Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹13.9 LAccepted-AOC | L1 | Accepted-AOC Lowest Bid Value. | |
| 2 | L2₹14.5 L+₹51,539 (3.69%)Rejected-AOC NO 9 1ST FLOOR C J N HERITAGE PWD MAIN ROAD AKASH NAGAR B NARAYANAPURA DOORAVANI NAGAR BANGALORE 560016 | BANGALORE | BENGALURU URBAN | KARNATAKA | 560016 | L2 | Rejected-AOC Higher Bid Value. | |
| 3 | L3₹14.9 L+₹91,514 (6.55%)Rejected-AOC BUILDING NO FLAT NO 19 6TH CROSS ROAD SANJEEVINI NAGAR MUDALAPALYA BANGALORE 560072 | BANGALORE | BANGALORE | KARNATAKA | 560072 | L3 | Rejected-AOC Higher Bid Value. | |
| 4 | L4₹15.6 L+₹1.7 L (11.9%)Rejected-AOC NO S 7 2ND CROSS 2ND MAIN KEB LAYOUT SANJAYANAGAR BANGALORE 560094 | BENGALURU URBAN | KARNATAKA | 560094 | L4 | Rejected-AOC Higher Bid Value. | |
| 5 | Rejected-Technical | - | Rejected-Technical Rejected as no enlisted in appropriate category. |
Tender Value
Refer Docs
EMD Value
₹30,000
Closing Date
26 Dec 2020, 6:00 pmClosed
GE (AF) BANGALORE
GE (AF) BANGALORE HQ TC AIR FORCE BANGALORE 560006
PROVISION OF AIR HANDLING UNIT (AHU) WITH HEPA FILTERS FOR BMT CENTRE IN THE FAMILY WING COMPLEX AT CHAFB
2020_MES_390575_2
8719/GE-52
Open Tender
Civil Works
Item Rate
180 days
CH (AF) BANGALORE
AS PER NIT
5 documents required · 5 mandatory
₹500
Yes
GE (AF) BANGALORE
₹30,000
Yes
22 Jan 2021
4 Dec 2020
28 Dec 2020
4 Dec 2020
26 Dec 2020
14 Dec 2020
5 Dec 2020 - 10 Dec 2020
Amount
Supply, installation, testing and commissioning of Air cooled condensing unit capacity of 5.5 TR all as specified and as directed. Make:Bluestar/Voltas/Carrier
Supply and laying of Refrigerant piping from AHU to Condensing unit usig 16 swg hard drawn copper pipe, fittings and supports for Liquid &Suction Line. The liquid line should be painted with approved colour enamel paint and Suction pipe shuld be insulated with 19mm thk nitrile rubber tubular foam all asspecified and as directed.
Supply and installation of Thermostatic Expansion valve and filter drier for condensing unit. Make:Danfoss/Emersson all as specified and as directed.
Supply and installation of 25mm/32 mm Drain piping with 6mm thick nitrile rubber tubular insulation all as specified and as directed.
Materials & Labour for charging of refrigerant R407/R410a all as specified and as directed
Supply and installation of hand/factory fabricated ducting made out of Aluminium sheets with proper gasket, supports ,rods,angle flanges etc and fabricated as per SMACNA standard.All flange joints shall be sealed with RTV Sealent to make it air tight 22 Gauge Aluminium sheet all as specified and as directed.
Supply and installation of hand/factory fabricated ducting made out of Aluminium sheets with proper gasket, supports ,rods,angle flanges etc and fabricated as per SMACNA standard.All flange joints shall be sealed with RTV Sealent to make it air tight 20 Gauge Aluminium sheet all as specified and as directed.
Supply and installation of 19 mm thk Aluminium foil faced self adhesive XLPE sheet for insulating the supply air duct all as perstandard and as directed Make :Torcelen/Paramount
Supply and installation of 13 mm thk Aluminium foil faced self adhesive XLPE sheet for insulating the supply air duct all as perstandard and as directed Make :Torcelen/Paramount
Supply and installation of Plenum box for HEPA filter made of 1mm thk 304 grade SS sheet with necessery framing arrangement, supply air collars with VCD, perforated SS grill andsupports all as per standard and as directed. Size: 1800 mm x 1800 mm x 500 mm
Supply and fixing of flanged type HEPA filters efficiency not less than 99.97% for particles down to 0.3 micron all as specified and as directed.size ‐ 600mm x 600mm x 150mm Make: Aerosole/Johnfowler/AAF/Trijama
Supply and installation of return air grill (openable dome bolt fit type) in BM OT area made out of perforated plate SS‐304complete with fixing frame gasket and damper all as specifiedand as directed. Make :Caryaire/Aerosole/Ajantha/Airmaster
Supply and fixing of Heater bank 3KW with safety thermostate all as specified and as directed. Make :Dasspass/Rapid Controls
Supply and fixing of Magnehelic gauges 100 mm ,range 0‐60 pascle WG With SS box and probe at different rooms with pvc tube all as specified and as directed. Make:Dwyer/Sensocon
Supply and laying of GI perforated 16 SWG thickness cable tray with cover of size 200 mm x 50mm including coupler plates,bends and cable tie etc all specified and as directed
Supply and laying of XLPE insulated 6 sqmm 4 core copper armoured cables, glands and lugs,Cables should be layed in GI perforated cable tray for power supply from Control panel to ODUall as specified and as directed.
Supply and laying of XLPE insulated 4 sqmm 4 core copper armoured cables, glands and lugs,Cables should be layed in GI perforated cable tray for power supply from controll panel to AHUand Heater Bankall as specified and as directed.
Supply and laying of XLPE insulated 2.5 sqmm 3 core copper armoured cables, glands and lugs,Cables should be layed in GI perforated cable tray for power supply from controll panel.all as specified and directed
Supply and laying of XLPE insulated 1 sqmm 4 core copper armoured cables, glands and lugs,Cables should be layed in GI perforated cable tray for all controll wiring all as specified and asdirected.
Supply, installing, testing and commisioning of LT cubical panel board 440 volts , 50 Hz , 3 phase , 4 wire ,In door type IP-65 and above , vermin, dust proof, front operated with adequate air ventilation at sides and back fabricated out of 2 mm thick CRCA sheet with shutter and locking arrangements cable lugs ,cable gland etc.including provision for taking out incoming and outgoing cables duly marked with relevetted letter plates of appropriate size for ech feeder cables danger board etc , suitable to accomodate and including the following mentioned fittings , floor mounted with PCC 1:2:4, type B1 platform of 20 cm height suitable nut bolts, washer etc. for grouting , and painting with power coated epoxy finish of approved colour over a coat of red oxide primer with all accessories for HVAC system mounted near AHU and Panel should also have necessary interlocking between AHU & condensing Units all as specified and as directed. Make: CPRI approved all as specified and as directed comprising the following:- (i) MCCB 63A 4 pole 25KA incoming -01 No (ii)MCB 32 A TPN for ODU-02 Nos (iii)MCB 25 A TPN for AHU, Exhaust fan, heater bank-03 Nos (iv)MCB SPN 6 A for control circuit (v)5.5 kw VFD starter for AHU (vi)2.2kw DOL starter for Exhaust fan (vii)1.5 kw starter for heater bank (viii) Digital type multi function meter (ix)On/Off indication lights (x)LED Phase indicator (xi)Auto /manual switch (xii)Local/Remot switch (xiii)digital thermostate, (xv)digital humidystate (x)programmable Logic controller
Glacier Cooling Solutions Private Limited
RAHUL ENTERPRISES
UNIVERSAL ENGINEERING
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .