25 mtr below ground level) with top edge of the plate not less than 1.5 mtr below normal ground level, connected to GI earth strip 32x6 mm by means of bolts, nuts, check nuts, and washers of galvanised iron or steel all as shown in electrical plate No. 3 connected to earthing test point all as specified or indicated including excavation and connected earth work, PCC chamber and cover, watering pipe, funnel wire mesh but with protection pipe and test on completion including dismantling unserviceable erthing complete all as directed.
Excavation in trenches/ foundation in soft/ loose soil not exc. 1.5 metre wide and n'exc. 1.50m deep for HT under ground cable/pole foundation and getting out including forming bottom surface to required level or slope, complete all as specified and directed
Returning filling including spreading leveling watering and well ramming in layers not exc 25Cm in soft/ loose soil, complete all as specified and directed.
Removing excavated material in soft/ loose soil n'exc 50M and depositing where directed at a level n'exc1.5M above the starting point, complete all as specified and directed.
Supply and laying in replacement of PCC cover DWC high density polyethelene pipes having dia 76/90 mm, dia as per site equitpmet having corrugation on outer the wall and plain surfaces on the inner wall conforming to IS-14930 (Part-I & II) for protection of under ground cable laid along pole/along wall/ in PCC/GL Roof and including all fittings as required at site complete all as specified and directed.
Supply, laying & testing in replacement cable XLPE insulated, screened, PVC bedded, galvanized steel strip or wire armoured, electric power cables (heavy duty)with stranded aluminium conductor, 11000 volts Earthed grade, of size 3 core cross sectional area 95 Sqmm complete all as specified and directed
M&L in replacement of indoor end terminal joints heat shrinkable Suitable for HT 11000V (Earthed), XLPE insulated armoured Heavy duty under ground cable including joint kits and labour complete for making joints suitable for aluminium conductor cable of cross sectional area 95 Sqmm 3 Core all as specified and directed.( Make : 3M/Denson/Raychem)
M&L in replacement of outdoor end terminal joints heat shrinkable Suitable for HT 11000V (Earthed), XLPE insulated armoured Heavy duty under ground cable including joint kits and labour complete for making joints suitable for aluminium conductor cable of cross sectional area 95 Sqmm 3 Core all as specified and directed.( Make : 3M/Denson/Raychem)
M & L in replacement of GI tubing light grade for passing through cables under the floor ,along the wall or along the pole of 80 mm bore and fixed to the poles/walls with suitable size of MS clamps and nut and botls/washers etc including taking down old GI tubing complete all as specified.
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 0.12 MB
TENDER.pdf
Tender Documents • 0.40 MB
BOQ_836522.xls
BOQ • 10.26 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .